Plan Review Details - Permit 18111244
Plan Review Stops For Permit 18111244
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By cthroop Date 2018-12-10 Time 08:59 Rev Time 0.00
Received By cthroop Date 2018-12-10 Time 08:36 Sent To  
Notes
2018-12-10 09:20:35BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW - REVISION DATED 11/28/2018
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLANS DO NOT SHOW LOCATION OF PROPOSED WORK FOR
 REVISION 4 AND 5.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2. THE PLAN SUBMITTED SHOWS ONE DOOR TO BE REMOVED AND
 ONE DOOR TO BE INSTALLED (NEW). WILL THE EXT. WALL BE
 CLOSED WHERE THE DOOR IS TO BE REMOVED? PROVIDE
 STRUCTURAL DETAILS AND PRODUCT APPROVALS FOR THESE TWO
 AREAS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 3. IT APPEARS NEW PIPING IS PENETRATING A RATED WALL.
 PROVIDE DETAIL FOR THIS CONDITION AND SPECIFY FIRE
 COLLAR OR DESIGN TO BE USED.
  
 4. PROVIDE PLAN SHEET WITH CLOUDED REVISIONS THAT SHOWS
 WORK THAT MATCHES THE REVISION NARRATIVE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By pleduc Date 2018-12-06 Time   Rev Time 0.00
Received By pleduc Date 2018-12-06 Time 14:45 Sent To B
Notes
2018-12-06 15:11:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLAN SHEET SHOWS VERY GENERAL
 INFOMATION WITH A LARGE CLOUD AREA.
  
 THE PREVIOUS PLANS SHOWED A DOMESTIC PUMP AREA.
  
 WHAT HAPPENED TO THE THAT PUMP?
  
  
  
 2) THERE ARE INDICATIONS WHERE THE NEW PIPING HAS
 BREACHED A FIRE RATED WALL.
  
 PLEASE PROVIDE THE LISTED FIRE WALL PENETRATIONS USED
 TO MAINTAIN THIS RATING?
  
  
  
 3) THERE IS AN INDICATION "DOOR TO BE REMOVED" AND A
 NEW DOOR ADDED.
  
 THE PUMP ROOM IS REQUIRED TO BE RATED. IS THIS NEW DOOR
 RATED?
  
 HOW IS IT ASCESSED?
  
 WAS AN EXIT LIGHT MOVED OR PROVIDED?
  
 HOW WAS THE DOOR VOID SPACE INFILLED?
  
 PLEASE CORRECT OR PROVIDE SPECIFIC DETAILES AND FIRE
 CODE REFERENCES.
  
  
  
 4) THERE IS TWO NEW PIPES ENTERING ANOTHER ROOM AND
 BREACHING ANOTHER WALL.
  
 THIS NEW ROOM IS NOT INDICATED AND HOW IT IS BEING
 USED.
  
 PLEASE PROVIDE THE ROOM DETAIL AND HOW IT IS USED..
  
  
  
 5) THE FDC CONFIGURATION IS DIFFERENT THAN PREVIOUSLY
 SUBMITTED.
  
 IT APPEARS THE FDC IS FEEDING THE INCORRECT END
 (DISCHARGE) OF THE PUMP.
  
 PLEASE REVIEW AND CORRECT OR EXPLAIN WITH DETAILS.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-10 Cont ID  
Sent By cthroop Date 2018-12-10 Time 09:20 Rev Time 0.00
Received By cthroop Date 2018-11-30 Time 13:55 Sent To  
Notes
2018-12-08 13:06:0612/8 TO CT DESK / S.HILL
  
2018-12-03 13:55:50REVISION ROUTED TO FIRE INBOX