Plan Review Details - Permit 18120194
Plan Review Stops For Permit 18120194
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-20 Cont ID  
Sent By jgomez Date 2018-12-19 Time 16:52 Rev Time 0.00
Received By jgomez Date 2018-12-19 Time 07:35 Sent To  
Notes
2018-12-19 08:19:38RESIDENTIAL (R3) FOUNDATION ONLY PERMIT, BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FOUNDATION PLAN WAS NOT SUBMITTED. 107.2.1 CITY
 AMENDMENTS.
  
 2- FLOOD ZONE AE WITH BASE FLOOD ELEVATION OF 7'-0"
 (NAVD OF 1988). POWDER ROOM LOCATED IN THE GARAGE NEEDS
 TO BE ELEVATED TO 9'-0".
 CITY ORDINANCE 4729-17 SEC. 18-34 THE FINISH FLOOR
 ELEVATION NEEDS TO BE TWO FEET FREEBOARD ABOVE THE BASE
 FLOOD ELEVATION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  
  
  
 NOTE: MAIN HOUSE AND FOUNDATION PERMITS WERE
 SIMULTANEOUSLY REVIEWED. MAIN HOUSE PERMIT WAS APPROVED
 WITH PROVISO. CONTRACTOR TO COORDINATE THIS TWO PERMITS
 TO AVOID CONFLICTS/DELAYS. SEE PROVISO BELOW:
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1-SHOW ATTIC ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN
 THE 1ST & 2ND FLOOR.
 2-PROVIDE PRODUCT APPROVAL FOR: A)WINDOW MULLIONS AND
 SPECIFY MULLION SIZE. B)DOORS PRODUCT APPROVAL
 FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE SHUTTERS
 PRODUCT APPROVAL AND COMPLETE INSTALLATION SCHEDULE.
 C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28: CLEARLY MARK
 WHICH ASSEMBLY L IS GOING TO BE USED. D) SHUTTERS SHOWN
 ON EXTERIOR ELEVATIONS AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE. E) WATER PROOFING AT TERRACE.
 PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE
 MATERIAL SPECIFIED BY THE DESIGNER OF RECORD. F)
 DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS.
 3-ALUMINUM TRELLIS UNDER SEPARATE PERMIT PER
 ARCHITECT'S RESPONSE LETTER.
 4-REVISE ENTRY FOYER FINISH ELEVATION IN ALL PLANS. PER
 JOHN MELHORN, THE ELEVATION WILL BE 9'-0" (NAVD OF
 1988) NOT 8'-6".
 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS.
 PROVIDE PRODUCT APPROVAL AND REVISE PLANS SHOWING
 LOCATION. ALSO, POWDER ROOM LOCATED IN THE GARAGE NEEDS
 TO BE ELEVATED TO 9'-0".
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-18 Cont ID  
Sent By jleahy Date 2018-12-18 Time 17:43 Rev Time 0.00
Received By jleahy Date 2018-12-18 Time 17:43 Sent To  
Notes
2018-12-18 17:46:28FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN, WHAT ARE YOU GOING TO PUT IN THE
 SLAB????

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2018-12-07 Cont ID  
Sent By pleduc Date 2018-12-07 Time   Rev Time 0.00
Received By pleduc Date 2018-12-07 Time 09:52 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-12-06 Cont ID  
Sent By fmittner Date 2018-12-06 Time 10:40 Rev Time 0.00
Received By fmittner Date 2018-12-06 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-20 Cont ID  
Sent By jgomez Date 2018-12-20 Time 08:58 Rev Time 0.00
Received By jgomez Date 2018-12-06 Time 10:21 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-12-19 Cont ID  
Sent By jgomez Date 2018-12-19 Time 07:46 Rev Time 0.00
Received By jgomez Date 2018-12-19 Time 07:42 Sent To  
Notes
2018-12-19 07:47:1612/18/18 STAMPED SET OF PLANS BY IMPACT FEE OFFICE IN
 PROJECTDOX. $0 AMOUNT DUE. MU18-37645

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2018-12-19 Cont ID  
Sent By jgomez Date 2018-12-19 Time 16:59 Rev Time 0.00
Received By jgomez Date 2018-12-19 Time 16:59 Sent To  
Notes
2018-12-19 16:59:14 
 1-ELEVATION CERTIFICATES ARE REC'D DURING CONSTRUCTION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-20 Cont ID  
Sent By jgomez Date 2018-12-20 Time 08:54 Rev Time 0.00
Received By jgomez Date 2018-12-20 Time 08:54 Sent To  
Notes
2018-12-20 08:56:17RESIDENTIAL (R3) FOUNDATION ONLY PERMIT, PLUMBING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FOUNDATION PLAN WAS NOT SUBMITTED. 107.2.1 CITY
 AMENDMENTS.
  
 2- FLOOD ZONE AE WITH BASE FLOOD ELEVATION OF 7'-0"
 (NAVD OF 1988). POWDER ROOM LOCATED IN THE GARAGE NEEDS
 TO BE ELEVATED TO 9'-0".
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-12-19 Cont ID  
Sent By jgomez Date 2018-12-19 Time 16:56 Rev Time 0.00
Received By jgomez Date 2018-12-19 Time 16:52 Sent To  
Notes
2018-12-19 16:57:03 
 DOCUMENTS SUBMITTED ARE NOT DIGITALLY SIGNED. AFTER ALL
 PLAN REVIEWS HAVE PASSED, SUBMIT ONE PAPER ORIGINAL AT
 THE BUILDING DIVISION. THIS INCLUDES THE FOLLOWING
 DOCUMENTS:
  
 1. ENERGY CALCS, LOAD CALCS
  
 2- SOIL TEST REPORT.

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By fmittner Date 2018-12-06 Time 10:40 Rev Time 0.00
Received By fmittner Date 2018-12-06 Time 10:40 Sent To  
Notes
2018-12-06 10:51:51POOL EQUIPTMENT SHALL NOT BE IN FRONT SETBACK.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved