Plan Review Details - Permit 18120419
Plan Review Stops For Permit 18120419
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-12-13 Cont ID  
Sent By cthroop Date 2018-12-13 Time 08:01 Rev Time 0.00
Received By cthroop Date 2018-12-13 Time 07:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-12-13 Cont ID  
Sent By scaldero Date 2018-12-13 Time 09:30 Rev Time 0.00
Received By scaldero Date 2018-12-13 Time 09:29 Sent To  
Notes
2018-12-13 09:30:30PERMIT # 18120419
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 2) TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 3) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 5) GENERATORS AND OTHER INTERNAL COMBUSTION POWER
 SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5
 FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-17 Cont ID  
Sent By sholder Date 2018-12-17 Time 10:17 Rev Time 0.00
Received By sholder Date 2018-12-12 Time 09:17 Sent To  
Notes
***NONE***