Plan Review Details - Permit 18120357
Plan Review Stops For Permit 18120357
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-02-22 Cont ID  
Sent By tklarge Date 2019-02-22 Time 05:41 Rev Time 0.00
Received By tklarge Date 2019-02-22 Time 05:21 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-02-07 Cont ID  
Sent By tklarge Date 2019-02-07 Time 12:44 Rev Time 0.00
Received By tklarge Date 2019-02-04 Time 06:12 Sent To  
Notes
2019-02-07 12:42:541) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE NEW
 DRYER.2ND REQUEST. 2017 FBC- RES. SEC.G2407.1, G2439.4.
 2) YOU HAVE SHOWN THE LOCATION OF THE DRYER ON THE
 PLAN. IS THIS IN A SEPARATE ROOM WITH A DOOR? NO DOOR?
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-01-23 Cont ID  
Sent By tklarge Date 2019-01-23 Time 12:59 Rev Time 0.00
Received By tklarge Date 2019-01-23 Time 12:41 Sent To  
Notes
2019-01-23 12:57:551) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS). 2ND REQUEST.
 2) WITH THE TANKLESS WATER HEATER AND DRYER, THE 3/4
 INCH GAS LINE IS UNDERSIZED BASED ON THE DISTANCE IN
 TABLE 402.4(2). THE LINE SHALL BE INCREASED TO 1 INCH
 OR THE GAS PRESSURE OF THE SYSTEM NEEDS TO BE INCREASED
 AND REGULATORS WILL BE REQUIRED AT THE APPLIANCES.2ND
 REQUEST.
 PROVISO:
 A SEPARATE PERMIT WILL BE REQUIRED FOR THE ASSOCIATED
 ELECTRIC WORK.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-12-26 Cont ID  
Sent By tklarge Date 2018-12-26 Time 05:26 Rev Time 0.00
Received By tklarge Date 2018-12-26 Time 05:13 Sent To  
Notes
2018-12-26 05:26:161) THERE IS AN APPLICATION IN THE PERMIT PACKAGE FOR A
 GAS DRYER BUT IT IS NOT SHOWN ON THE GAS RISER DIAGRAM.
 SHOW THE GAS DRYER ON THE GAS RISER AND SHOW THE BTU
 LOAD OF THE DRYER ON THE PLAN. REFER TO THE 2017
 FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4
 AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21).
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
 4) WITH THE ADDED DRYER, IT APPEARS THAT THE 3/4 INCH
 GAS LINE MAY BE UNDERSIZED BASED ON THE DISTANCE IN
 TABLE 402.4(2).
 5) SHOW THE LOCATION OF THE DRYER ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT AN ADDITIONAL APPLICATION FOR THE PLUMBING
 CONNECTIONS FOR THE TANKLESS WATER HEATER.
 7) A SEPARATE PERMIT WILL BE REQUIRED FOR THE
 ASSOCIATED ELECTRIC WORK.
 8) SHOW THE LOCATION OF THE GAS METER ON THE HOUSE
 PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-02-22 Cont ID  
Sent By tklarge Date 2019-02-22 Time 05:41 Rev Time 0.00
Received By tklarge Date 2019-02-22 Time 05:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-07 Cont ID  
Sent By tklarge Date 2019-02-07 Time 12:44 Rev Time 0.00
Received By tklarge Date 2019-01-30 Time 13:50 Sent To  
Notes
2019-01-31 13:50:34RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-23 Cont ID  
Sent By tklarge Date 2019-01-23 Time 12:59 Rev Time 0.00
Received By tklarge Date 2019-01-18 Time 14:18 Sent To  
Notes
2019-01-22 14:18:29RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-26 Cont ID  
Sent By tklarge Date 2018-12-26 Time 05:27 Rev Time 0.00
Received By tklarge Date 2018-12-11 Time 13:30 Sent To  
Notes
2018-12-12 13:30:59PLUMB <5K

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-26 Cont ID  
Sent By tklarge Date 2018-12-26 Time 05:26 Rev Time 0.00
Received By tklarge Date 2018-12-26 Time 05:26 Sent To I
Notes
***NONE***