Plan Review Details - Permit 18111193
Plan Review Stops For Permit 18111193
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-06-12 Cont ID  
Sent By jduprey Date 2019-06-12 Time 14:27 Rev Time 0.00
Received By dbattles Date 2019-06-12 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-27 Cont ID  
Sent By jduprey Date 2019-03-27 Time 14:46 Rev Time 0.00
Received By jduprey Date 2019-03-27 Time 14:46 Sent To  
Notes
2019-03-27 14:51:13PROVISO
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD.DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-05 Cont ID  
Sent By jduprey Date 2019-03-05 Time 14:58 Rev Time 0.00
Received By jduprey Date 2019-03-05 Time 13:34 Sent To  
Notes
2019-03-05 14:57:55BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ANSWERED
  
 2. NOTED
  
 ADDITIONAL COMMENTS:
  
 3. BUILDING CODE DATA PAGE ALS.0.1 REFERED TO THE 2014
 5TH EDITION FBC. PLEASE SEE BELOW THE CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH
 EDITION
 FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 4. SOME PAGES ARE MAKING REFRENCE TO THE THE STRUCTURAL
 DRAWINGS, HOWEVER NO STRUCTURAL DRAWINGS WERE
 SUBMITTED. PLEASE SUBMIT THE APPLICABLE STRUCTURAL
 DRAWINGS. FBC 107
  
 5. PAGE A7.0.1 REFERS SECTIONS 8/A7.0.2 FOR DOOR JAMS,
 HOWEVER THE DRAWING SHEET 8/A7.0.2 WAS NOT SUBMITTED.
 PLEASE SUBMIT THE APPLICABLE DETAILS. FBC 107
  
 6. FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS OR INDICATE IF THIS PRODUCT APPROVALS WILL
 BE DEFERRED.
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By shill Date 2019-01-08 Time 13:18 Rev Time 0.00
Received By jduprey Date 2019-01-07 Time 14:14 Sent To  
Notes
2019-01-07 16:48:44BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. INTERIOR DOOR SCHEDULE WAS NOT PROVIDED. PLEASE
 PROVIDE NEW INTERIOR DOOR DIMENSION AND DOOR SHCEDULE.
 FBC 107
  
 2. PLEASE PROVIDE STATUS OF YOUR AIPP. THIS WAS
 REQUIRED TO BE SUBMITTED WHITIN 90 DAYS OF COMMENCEMENT
 OF CONSTRUCTION.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2019-06-08 Cont ID  
Sent By jpearson Date 2019-06-08 Time 11:17 Rev Time 0.00
Received By fgiaquin Date 2019-06-08 Time 10:22 Sent To  
Notes
2019-06-08 11:17:06REVIEWED NEW VERSIONS OF PLANS, NO CHANGES THAT CAN BE
 SEEN. PLAN ALREADY PASSED BY JOHN PEARSON

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2019-04-09 Cont ID  
Sent By jpearson Date 2019-04-09 Time 15:09 Rev Time 0.00
Received By jpearson Date 2019-04-09 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-03-04 Cont ID  
Sent By jpearson Date 2019-03-04 Time 09:54 Rev Time 0.00
Received By jpearson Date 2019-03-04 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-26 Cont ID  
Sent By jpearson Date 2019-02-26 Time 07:22 Rev Time 0.00
Received By jpearson Date 2019-02-26 Time 07:22 Sent To  
Notes
2019-02-26 07:22:24DUPLICATE STOP, ALREADY PASSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By jpearson Date 2019-02-20 Time 09:44 Rev Time 0.00
Received By jpearson Date 2019-02-20 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-23 Cont ID  
Sent By jpearson Date 2018-12-23 Time 15:25 Rev Time 0.00
Received By jpearson Date 2018-12-23 Time 15:25 Sent To  
Notes
2018-12-23 15:25:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER NEC 240.6(B), THE ADJUSTABLE BREAKER FOR PANEL
 MDP-B SHALL BE RATED AT THE MAXIMUM POSSIBLE SETTING,
 WHICH IS 1000 AMPS. THE CONDUCTORS FEEDING THIS BREAKER
 SHALL HAVE AN AMPACITY EQUAL TO OR GREATER THAN THE
 RATRING OF THE BREAKER. PROVIDE CORRECTION. NEC
 240.4(C)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-29 Cont ID  
Sent By scaldero Date 2019-05-29 Time   Rev Time 0.00
Received By pleduc Date 2019-05-28 Time 15:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-03-26 Cont ID  
Sent By scaldero Date 2019-03-26 Time 09:31 Rev Time 0.00
Received By scaldero Date 2019-03-26 Time 08:05 Sent To  
Notes
2019-03-26 09:31:04PERMIT # 18111193
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET ALS 1.3 ON REVIEW OF THE REVISION TO THE 3RD
 FLOOR TERRACE IT APPEARS THAT THE EGRESSING FOR THE
 TERRACE SPACE DOES NOT MEET THE MEANS OF EGRESS
 REQUIREMENTS FOR ASSEMBLY OCCUPANCIES.
 ASSEMBLY REQUIREMENTS SHALL HAVE A MINIMUM OF 2,
 PROPERLY SEPARATED, MEANS OF EGRESS. ALTHOUGH THERE ARE
 3 SEPARATE EXIT STAIRWELLS ON THE 3RD FLOOR, THE
 TERRACE AREA HAS ONLY ONE MEANS OF EGRESS LEADING
 OUT/OFF OF THE TERRACE AREA.
 NFPA 101, CHAPTER 7:
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL
 LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET.
  
