Plan Review Details - Permit 18111148
Plan Review Stops For Permit 18111148
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By jgomez Date 2018-12-18 Time 14:42 Rev Time 0.00
Received By jgomez Date 2018-12-18 Time 14:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-03 Cont ID  
Sent By jgomez Date 2018-11-29 Time 18:31 Rev Time 0.00
Received By jgomez Date 2018-11-29 Time 16:34 Sent To  
Notes
2018-11-29 18:43:14RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- REVISE RAS 117 CALCULATIONS SUBMITTED;
 A) CALCULATIONS SUBMITTED SPECIFY 8'-0" HEIGHT FOR THIS
 BUILDING. THIS IS INCORRECT. THIS IS A TWO STORY
 BUILDING. PROVIDE THE CORRECT MEAN ROOF HEIGHT AND
 REVISE DESIGN PRESSURES ACCORDINGLY. SEC. 1609.1 FBC
 AND CITY POLICY FOR ALL ROOFING PERMITS.
  
 B) NUMBER OF BASE SHEET FASTENING ROWS SPECIFIED (3)
 ARE INCORRECT BASED ON THE SPECIFIED DESIGN PRESSURES.
 BY RUNNING RAS 117 CALCULATIONS BASED ON THE DESIGN
 PRESSURES AND NAILING SPACING SHOWN FOR ROOF ZONE #1 I
 FOUND THAT NEED AT LEAST 5 ROWS IN THE FIELD OF THE
 SHEET FOR ROOF ZONE #3. REVISE AS REQUIRED. NOTE: RAS
 117 CALCULATIONS SEC. 8.1 DOESN'T ALLOW NAIL SPACING
 LESS THAN 4"O.C. THAT'S WHY 5 ROWS ARE REQUIRED.
  
 C) FLAT ROOF NOA 15-1020.01 DOESN'T MATCH NOA
 18-0919.12 SUBMITTED. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) THERE ARE TWO BUILDING THIS PROPERTY. CLARIFY IF
 RE-ROOFING BOTH BUILDINGS OR JUST ONE. BASED ON
 PROPERTY APPRAISER THE SQUARE FOOTAGE IS +/- 5784 S.F.
 FOR BOTH BUILDING. VALUATION WAS UPDATED TO $36,150 AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. THE PERMIT FEE
 BALANCE IS $808.86.
 OR PROVIDE COPY OF SIGNED CONTRACT (BOTH PARTIES) FOR
 BUILDING OFFICIAL CONSIDERATION.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DOCUMENTS. SUBMIT OLD DOCUMENTS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-18 Cont ID  
Sent By jgomez Date 2018-12-18 Time 14:42 Rev Time 0.00
Received By jgomez Date 2018-12-18 Time 14:30 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-03 Cont ID  
Sent By jgomez Date 2018-11-29 Time 18:42 Rev Time 0.00
Received By jgomez Date 2018-11-28 Time 12:45 Sent To I
Notes
2018-11-29 12:46:03JGOMEZ


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved