Plan Review Details - Permit 18111269
Plan Review Stops For Permit 18111269
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-07-29 Cont ID  
Sent By cthroop Date 2019-07-29 Time 08:34 Rev Time 0.00
Received By cthroop Date 2019-07-26 Time 07:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-08 Cont ID  
Sent By cthroop Date 2019-04-08 Time 16:01 Rev Time 0.00
Received By cthroop Date 2019-04-04 Time 17:04 Sent To  
Notes
2019-04-08 17:01:32BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE
 LIST THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL
 STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN
 PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE
 WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT
 INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE
 CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS
 FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN
 AND SCOPE OF WORK FOR 2ND UNIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PLAN REVIEW RESPONSE SHEET SUBMITTED WITH THIS
 RE-SUBMITTAL IS ADDRESSED TO THE DADE COUN TY BUILDING
 DEPT. AND IDENTIFIES THE SUBJECT PROPERTY AS 4519 NW
 22ND CT & 4237 NW 23RD AVE. PLEASE REMOVE FROM
 SUBMITTAL.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2019-02-21 Cont ID  
Sent By pvalenti Date 2019-02-21 Time 16:50 Rev Time 0.00
Received By pvalenti Date 2019-02-15 Time 08:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-07-29 Cont ID  
Sent By cthroop Date 2019-07-29 Time 08:34 Rev Time 0.00
Received By cthroop Date 2019-07-26 Time 07:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-04-08 Cont ID  
Sent By cthroop Date 2019-04-08 Time 17:02 Rev Time 0.00
Received By cthroop Date 2019-04-08 Time 17:02 Sent To  
Notes
2019-04-08 17:37:26ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE
 LIST THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL
 STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN
 PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE
 WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT
 INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE
 CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS
 FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN
 AND SCOPE OF WORK FOR 2ND UNIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. NEW CHANGE IN SERVICE -
 2A. STATE CONDUCTOR SIZE OF EXISTING SERVICE DROP.
 E3602.1 AMPACITY OF UNGROUNDED CONDUCTORS.
 2B. IDENTIFY LOCATION OF SERVICE DISCONNECT. E3601.6.2
 SERVICE DISCONNECT LOCATION.
 2C. PROVIDE LOAD CALCULATIONS FOR BOTH NEW PANELS.
 UTILIZE RESIDENTIAL FORMULA TABLE E3602.2
 2D. PROVIDE AIC CALCULATIONS FOR BOTH NEW SERVICES.
 E3602.2 SERVICE LOAD.
  
 3. ELECTRICAL NOTE #6 IS INCORRECT. AFCI PROTECTION IS
 REQUIRED PER THE FOLLOWING: E3902.16 ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
  
 4. ELECTRICAL PLAN SHOWS BOTH KITCHEN COUNTER TOP
 RECEPTACLES ARE SUPPLIED FROM A SINGLE 20AMP CIRCUT-
 #2. PLEASE SEE FBC R3703.2 AND CORRECT.
 E3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES. [210.11(C)(1) AND
 210.52(B)(1) AND (B)(2)].
  
 5. CIRCUT #10 OVERCURRENT PROTECTION AND CONDUCTOR SIZE
 IS INCORRECT. E3703.4 BATHROOM BRANCH CIRCUITS AND
 TABLE E3702.14.
 A MINIMUM OF ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. [210.11(C)(3)].
  
 6. PANEL SCHEDULE ON PLAN PAGE A-1 IS LABELED WINDOW
 AND DOOR SCHEDULE. PLEASE CORRECT. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 7. OVERCURRENT PROTECTION FOR THE INDOOR AND OUTDOOR
 MINI-SPLIT A/C SYSTEM PROPOSES TWO SEPERATE SINGLE POLE
 20AMP CIRCUTS. PROVIDE MANUFACTURERS SPCIFICATIONS TO
 VERIFY. E3702.11 BRANCH CIRCUITS FOR AIR-CONDITIONING
 AND HEAT PUMP EQUIPMENT.
  