 NFPA 101, CHAPTER 12:
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH SECTION 7.4, OTHER THAN EXITS FOR
 FENCED OUTDOOR ASSEMBLY OCCUPANCIES IN ACCORDANCE WITH
 12.2.4.4.
  
 2) THE 3RD FLOOR AND TERRACE PLANS DO NOT MATCH THE
 APPROVED LAYOUTS/FLOOR PLANS AS PROVIDED ON MASTER
 PERMIT #17120610 AND REVISION 18040104. THIS NEW
 LOCATION OF THE "TERRACE" IS NOT COMPLIANCE OF THE FIRE
 CODE REQUIREMENTS FOR EGRESS.
  
 3) SHEET ALS 0.1: THE OCCUPANCY LOADS DO NOT FULLY
 MATCH THE OCCUPANT LOADS PROVIDED ON SHEETS ALS 1.1,
 ALS 1.2, AND ALS 1.3.
 SPECIFICALLY, THE CONFERENCE ROOM TOTALS, AND THE TENAN
 OCCUPANT LOADS ON THE 3RD FLOOR.
 ON ALS 0.1, THE TERRACE IS LABELED AS FLOOR 4, NOT
 FLOOR 3.
 PLEASE REVIEW AND ENSURE THAT ALL OCCUPANT LOAD
 CALCULATIONS AND TOTAL MATCH ON ALL APPLICABLE SHEETS.
  
 4) ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 DURING PLAN RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-12-12 Cont ID  
Sent By scaldero Date 2018-12-12 Time 10:42 Rev Time 0.00
Received By scaldero Date 2018-12-10 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-06-12 Cont ID  
Sent By gjohnson Date 2019-06-12 Time 15:48 Rev Time 0.00
Received By gjohnson Date 2019-05-24 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-28 Cont ID  
Sent By cpuell Date 2019-04-28 Time 11:04 Rev Time 0.00
Received By cpuell Date 2019-03-19 Time 12:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-12 Cont ID  
Sent By shill Date 2019-03-12 Time 14:54 Rev Time 0.00
Received By cpuell Date 2019-01-22 Time 14:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-11 Cont ID  
Sent By gjohnson Date 2019-01-11 Time 09:41 Rev Time 0.00
Received By gjohnson Date 2018-12-06 Time 11:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2019-06-12 Cont ID  
Sent By ccole Date 2019-06-12 Time 14:09 Rev Time 0.00
Received By ccole Date 2019-06-12 Time 11:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-03-05 Cont ID  
Sent By ccole Date 2019-03-05 Time 11:08 Rev Time 0.00
Received By ccole Date 2019-03-05 Time 11:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-02-26 Cont ID  
Sent By ccole Date 2019-02-26 Time 11:12 Rev Time 0.00
Received By ccole Date 2019-02-26 Time 11:12 Sent To  
Notes
2019-02-26 11:40:093RD REVIEW FBC-2017 MECHANICAL
 MASTER PERMIT #18040104
 REVISION #18111193
 1/26/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NEW COMMENT, SHEET M2.2: THE MMU-2-19 IS NOT
 PERMITTED TO BE INSTALLED IN STAIR B PER SECTION
 1023.6.
  
