Plan Review Details - Permit 18111109
Plan Review Stops For Permit 18111109
Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2019-07-24 Cont ID  
Sent By rrossano Date 2019-07-24 Time   Rev Time 0.00
Received By rrossano Date 2019-07-24 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-07-10 Cont ID  
Sent By rrossano Date 2019-07-10 Time   Rev Time 0.00
Received By rrossano Date 2019-07-10 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-12-20 Cont ID  
Sent By RRossano Date 2018-12-20 Time   Rev Time  
Received By rrossano Date 2018-12-20 Time   Sent To I
Notes
2018-12-20 07:30:29PLEASE ADDRESS FIRE & MECHANICAL COMMENTS AND SUBMIT
 FULL SIZE PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-07-17 Cont ID  
Sent By pleduc Date 2019-07-17 Time   Rev Time 0.00
Received By pleduc Date 2019-07-17 Time 15:08 Sent To M
Notes
2019-07-17 15:09:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED UNDERGROUND SHALL BE INSTALLED,
 INSPECTED AND TESTED PER NFPA 24.
  
  
  
 2) PLEASE DO NOT COVER OVER ANY JOINTS PRIOR TO
 INSPECTION.
  
  
  
 3) PLEASE ENSURE COMPLIANCE AND ENSURE MANUFACTURES
 SPECIFICATIONS ARE ONSITE FOR FIRE INSPECTOR REVIEW AND
 VERIFICATION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-28 Cont ID  
Sent By pleduc Date 2019-06-28 Time   Rev Time 0.00
Received By pleduc Date 2019-06-28 Time 11:00 Sent To M
Notes
2019-06-28 11:03:43THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED UNDERGROUND SHALL BE INSTALLED,
 INSPECTED AND TESTED PER NFPA 24.
  
  
  
 2) PLEASE DO NOT COVER OVER ANY JOINTS PRIOR TO
 INSPECTION.
  
  
  
 3) PLEASE ENSURE COMPLIANCE AND ENSURE MANUFACTURES
 SPECIFICATIONS ARE ONSITE FOR FIRE INSPECTOR REVIEW AND
 VERIFICATION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By Bwoods Date 2018-12-06 Time 00:00 Rev Time  
Received By   Date 2018-12-04 Time 00:00 Sent To M
Notes
2018-12-06 14:25:09 
 SHALL COMPLY WITH NFPA 24
 2013 EDITION
  
