Plan Review Details - Permit 18111103
Plan Review Stops For Permit 18111103
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-28 Cont ID  
Sent By jgomez Date 2019-03-28 Time 12:14 Rev Time 0.00
Received By jgomez Date 2019-03-28 Time 11:18 Sent To  
Notes
2019-03-27 13:14:14BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2COPIES) FOR THE OVERHEAD
 GARAGE DOOR APPROVED BY THE ARCHITECT OF RECORD.
 NOTE: PROVIDE PRODUCT APPROVAL PRIOR TO INSTALLATION
 AND INSPECTION TO AVOID CONFLICTS/DELAYS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-07 Cont ID  
Sent By jgomez Date 2019-03-07 Time 12:25 Rev Time 0.00
Received By jgomez Date 2019-03-06 Time 11:27 Sent To  
Notes
2019-03-07 12:31:382017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18111103
 ADD: 901 NORTHWOOD PARKWAY, SUITE: 202-205
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-373-3902
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: 03/06/19
 ACTION: DENIED
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 1) OK.
  
 ORIGINAL COMMENT:
 2) THE LIFE SAFETY SHEET CHAPTER 10 SCHEDULE TYPICAL IS
 TAKING CREDIT FOR FIRE SPRINKLERS, IF THE BUILDING IS
 NOT FIRE SPRINKLERED THEN CORRECT THE FOLLOWING:
  
 2A) OK.
 2B) OK.
 2C) OK.
  
 NEW COMMENT:
 2D) DEAD END CORRIDOR FOR UNSPRINKLERED BUILDING IS 20
 FEET NOT 25 FEET. REVISE AS REQUIRED. SEC. 1020.4 FBC.
 ALSO, THERE IS NOT SEC. 1024.2 AS REFERENCED IN THE
 LIFE SAFETY TABLE ON SHEET LS-1.
  
 ORIGINAL COMMENT:
 3) SHEET A-1 THE FLOOR PLAN:
  
 3A) OK.
  
 3B) OK. LAB EQUIPMENT INSTALLATION TO BE COORDINATED
 WITH CHIEF BUILDING INSPECTOR.
  
 2017 FBC-B 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE
 PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE
 MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR
 ADDITIONS TO ANY BUILDING OR STRUCTURE.
  
 ORIGINAL COMMENT:
 3C) WALL TYPES: THE WALLS LABELED C-2 IN THE WALL
 SCHEDULE ARE LABELED 1 HOUR FIRE WALLS:
  
 3C)(1) OK.
 3C)(2) OK.
 3D) OK.
  
 ORIGINAL COMMENT:
 3E) AT THIS TIME THE OCCUPANCY OF THE LAB, CANNOT BE
 DETERMINED THE USAGE WILL NEED TO BE BETTER DEFINED.
 WHAT TYPES OF HAZARDOUS MATERIALS ARE TO BE USED IN THE
 DAY TO DAY USAGE OF THE LAB. PLEASE PROVIDE AMOUNT OF
 HAZARDOUS MATERIALS, IF THEY ARE SOLIDS, LIQUIDS, AND
 OR GASEOUS MATERIALS( FC-B TABLE 307.1(1), IF THEY ARE
 GOING TO BE STORED IN 1 HOUR FIRE RATED CABINETS, AND
 IF THIS ROOM (LAB) IS TO BE CONSIDERED A 1 HOUR FIRE
 CONTROL AREA IN COMPLIANCE WITH 2017 FBC-B SECTION
 414.2 THROUGH 414.4. PLEASE ALSO SUBMIT THE MSDS SHEETS
 FOR ALL CHEMICALS TO BE USED IN THE DAILY PROCESS OF
 THE LAB. A NARRATIVE FROM THE TENANT MAYBE OF HELP OF
 WHAT WORK, OR PROCESS WILL OCCUR IN THE ROOM CONSIDERED
 A LAB.
  
 RESPONSE:
 PARTIALLY COMPLIED. TO AVOID CONFUSION AND TO BE CLEAR
 THAT CONTROL AREAS ARE NOT REQUIRED. ARCHITECT TO
 CLEARLY SPECIFY ON PLANS THE TYPE OF TESTING TO BE
 PERFORMED IN THIS LAB . AND, ACKNOWLEDGE THAT HAZARDOUS
 MATERIALS ARE NOT STORED OR HANDLED IN THIS LAB. ALSO,
 NARRATIVE FROM THE DIRECTOR OF THE LAB NEEDS TO HAVE
 THE SIGNATURE OF THE DIRECTOR. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
 3F) AT THIS TIME IT IS UNCERTAIN IF THERE NEEDS TO BE
 OCCUPANCY SEPARATION BETWEEN THE LAB AND THE EQUIPMENT
 STORAGE ROOM. THE MAINTENANCE EQUIPMENT STORAGE ROOM IS
 284 SQUARE FEETLESS THAN 10% OF THE FLOOR AREA OF THE
 BUILDING. IF PART OF THE CONTROL AREA, ADDITIONAL
 COMMENTS MAY OCCUR UNDER THE MECHANICAL PLAN REVIEWER.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
  
 3G) OK.
  
 ORIGINAL COMMENT:
 3H)(1) SHEET A2 THE DOOR SCHEDULE INDICATES THE
 OVERHEAD GARAGE DOOR IS BEING REPLACED, PLEASE PROVIDE
 THE PRODUCT APPROVAL FOR THIS DOOR. COMPONENTS &
 CLADDING. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
  
 (31)(A) EXTERIOR OVERHEAD GARAGE DOORS ,
  
 RESPONSE:
 PRODUCT APPROVAL NOT SUBMITTED AT THIS TIME.
 THIS CAN BE A DEFERRED SUBMITTAL.
  
  
 ORIGINAL COMMENT:
 3H)(2) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.
  
 RESPONSE:
 TO BE DONE AT TIME OF PRODUCT APPROVAL SUBMITTAL.
  
  
 ORIGINAL COMMENT:
 3I) IN THE BREAK AREA/ COMMUNITY SPACE THERE IS A
 BARRIER FREE ELECTRIC WATER COOLER AND REFERENCES THE
 PLUMBING CODE SECTION 404.2. PLEASE NOTE THERE IS NO
 404.2 IN THE 2017 FBC-PLUMBING CODE. YOU DO HAVE TO
 COMPLY WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 RESPONSE:
 PLANS ARE NOT SHOWING DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE. PLANS ARE ONLY CITING SECTIONS OF
 THE FBC- ACCESSIBILITY CODE. PROVIDE COMPLETE DETAILS
 SHOWING COMPLIANCE. DON'T JUST CITE CODE SECTIONS. SEC.
 107.2.1 CITY AMENDMENTS.
  
  
 3J) OK.
 3J)(1) OK.
 3J)(2) OK.
 3K) OK
 3K)(1) OK
 3K)(2)OK
 3K)(3) OK
 3K)(4)OK
 3L) OK
  
 ORIGINAL COMMENT:
 4A) BOTH THE M1 AND E1 BOTH SHOW NEW ROOF TOP UNITS
 PLEASE PROVIDE PRODUCT APPROVAL FOR THE NEW ROOF TOP
 CURB. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) ROOF TOP CURBS
  
 RESPONSE:
 DEFERRED SUBMITTAL
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 RESPONSE:
 DEFERRED SUBMITTAL
  
  
 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 2017 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 RESPONSE:
 DEFERRED SUBMITTAL
  
 ORIGINAL COMMENT:
 5) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY WIND
 DESIGN CRITERIA FOR THE REPLACEMENT OVERHEAD GARAGE
 DOOR NOR THE ROOF TOP A/C UNITS.
  