 2) REPEAT COMMENT, M2.2: THE 6" DUCT SHALL NOT
 PENETRATE INTO STAIR B- SECTIONS 1023.5 & 1023.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-02-19 Cont ID  
Sent By ccole Date 2019-02-19 Time 11:51 Rev Time 0.00
Received By ccole Date 2019-02-19 Time 10:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-28 Cont ID  
Sent By ccole Date 2018-12-28 Time 16:14 Rev Time 0.00
Received By ccole Date 2018-12-28 Time 16:14 Sent To  
Notes
2018-12-28 16:25:261ST REVIEW FBC-2017 MECHANICAL
 MASTER PERMIT #18040104
 REVISION #18111193
 12/28/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.2: THE 6X4 DUCT IS NOT PERMITTED TO
 PENETRATE INTO THE INTERIOR EXIT STAIRWAY B- SECTION
 1023.5 FBC B.
  
 2) M2.2: A FIRE DAMPER IS REQUIRED AT THE PENETRATION
 OF THE 12X12 DUCT THROUGH THE FLOOR INTO THE BASEMENT-
 SECTION 607.6.1 FBC M.
  
 3) M2.4A: REVISE THE O/A CALCULATIONS AND THE AC
 EQUIPMENT SCHEDULE ON THE MAIN PLAN TO INCLUDE THE NEW
 THIRD FLOOR AC SYSTEMS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-06-12 Cont ID  
Sent By gjohnson Date 2019-06-12 Time 15:47 Rev Time 0.00
Received By gjohnson Date 2019-06-12 Time 15:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-07 Cont ID  
Sent By gjohnson Date 2019-03-07 Time 12:25 Rev Time 0.00
Received By gjohnson Date 2019-03-07 Time 12:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-11 Cont ID  
Sent By gjohnson Date 2019-01-11 Time 09:40 Rev Time 0.00
Received By gjohnson Date 2019-01-11 Time 06:37 Sent To  
Notes
2019-01-11 09:40:471ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 SHOW COMPLIANCE WITH THE FOLLOWING: SHEET A9-5-2
  
 1. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT.PER FBC ACC 604.4
  
 2. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER
 FBC ACC 604.5.1
  
 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM)
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. PER FBC
 ACC 604.5.2
  
 4. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER FBC ACC 603.3
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. PER FBC ACC 604.7
  
 6. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER
 FBC ACC 606.3
  
 7. CLEAR FLOOR SPACE FOR THE TOILET AND LAVATORY WITH
 DIMENSIONS. PER FBC ACC 604.3.1, 606.2
  
 8. AT LEAST ONE OF THE LAVATORY'S OUTSIDE OF THE
 ACCESSIBLE STALL SHALL COMPLY WITH . FBC ACC 213.3.4,
 606.2, 606.3
  
 9. PLEASE REVISE SHEETS P5.1 + P6.1 SHOW THE NEW MOP
 SINK IN THE BASEMENT , SINK ON 2ND FLOOR AND
 RECONFIGURED BATHROOM ON 3RD FLOOR. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 10. THE NEW SINK ON THE 2ND FLOOR NEXT TO BATHROON 208
 SHALL COMPLY WITH FBC ACC 212.3, 606.2, 606.3
  
 11. SHEET P2.3 THE WC IN THE OFFICE BATHROOM 202 IS NOT
 VENT IT SHOULD CONNECT TO THE WET VENT WITH TH E
 LAVATORY AND SHOWER. PER FBC PL 913.1
  
 12. SHEET P2.3 THE NEW SINK NEXT TO BATHROOM 208 ON 2ND
 FLOOR SHALL NOT CONNECT BETWEEN THE SHOWER AND WC IT
 SHALL CONNECT DOWN STREAM OF THE BATHROOM GROUP. PER
 FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-06-12 Cont ID  
Sent By dbattles Date 2019-06-12 Time 14:42 Rev Time 0.00
Received By dbattles Date 2019-06-12 Time 14:41 Sent To  
Notes
2019-06-12 14:11:04MEP SHEETS ARE ELECTRONICALLY SIGNED BUT NOT SEALED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 07:05 Rev Time 0.00
Received By shill Date 2019-03-27 Time 14:46 Sent To  
Notes
2019-04-30 06:59:15SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SIGNATURE REVIEW, 4/30/2019
  
 1. CIVIL PAGES ARE NOT DIGITALLY SIGNED. IF RICHARD
 RIKENIS, PE DOES NOT HAVE A DIGITAL SIGNATURE, SUBMIT
 ONE PAPER ORIGINAL TO THE BUILDING DIVISION WITH A
 SUBMITTAL FORM AND THE DESCRIPTION "SIGNATURE
 DOCUMENTS". A SIGNATURE REVIEW WILL BE DONE PRIOR TO
 ISSUANCE.
  
