Plan Review Details - Permit 18111269
Plan Review Stops For Permit 18111269 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-07-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-07-29 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-07-26 |
Time |
07:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-04-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-04-08 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-04-04 |
Time |
17:04 |
Sent To |
|
|
Notes |
2019-04-08 17:01:32 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE | | LIST THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL | | STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN | | PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE | | WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT | | INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE | | CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS | | FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN | | AND SCOPE OF WORK FOR 2ND UNIT. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. PLAN REVIEW RESPONSE SHEET SUBMITTED WITH THIS | | RE-SUBMITTAL IS ADDRESSED TO THE DADE COUN TY BUILDING | | DEPT. AND IDENTIFIES THE SUBJECT PROPERTY AS 4519 NW | | 22ND CT & 4237 NW 23RD AVE. PLEASE REMOVE FROM | | SUBMITTAL. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 3. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK. | | THE PERMIT VALUATION AND PERMIT FEE MUST BE | | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED | | CONTRACTOR WOULD PROVIDE. | | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE | | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT | | RENTAL TO VERIFY VALUE. | | | | CITY OF WPB CHPT. 1 ? VALUE | | 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF | | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, | | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE | | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE | | DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, | | QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS | | (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE | | BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION | | OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT | | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, | | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, | | ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, | | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | DATA OF NATIONAL CONSTRUCTION | | COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), | | AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | BUILDING OFFICIAL. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2019-02-21 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-02-21 |
Time |
16:50 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-02-15 |
Time |
08:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-07-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-07-29 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-07-26 |
Time |
07:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-04-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-04-08 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-04-08 |
Time |
17:02 |
Sent To |
|
|
Notes |
2019-04-08 17:37:26 | ELECTRICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE | | LIST THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL | | STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN | | PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE | | WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT | | INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE | | CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS | | FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN | | AND SCOPE OF WORK FOR 2ND UNIT. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. NEW CHANGE IN SERVICE - | | 2A. STATE CONDUCTOR SIZE OF EXISTING SERVICE DROP. | | E3602.1 AMPACITY OF UNGROUNDED CONDUCTORS. | | 2B. IDENTIFY LOCATION OF SERVICE DISCONNECT. E3601.6.2 | | SERVICE DISCONNECT LOCATION. | | 2C. PROVIDE LOAD CALCULATIONS FOR BOTH NEW PANELS. | | UTILIZE RESIDENTIAL FORMULA TABLE E3602.2 | | 2D. PROVIDE AIC CALCULATIONS FOR BOTH NEW SERVICES. | | E3602.2 SERVICE LOAD. | | | | 3. ELECTRICAL NOTE #6 IS INCORRECT. AFCI PROTECTION IS | | REQUIRED PER THE FOLLOWING: E3902.16 ARC-FAULT | | CIRCUIT-INTERRUPTER PROTECTION. | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)] | | | | 4. ELECTRICAL PLAN SHOWS BOTH KITCHEN COUNTER TOP | | RECEPTACLES ARE SUPPLIED FROM A SINGLE 20AMP CIRCUT- | | #2. PLEASE SEE FBC R3703.2 AND CORRECT. | | E3703.2 KITCHEN AND DINING AREA RECEPTACLES. | | A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL | | BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE | | OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA, | | DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN | | COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF | | TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF | | WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER | | RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY, | | BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS | | FOR REFRIGERATION APPLIANCES. [210.11(C)(1) AND | | 210.52(B)(1) AND (B)(2)]. | | | | 5. CIRCUT #10 OVERCURRENT PROTECTION AND CONDUCTOR SIZE | | IS INCORRECT. E3703.4 BATHROOM BRANCH CIRCUITS AND | | TABLE E3702.14. | | A MINIMUM OF ONE 20-AMPERE BRANCH CIRCUIT SHALL BE | | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH | | CIRCUITS SHALL HAVE NO OTHER OUTLETS. [210.11(C)(3)]. | | | | 6. PANEL SCHEDULE ON PLAN PAGE A-1 IS LABELED WINDOW | | AND DOOR SCHEDULE. PLEASE CORRECT. 107.2.1 INFORMATION | | ON CONSTRUCTION DOCUMENTS. | | | | 7. OVERCURRENT PROTECTION FOR THE INDOOR AND OUTDOOR | | MINI-SPLIT A/C SYSTEM PROPOSES TWO SEPERATE SINGLE POLE | | 20AMP CIRCUTS. PROVIDE MANUFACTURERS SPCIFICATIONS TO | | VERIFY. E3702.11 BRANCH CIRCUITS FOR AIR-CONDITIONING | | AND HEAT PUMP EQUIPMENT. | | | | 8. PROVIDE A 125-VOLT, SINGLE PHASE, 15 OR 20 AMP | | RECEPTACLE OUTLET FOR THE SERVICING OF THE NEW | | MECHANICAL EQUIPMENT. E3901.12 HVAC OUTLET. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2019-02-21 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-02-21 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-02-15 |
Time |
08:18 |
Sent To |
|
|
Notes |