 RESPONSE:
 REVISE WIND DESIGN DATA ON SHEET A-2. ACCORDING TO SEC.
 1609.4 THIS BUILDING IS LOCATED IN EXPOSURE "C" NO
 EXPOSURE "B". REVISE AS REQUIRED AND REVISE DESIGN
 PRESSURES ACCORDINGLY. ALSO, PROVIDE THE SIZE OF THE
 OVERHEAD GARAGE DOOR TO BE REPLACED TO VERIFY DESIGN
 PRESSURES.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. OK.
 5.2. OK.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 RESPONSE:
 REVISE WIND EXPOSURE
  
 5.4. OK.
 5.5. OK.
  
 ORIGINAL COMMENT:
 6) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY
 STRUCTURAL INFORMATION OF HOW THE ROOF TOP DECK IS TO
 BE CUT NOR ROOF FRAMING TO BE STRENGTHEN FOR THE
 ADDITIONAL WEIGHT AND POINT LOADING OF THE ROOF JOIST.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 RESPONSE:
 PLANS STILL DON'T SHOW ANY STRUCTURAL INFORMATION ABOUT
 THE ROOF TOP DECK PREPARATION TO RECEIVE THE NEW
 ADDITIONAL LOAD OF THE A/C CONDENSER UNIT. IT DOESN'T
 SPECIFY THE STRUCTURAL SUPPORTS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 7) 2017 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL
 BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF
 HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE
 ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO PREVENT THE PASSAGE OF A SPHERE 21 INCHES IN
 DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT,
 FAN OR COMPONENT.
  
 RESPONSE:
 PROVIDE EXACT LOCATION OF ROOF TOP UNIT. COORDINATE
 WITH ITEM #6 ABOVE.
  
 8) OK.
  
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 NEW COMMENT:
 10-THIS BUILDING IS NOT SPRINKLERED. ACCORDING TO
 EXCEPTION #4 OF SEC. 1020.1 FBC THE CORRIDORS NEED TO
 BE FIRE RATED IN ACCORDANCE WITH TABLE 1020.1. REVISE
 PLANS AS REQUIRED TO COMPLY.
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By jwitmer Date 2019-01-03 Time 13:34 Rev Time 0.00
Received By jwitmer Date 2019-01-03 Time 07:27 Sent To  
Notes
2019-01-03 13:34:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18111103
 ADD: 901 NORTHWOOD PARKWAY, SUITE: 202-205
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-373-3902
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 03/2019
 ACTION: DENIED
  
 1) THE COVERSHEET CS-1 AND LIFE SAFETY SHEET LS-1 BOTH
 INDICATE THIS BUILDING IS UNSPRINKLERED. THE LIFE
 SAFETY SHEET CHAPTER 10 SCHEDULE TYPICAL: INDICATES THE
 FIRE SPRINKLER SYSTEM 100%. PLEASE CORRECT THE
 DISCREPANCY BETWEEN THE BUILDING BEING FIRE SPRINKLERED
 AND UNSPRINKLERED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) THE LIFE SAFETY SHEET CHAPTER 10 SCHEDULE TYPICAL IS
 TAKING CREDIT FOR FIRE SPRINKLERS, IF THE BUILDING IS
 NOT FIRE SPRINKLERED THEN CORRECT THE FOLLOWING:
  
 2A) COMMON PATH OF TRAVEL IS TAKEN AT 100 FEET,
 ASSEMBLY & BUSINESS OCCUPANCY, OCCUPANT LOAD OF 97 AND
 UNSPRINKLERED THE COMMON PATH OF TRAVEL IS 75 FEET.
 2017 FBC-B TABLE 1006.2.1.
  
 2B) TRAVEL DISTANCE IS LISTED AT 300 FEET PER FBC-B
 TABLE 1017.2 FOR ASSEMBLY AND BUSINESS IS AGAIN FOR A
 FIRE SPRINKLERED BUILDING SEE TABLE 1017.2 OF THE
 FBC-B.
  