 2. THE STRUCTURAL PAGES ARE NOT DIGITALLY SIGNED.
 ANDREW SULLIVAN, PE HAS A DIGITAL SIGNATURE; PLEASE
 UPLOAD DIGITALLY SIGNED PAGES. A NEW BUILDING REVIEW
 WILL BE REQUIRED; PLEASE ADVISE THE BUILDING REVIEWER
 WHEN THE NEW PAGES HAVE BEEN UPLOADED AND RESUBMITTED,
 FS471, FAC61G15-23.004.
  
 3. MECHANICAL PAGES ARE NOT DIGITALLY SIGNED. BRADLY
 BROWN, PE HAS A DIGITAL SIGNATURE; PLEASE UPLOAD
 DIGITALLY SIGNED PAGES. A NEW MECHANICAL REVIEW WILL BE
 REQUIRED; PLEASE ADVISE THE MECHANICAL REVIEWER WHEN
 THE NEW PAGES HAVE BEEN UPLOADED AND RESUBMITTED,
 FS471, FAC61G15-23.004, FBC 107.
  
 4. PLUMBING AND ELECTRICAL PAGES ARE DIGITALLY SIGNED
 BY BRADLY BROWN, PE BUT LACKS A SEAL AND LACKS
 INFORMATION REQUIRED BY FAC61G15-23.004. IT IS NOT
 NECESSARY TO UPLOAD NEW PLUMBING SHEETS BUT PLEASE HAVE
 MR. BROWN, PE CORRECT THIS ISSUE ON ALL NEW PAGES.
  
  
 *******************************************************
 ***************
  
2019-04-09 15:09:41ELECTRICAL SHEETS OK.
  
2019-03-27 14:49:02PE SIGNATURES FOR DRAWING SHEET SSK-013; SSK-015;
 SSK-016; SSK-018; SSK019 AND SSK-021 ARE MISSING.
 ARCH AND STRUCTURAL ARE OK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-03-11 Cont ID  
Sent By shill Date 2019-03-11 Time 10:08 Rev Time 0.00
Received By shill Date 2019-03-11 Time 10:08 Sent To  
Notes
2019-03-07 12:27:16DIG SIG ON PLUMB SHEETS OK
2019-03-05 11:12:53MECH SHEETS M2.1 AQND M2.2 NOT ELECTRONICALLY SIGNED
 AND SEALED.
2019-02-20 09:45:01ELECTRICAL SHEETS OK AS OF 3-1-19 SUBMISSION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-03-04 Cont ID  
Sent By jpearson Date 2018-12-23 Time 14:47 Rev Time 0.00
Received By jpearson Date 2018-12-23 Time 14:47 Sent To  
Notes
2019-03-04 08:55:47CHANGED STATUS TO FAIL SO RE-SUBMITTALS WILL BE
 CHECKED.

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-31 Cont ID  
Sent By elevesqu Date 2019-05-31 Time 16:34 Rev Time 0.00
Received By elevesqu Date 2019-05-31 Time 16:34 Sent To  
Notes
2019-05-31 16:39:38PHOTOMETRICS TO BE REVIEWED THROUGH SEPARATE PERMIT TO
 ENSURE SUFFICIENT LIGHTING ON PUBLIC ROW.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-05-31 Cont ID  
Sent By elevesqu Date 2019-04-18 Time 16:01 Rev Time 0.00
Received By elevesqu Date 2019-04-18 Time 16:01 Sent To  
Notes
2019-04-18 16:02:18STREET LIGHTING SHALL BE REVIEWED FOR PHOTOMETRICS AND
 POLE DETAILS AT TIME OF PERMITTING
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 1 Status P Date 2019-03-12 Cont ID  
Sent By elevesqu Date 2019-03-12 Time 14:47 Rev Time 0.00
Received By elevesqu Date 2019-03-12 Time 14:45 Sent To  
Notes
2019-03-12 14:47:081. FIRST TWO PARKING SPACES AT ENTRANCE PARKING GATE
 (FIRST ON EAST AND FIRST ON WEST) APPEAR TO BE LESS
 THAN 7 FEET WIDE. THESE ARE SMALLER THAN COMPACT
 SPACES. ALL SPACES WILL NEED TO MEET CODE REQUIREMENTS
  
 2. THE BICYCLE RACK ALONG OLIVE STREET WILL NEED TO BE
 MOVED FURTHER INTO THE SIDEWALK TO ALLOW FOR THREE FEET
 BETWEEN THE CURB AND HITCH, KEEPING 5 FEET OF CLEAR
 SIDEWALK PATH
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426