Plan Review Details - Permit 18120423
Plan Review Stops For Permit 18120423
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-09 Cont ID  
Sent By jduprey Date 2019-01-09 Time 09:56 Rev Time 0.00
Received By jduprey Date 2019-01-09 Time 09:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By pvalenti Date 2019-01-02 Time 13:47 Rev Time 0.00
Received By pvalenti Date 2019-01-02 Time 13:47 Sent To E
Notes
2019-01-02 13:56:42****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION: MISSING
 CONNECTION DETAILS (GENERATOR TO SLAB). PROVIDE DETAILS
 FOR: CONNECTORS (STRAPS/ANGLE CLIPS), ANCHORS
 (TYPE/SIZE), AND EDGE DISTANCE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-09 Cont ID  
Sent By fgiaquin Date 2019-01-09 Time 09:29 Rev Time 0.00
Received By fgiaquin Date 2019-01-09 Time 09:29 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-04 Cont ID  
Sent By fgiaquin Date 2019-01-04 Time 07:11 Rev Time 0.00
Received By fgiaquin Date 2019-01-04 Time 06:57 Sent To I
Notes
2019-01-04 07:09:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE ONE-LINE DIAGRAM WITH WIRE SIZES
 AND CONDUIT SIZES TO METER-CAN, NEW ATS, GENERATOR, AND
 FROM ATS TO EXISTING 125AMP PANEL AND GENERATOR OCP.
 FBC 107.2.1
  
 2. PROVIDE LOAD CALCULATION SHOWING LOAD SHEDDING. NEC
 220
  
 3. VALUE IS LOW, RAISE VALUE. VALUE TO INCLUDE ALL
 MATERIALS (GENERATOR INCLUDED) AND LABOR. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 4. PLAN SHOWS 20KW GENERATOR BUT SPEC SHEETS SHOW 22KW
 GENERATOR. PROVIDE CLARIFICATION OF WHAT IS ACTUALLY
 BEING INSTALLED. FBC 107.2.1
  
 5. LICENSE # 13004086 IS ASSOCIATED WITH BRUCE KEMP AND
 DBA "DOUG'S INDUSTRIAL REFRIDGERATION INC". PLAN IS
 SIGNED BY LIGHTHOUSE ENERGY. ELECTRICAL PLAN MUST BE
 SIGNED BY ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-09 Cont ID  
Sent By jduprey Date 2019-01-09 Time 10:04 Rev Time 0.00
Received By jduprey Date 2019-01-09 Time 09:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-04 Cont ID  
Sent By fgiaquin Date 2019-01-04 Time 07:12 Rev Time 0.00
Received By fgiaquin Date 2018-12-12 Time 13:30 Sent To  
Notes
2018-12-13 13:30:39ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-19 Cont ID  
Sent By mcruz Date 2018-12-19 Time 15:11 Rev Time 0.00
Received By mcruz Date 2018-12-19 Time 15:09 Sent To B
Notes
***NONE***