 2C) THE EXIT SEPARATION DISTANCE IS ALSO TAKEN AT 1/3RD
 THE OVERALL DIAGONAL DISTANCE OF THE BUILDING WHICH IS
 AN EXCEPTION FOR FIRE SPRINKLERED BUILDINGS. IF THE
 BUILDING IS NOT FIRE SPRINKLERED THEN THE FBC-B SECTION
 1007.1.1 WOULD REQUIRE THE DIAGONAL DISTANCE TO BE ? OF
 THE OVERALL DIAGONAL DISTANCE.
  
 3) SHEET A-1 THE FLOOR PLAN:
  
 3A) PLEASE NOTE THE PHASE I/ PHASE II LABELING ON THE
 LEFT SIDE OF THE PLAN, CENTER OF THE PLAN ARE THE SAME
 WITH THE LAB AS PART OF PHASE L. JUST TO THE RIGHT OF
 THE LAB AND MAINTENANCE EQUIPMENT STORAGE ROOM THE
 LABELING FOR THE PHASING IS REVERSED. PLEASE CORRECT
 THE DISCREPANCY IN THE LABELING FOR THE PHASING PLAN.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3B) PLEASE PROVIDE IS THE INTENT OF PHASING OCCUPYING
 THE LAB AND EQUIPMENT STORAGE ROOM BEFORE THE OFFICES
 ARE OCCUPIED? AS SHOWN THE RESTROOMS ARE IN THE PHASE
 LL PART OF THE PHASING PLAN, WILL THERE BE TEMPORARY
 WALLS FOR EMPLOYEES TO BE ABLE TO GO TO THE RESTROOMS
 WITHOUT GOING THROUGH A CONSTRUCTION.
  
 2017 FBC-B 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE
 PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE
 MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR
 ADDITIONS TO ANY BUILDING OR STRUCTURE.
  
 3C) WALL TYPES: THE WALLS LABELED C-2 IN THE WALL
 SCHEDULE ARE LABELED 1 HOUR FIRE WALLS:
  
 3C)(1) THE WALLS THAT SURROUND THE LAB ARE WALLS
 SEPARATING WHAT MOST LIKELY WILL BE A CONTROL AREA FROM
 OTHER OCCUPANCIES AND ARE TO BE IDENTIFIED AS FIRE
 BARRIERS SEE 2017 FBC-B SECTION 707.3.8.
  
 3C)(2) THERE ARE ADDITIONAL WALLS IDENTIFIED AS C-2
 TYPE WALLS BETWEEN THE OPEN OFFICE AND THE OFFICES TO
 THE RIGHT OF THIS WALL AND CONFERENCE ROOM. THIS WALL
 DOES NOT NEED TO BE FIRE RATED. THE DESIGNER OF RECORD
 HAS LABELED THIS WALL AS AN 1 HOUR FIRE WALL. THE FBC-B
 TABLE 706.4 THERE IS NO 1 HOUR FIRE WALL RATING
 SEPARATING OCCUPANCIES.
  
 3D) IN THE CENTER OF THE PLAN THERE IS A ROOM LABELED A
 LAB. PLEASE NOTE DEFINING AN AREA AS A LAB IS A VERY
 BROAD IN DETERMINING CODE COMPLIANCE. THE QUESTION IS
 IT APPEARS THE DESIGNER OF RECORD IS TRYING TO ENCLOSE
 THE LAB AND EQUIPMENT STORAGE ROOM (HIGHER HAZARD
 OCCUPANCY) WITH 1 HOUR FIRE RATED WALLS. THE 4
 RESTROOMS ARE ALSO INCLUDED IN THE 1 HOUR FIRE RATED
 WALL ASSEMBLY. THIS MEANS THE ASSEMBLY AND BUSINESS
 OCCUPANCIES ARE GOING INTO A MORE HAZARDOUS OCCUPANCY
 TO USE THE RESTROOMS. IT WOULD APPEAR THE DESIGN
 PROFESSIONAL?S INTENT WAS TO HAVE THE 1 HOUR FIRE
 RATING BEHIND THE REAR RESTROOM WALLS TO ALLOW THE
 OCCUPANTS FROM THE ASSEMBLY AND BUSINESS OCCUPANCY TO
 USE THE 4 RESTROOMS. SEE 2017 FBC-B TABLE 508.4.
  