 8. PROVIDE A 125-VOLT, SINGLE PHASE, 15 OR 20 AMP
 RECEPTACLE OUTLET FOR THE SERVICING OF THE NEW
 MECHANICAL EQUIPMENT. E3901.12 HVAC OUTLET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By jpearson Date 2019-02-21 Time 15:15 Rev Time 0.00
Received By jpearson Date 2019-02-15 Time 08:18 Sent To  
Notes
2019-02-21 15:15:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 3. NOTE 3(?) STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 4. PROVIDE LOCATION ON PLAN OF MINI-SPLIT OUTSIDE UNIT.
 PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR SERVICING
 OF A/C EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER
 CODE. NEC 210.63; FBC RE E3901.12; WPB FBC 107.2.1
 5. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 6. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 7. PROVIDE CLARIFICATION FOR LOCATION OF ELECTRICAL
 PANEL. DOES THE PANEL HAVE THE REQUIRED CLEARANCE IF IT
 FACES THE RANGE? PROVIDE CORRECTION AS NEEDED. NEC
 110.26; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2019-02-15 Cont ID  
Sent By fmittner Date 2019-02-15 Time 16:35 Rev Time 0.00
Received By fmittner Date 2019-02-15 Time 16:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-29 Cont ID  
Sent By cthroop Date 2019-07-29 Time 08:34 Rev Time 0.00
Received By cthroop Date 2019-07-15 Time 16:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-04-15 Cont ID  
Sent By mcruz Date 2019-04-15 Time 14:35 Rev Time 0.00
Received By mcruz Date 2019-04-02 Time 16:57 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-02-22 Cont ID  
Sent By cthroop Date 2019-02-22 Time 07:34 Rev Time 0.00
Received By cthroop Date 2019-02-04 Time 08:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-07-29 Cont ID  
Sent By cthroop Date 2019-07-29 Time 08:34 Rev Time 0.00
Received By cthroop Date 2019-07-26 Time 07:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-09 Cont ID  
Sent By cthroop Date 2019-04-09 Time 07:32 Rev Time 0.00
Received By cthroop Date 2019-04-08 Time 17:02 Sent To  
Notes
2019-04-09 07:49:27MECANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE LIST
 THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL
 STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN
 PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE
 WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT
 INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE
 CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS
 FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN
 AND SCOPE OF WORK FOR 2ND UNIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. MECHANICAL SCOPE OF WORK INCLUDES EXHAUST FANS,
 MINI-SPLIT AND DRYER EXHAUST. EXHAUST FANS MISSING FROM
 PLAN. NO DRYER SHOWN ON PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE ENERGY CALCULATIONS (MANUAL J), INCLUDE
 EQUIPMENT SIZING PER ACCA MANUAL S. M1401.3 EQUIPMENT
 AND APPLIANCE SIZING.
  
 4. TWO SEPERATE 20 AMP CIRCUTS ARE PROPOSED FOR NEW
 MINI-SPLIT SYSTEM. PROVIDE MANUFACTURERS SPCIFICATIONS
 TO VERIFY POWER REQUIREMENTS. M1401.1 INSTALLATION
  
 5. PROVIDE SURVEY. SHOW LOCATION OF NEW CONDENSING
 UNIT. PROVIDE DISTANCE TO PROPERTY LINE. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE NOTE ON PLAN TO PROVIDE LOCKING ACCESS
 PORTS. M1411.8 LOCKING ACCESS PORT CAPS.
  
 7. PROVIDE DETAIL OF CONDENSATE DISPOSAL PIPING ROUTING
 THROUGH BUILDING. M1411.3 CONDENSATE DISPOSAL.
  
 8. PROVIDE A 125-VOLT, SINGLE PHASE, 15 OR 20 AMP
 RECEPTACLE OUTLET FOR THE SERVICING OF THE NEW
 MECHANICAL EQUIPMENT. E3901.12 HVAC OUTLET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-02-21 Cont ID  
Sent By hmoser Date 2019-02-21 Time 15:13 Rev Time 0.00
Received By hmoser Date 2019-02-21 Time 15:13 Sent To  
Notes
2019-02-21 15:24:22PLAN DENIED
 PROVIDE MORE INFORMATION ON MECHANICAL PLAN.
 PER SECTION 107 FBC. 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-07-29 Cont ID  
Sent By cthroop Date 2019-07-29 Time 08:34 Rev Time 0.00
Received By cthroop Date 2019-07-26 Time 07:23 Sent To  
Notes
2019-08-15 13:33:02PLUMBING PERMIT IS NOT REQUIRED FOR REPLACEMENT OF
 FIXTURES IN SAME LOCATION PER WPB AMEND. TO FBC
 SEC.105.2 PLUMBING (3). SEE T.LARGE WITH ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-09 Cont ID  
Sent By cthroop Date 2019-04-09 Time 07:30 Rev Time 0.00
Received By cthroop Date 2019-04-08 Time 17:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-03-07 Cont ID  
Sent By cthroop Date 2019-02-22 Time 07:29 Rev Time 0.00
Received By cthroop Date 2019-02-15 Time 08:18 Sent To  
Notes
2019-02-22 07:34:34NO NOTES

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-07-29 Cont ID  
Sent By cthroop Date 2019-07-29 Time 08:34 Rev Time 0.00
Received By cthroop Date 2019-07-26 Time 07:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-04-09 Cont ID  
Sent By cthroop Date 2019-04-09 Time 07:31 Rev Time 0.00
Received By cthroop Date 2019-04-04 Time 17:05 Sent To  
Notes
2019-04-09 07:32:05NEW PLANS ARE EXPECTED. A THIRD SIGNATURE REVIEW WILL
 BE REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2019-02-21 Cont ID  
Sent By pvalenti Date 2019-02-21 Time 16:51 Rev Time 0.00
Received By pvalenti Date 2019-02-15 Time 08:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2019-07-25 Cont ID  
Sent By avann Date 2019-07-25 Time 16:16 Rev Time 0.00
Received By ajones Date 2019-07-25 Time 16:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2019-04-15 Cont ID  
Sent By mcruz Date 2019-04-15 Time 14:35 Rev Time 0.00
Received By mcruz Date 2019-04-15 Time 14:26 Sent To PC
Notes
2019-04-15 14:35:26ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PROVIDE A CURRENT SURVEY, WHICH INCLUDES THE
 PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
 2) INDICATE THE SETBACK DIMENSION FROM THE PROPOSED A/C
 UNIT TO ALL ADJACENT PROPERTY LINES.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME. IF YOU WANT TO MEET IN PERSON TO GO OVER
 THE ABOVE COMMENTS, PLEASE CALL OR E-MAIL ME TO
 SCHEDULE AN APPOINTMENT.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  