 4.1.3 WORKING PLANS SHALL BE DRAWN TO AN INDICATED
 SCALE ON
 SHEETS OF UNIFORM SIZE, WITH A PLAN OF EACH FLOOR AS
 APPLICABLE,
 AND SHALL INCLUDE THE FOLLOWING ITEMS THAT PERTAIN TO
 THE DESIGN
 OF THE SYSTEM:
 (1) NAME OF OWNER
 (2) LOCATION, INCLUDING STREET ADDRESS
 (3) POINT OF COMPASS
 (4) A GRAPHIC REPRESENTATION OF THE SCALE USED ON ALL
 PLANS
 (5) NAME AND ADDRESS OF CONTRACTOR
 (6) SIZE AND LOCATION OF ALL WATER SUPPLIES
 (7) SIZE AND LOCATION OF STANDPIPE RISERS, HOSE
 OUTLETS, HAND
 HOSE, MONITOR NOZZLES, AND RELATED EQUIPMENT
 (8) THE FOLLOWING ITEMS THAT PERTAIN TO PRIVATE FIRE
 SERVICE
 MAINS:
 (A) SIZE
 (B) LENGTH
 (C) LOCATION
 (D) WEIGHT
 (E) MATERIAL
 (F) POINT OF CONNECTION TO CITY MAIN
 (G) SIZES, TYPES, AND LOCATIONS OF VALVES, VALVE
 INDICATORS,
 REGULATORS, METERS, AND VALVE PITS
 (H) DEPTH AT WHICH THE TOP OF THE PIPE IS LAID BELOW
 GRADE
 (I) METHOD OF RESTRAINT
 (9) THE FOLLOWING ITEMS THAT PERTAIN TO HYDRANTS:
 (A) SIZE AND LOCATION, INCLUDING SIZE AND NUMBER OF
 OUTLETS
 AND WHETHER OUTLETS ARE TO BE EQUIPPED WITH INDEPENDENT
 GATE VALVES
 (B) THREAD SIZE AND COUPLING ADAPTER SPECIFICATIONS IF
 DIFFERENT FROM NFPA 1963
 (C) WHETHER HOSE HOUSES AND EQUIPMENT ARE TO BE
 PROVIDED,
 AND BY WHOM
 (D) STATIC AND RESIDUAL HYDRANTS USED IN FLOW
 (E) METHOD OF RESTRAINT
 (10) SIZE, LOCATION, AND PIPING ARRANGEMENT OF FIRE
 DEPARTMENT
 CONNECTIONS
 4.1.4 THE WORKING PLAN SUBMITTAL SHALL INCLUDE THE
 MANUFACTURER?S
 INSTALLATION INSTRUCTIONS FOR ANY SPECIALLY LISTED
 EQUIPMENT,
 INCLUDING DESCRIPTIONS, APPLICATIONS, AND LIMITATIONS
 FOR
 ANY DEVICES, PIPING, OR FITTINGS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-07-24 Cont ID  
Sent By cpuell Date 2019-07-24 Time 13:14 Rev Time 0.00
Received By cpuell Date 2019-07-15 Time 14:55 Sent To  
Notes
2019-07-16 14:55:25RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-07-10 Cont ID  
Sent By cpuell Date 2019-07-10 Time 10:54 Rev Time 0.00
Received By cpuell Date 2019-06-25 Time 13:49 Sent To  
Notes
2019-06-27 13:50:02RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-20 Cont ID  
Sent By cpuell Date 2018-12-20 Time 10:52 Rev Time 0.00
Received By cpuell Date 2018-11-27 Time 14:02 Sent To  
Notes
2018-11-29 14:02:48ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-07-23 Cont ID  
Sent By hmoser Date 2019-07-23 Time 10:53 Rev Time 0.00
Received By hmoser Date 2019-07-23 Time 10:53 Sent To ENG
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-07-08 Cont ID  
Sent By ccole Date 2019-07-08 Time 15:54 Rev Time 0.00
Received By ccole Date 2019-07-08 Time 15:01 Sent To ENG
Notes
2019-07-08 16:02:112ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18111109
 7/8/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, SUBMIT
 TWO SETS OF FULL-SIZE ORIGINAL SIGNED AND SEALED PLANS
 FOR THE FIRE LINE- REFER TO SECTION 107.2.1 WPB. THE
 COPIED SINGLE SET OF MASTER CIVL AND LANDSCAPING PLANS
 FOR THE PROJECT ARE NOT AN ACCEPTABLE SUBMITTAL FOR THE
 SEPARATE FIRE LINE PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-19 Cont ID  
Sent By ccole Date 2018-12-19 Time 15:45 Rev Time 0.00
Received By ccole Date 2018-12-19 Time 15:45 Sent To ENG
Notes
2018-12-19 16:02:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18111109
 12/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A FLORIDA UNDERGROUND UTILITY AND EXCAVATION
 CONTRACTOR MAY NOT INSTALL PIPING THAT IS AN INTEGRAL
 PART OF A FIRE PROTECTION SYSTEM AS DEFINED IN FL.
 STATUTES 633.021 BEGINNING AT THE POINT WHERE THE
 PIPING IS USED EXCLUSIVELY FOR SUCH SYSTEM. FOR THIS
 TYPE OF INSTALLATION A FLORIDA FIRE PROTECTION V
 CONTRACTOR LICENSE IS REQUIRED INSTEAD.
  
 2) THE SUBMITTED SETS OF COPIED PLANS HAVE BEEN REDUCED
 IN SIZE AND ARE COMPLETELY ILLEGIBLE AND NOT ACCEPTABLE
 FOR REVIEW. PROVIDE CLEAR, LEGIBLE PLANS AT MINIMUM
 1/8" SCALE THAT ALSO BEAR THE ORIGINAL SIGNATURE AND
 SEAL OF THE ENGINEER OF RECORD- SECTION 107.2.1 WPB AND
 SECTION 61G15- 23.002 FAC.
  
 3) PROVIDE A PRODUCT SUBMITTAL PACKAGE THAT INCLUDES
 ALL COMPONENTS OF THE FIRE LINE ASSEMBLY INCLUDING THE
 PIPING, TEES, PLUGS, CAPS, REDUCERS, VALVES, AND ALL
 RESTRAINING DEVICES. PLEASE NOTE THAT MATERIAL DATA
 SHEETS WITH TORQUE WRENCH SETTINGS SHALL BE ONSITE AT
 TIME OF INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  