2018-12-19 07:09:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL SHOWING UL |
| OR OTHER NRTL LISTINGS FOR GENERATOR AND TRANSFER |
| SWITCH. FBC 107.2.1 NEC 90.7 110.2 110.3B |
| |
| 2. LICENSE NUMBER ON PERMIT IS FOR CAL BRUCE KEMP ONLY |
| DBA IS DOUG'S INDUSTRIAL REFRIDGERATION. LIGHTHOUSE |
| ENERGY IS NOT ASSOCIATED WITH THIS LICENSE. LIGHTHOUSE |
| ENERGY IS WHO HAS SIGNED THE PLAN WHICH IS NOT |
| ACCEPTABLE. |
| |
| ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |
| |