2019-02-21 15:15:29 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | 109.3 | | 2. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, | | 801.2, OR 901.2 AS APPLICABLE. | | 3. NOTE 3(?) STATES THAT RECEPTACLES SHALL BE TAMPER | | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT | | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE | | CORRECTION. NEC 406.12; FBC RE E4002.14 | | 4. PROVIDE LOCATION ON PLAN OF MINI-SPLIT OUTSIDE UNIT. | | PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING | | OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER | | CODE. NEC 210.63; FBC RE E3901.12; WPB FBC 107.2.1 | | 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | 6. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, | | E3609.3; WPB FBC 107.2.1 | | 7. PROVIDE CLARIFICATION FOR LOCATION OF ELECTRICAL | | PANEL. DOES THE PANEL HAVE THE REQUIRED CLEARANCE IF IT | | FACES THE RANGE? PROVIDE CORRECTION AS NEEDED. NEC | | 110.26; WPB FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
N |
Date |
2019-02-15 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2019-02-15 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2019-02-15 |
Time |
16:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-07-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-07-29 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-07-15 |
Time |
16:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-04-15 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2019-04-15 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2019-04-02 |
Time |
16:57 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-02-22 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-22 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-04 |
Time |
08:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2019-07-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-07-29 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-07-26 |
Time |
07:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2019-04-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-04-09 |
Time |
07:32 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-04-08 |
Time |
17:02 |
Sent To |
|
|
Notes |
2019-04-09 07:49:27 | MECANICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1.THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE LIST | | THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL | | STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN | | PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE | | WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT | | INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE | | CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS | | FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN | | AND SCOPE OF WORK FOR 2ND UNIT. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. MECHANICAL SCOPE OF WORK INCLUDES EXHAUST FANS, | | MINI-SPLIT AND DRYER EXHAUST. EXHAUST FANS MISSING FROM | | PLAN. NO DRYER SHOWN ON PLAN. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 3. PROVIDE ENERGY CALCULATIONS (MANUAL J), INCLUDE | | EQUIPMENT SIZING PER ACCA MANUAL S. M1401.3 EQUIPMENT | | AND APPLIANCE SIZING. | | | | 4. TWO SEPERATE 20 AMP CIRCUTS ARE PROPOSED FOR NEW | | MINI-SPLIT SYSTEM. PROVIDE MANUFACTURERS SPCIFICATIONS | | TO VERIFY POWER REQUIREMENTS. M1401.1 INSTALLATION | | | | 5. PROVIDE SURVEY. SHOW LOCATION OF NEW CONDENSING | | UNIT. PROVIDE DISTANCE TO PROPERTY LINE. 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 6. PROVIDE NOTE ON PLAN TO PROVIDE LOCKING ACCESS | | PORTS. M1411.8 LOCKING ACCESS PORT CAPS. | | | | 7. PROVIDE DETAIL OF CONDENSATE DISPOSAL PIPING ROUTING | | THROUGH BUILDING. M1411.3 CONDENSATE DISPOSAL. | | | | 8. PROVIDE A 125-VOLT, SINGLE PHASE, 15 OR 20 AMP | | RECEPTACLE OUTLET FOR THE SERVICING OF THE NEW | | MECHANICAL EQUIPMENT. E3901.12 HVAC OUTLET. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2019-02-21 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2019-02-21 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2019-02-21 |
Time |
15:13 |
Sent To |
|
|
Notes |
2019-02-21 15:24:22 | PLAN DENIED | | PROVIDE MORE INFORMATION ON MECHANICAL PLAN. | | PER SECTION 107 FBC. 2017 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2019-07-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-07-29 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-07-26 |
Time |
07:23 |
Sent To |
|
|
Notes |
2019-08-15 13:33:02 | PLUMBING PERMIT IS NOT REQUIRED FOR REPLACEMENT OF | | FIXTURES IN SAME LOCATION PER WPB AMEND. TO FBC | | SEC.105.2 PLUMBING (3). SEE T.LARGE WITH ANY QUESTIONS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-04-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-04-09 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-04-08 |
Time |
17:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2019-03-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-22 |
Time |
07:29 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-15 |
Time |
08:18 |
Sent To |
|
|
Notes |
2019-02-22 07:34:34 | NO NOTES |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2019-07-29 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-07-29 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-07-26 |
Time |
07:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-04-09 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-04-09 |
Time |
07:31 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-04-04 |
Time |
17:05 |
Sent To |
|
|
Notes |
2019-04-09 07:32:05 | NEW PLANS ARE EXPECTED. A THIRD SIGNATURE REVIEW WILL | | BE REQUIRED. CT |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2019-02-21 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2019-02-21 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2019-02-15 |
Time |
08:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-07-25 |
|
|
Cont ID |
|
Sent By |
avann |
Date |
2019-07-25 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2019-07-25 |
Time |
16:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2019-04-15 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2019-04-15 |
Time |
14:35 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2019-04-15 |
Time |
14:26 |
Sent To |
PC |
|
Notes |
2019-04-15 14:35:26 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | 1) PROVIDE A CURRENT SURVEY, WHICH INCLUDES THE | | PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | 2) INDICATE THE SETBACK DIMENSION FROM THE PROPOSED A/C | | UNIT TO ALL ADJACENT PROPERTY LINES. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER | | THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO | | SCHEDULE AN APPOINTMENT. | | | | MAGGIE CRUZ | | ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1442 | | E-MAIL: [email protected] | | |
|
|
|