 3E) AT THIS TIME THE OCCUPANCY OF THE LAB, CANNOT BE
 DETERMINED THE USAGE WILL NEED TO BE BETTER DEFINED.
 WHAT TYPES OF HAZARDOUS MATERIALS ARE TO BE USED IN THE
 DAY TO DAY USAGE OF THE LAB. PLEASE PROVIDE AMOUNT OF
 HAZARDOUS MATERIALS, IF THEY ARE SOLIDS, LIQUIDS, AND
 OR GASEOUS MATERIALS( FC-B TABLE 307.1(1), IF THEY ARE
 GOING TO BE STORED IN 1 HOUR FIRE RATED CABINETS, AND
 IF THIS ROOM (LAB) IS TO BE CONSIDERED A 1 HOUR FIRE
 CONTROL AREA IN COMPLIANCE WITH 2017 FBC-B SECTION
 414.2 THROUGH 414.4. PLEASE ALSO SUBMIT THE MSDS SHEETS
 FOR ALL CHEMICALS TO BE USED IN THE DAILY PROCESS OF
 THE LAB. A NARRATIVE FROM THE TENANT MAYBE OF HELP OF
 WHAT WORK, OR PROCESS WILL OCCUR IN THE ROOM CONSIDERED
 A LAB.
  
 3F) AT THIS TIME IT IS UNCERTAIN IF THERE NEEDS TO BE
 OCCUPANCY SEPARATION BETWEEN THE LAB AND THE EQUIPMENT
 STORAGE ROOM. THE MAINTENANCE EQUIPMENT STORAGE ROOM IS
 284 SQUARE FEETLESS THAN 10% OF THE FLOOR AREA OF THE
 BUILDING. IF PART OF THE CONTROL AREA, ADDITIONAL
 COMMENTS MAY OCCUR UNDER THE MECHANICAL PLAN REVIEWER.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3G) THERE ARE 8 DOORS ON SHEET A2 THE DOOR SCHEDULE
 THAT ARE LABELED C LABELED DOORS. PLEASE NOTE THESE
 DOORS ARE 12, 13, 14, 18, 19, 20, 21, & 38. IN THE 2017
 FBC-B THE RATING OF FIRE RATED DOORS IS IN MINUTES AND
 IN HOURS, PLEASE SEE FBC-B TABLE 716.5 FOR THE FIRE
 RATING FOR FIRE BARRIERS AND FIRE PARTITIONS AND DOOR
 RATING.
 3H)(1) SHEET A2 THE DOOR SCHEDULE INDICATES THE
 OVERHEAD GARAGE DOOR IS BEING REPLACED, PLEASE PROVIDE
 THE
 PRODUCT APPROVAL FOR THIS DOOR. COMPONENTS & CLADDING.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR OVERHEAD GARAGE DOORS ,
  
 3H)(2) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 3I) IN THE BREAK AREA/ COMMUNITY SPACE THERE IS A
 BARRIER FREE ELECTRIC WATER COOLER AND REFERENCES THE
 PLUMBING CODE SECTION 404.2. PLEASE NOTE THERE IS NO
 404.2 IN THE 2017 FBC-PLUMBING CODE. YOU DO HAVE TO
 COMPLY WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 3J) SHEET A-1 IN THE BREAK ROOM THERE IS SHOWN 2
 MICROWAVES BUT IN THE DETAIL 2/ A-3 THEY ARE NOT SHOWN?
 THERE IS 2 OPEN SHELVES NOTE # 10. ON THE ELECTRIC
 SHEET E-1 IN THIS SAME AREA SHOWS 2 GFCI 20 AMP
 RECEPTACLES AT 64 INCHES OFF THE FLOOR. PLEASE NOTE IF
 THE MICROWAVES ARE LOCATED ON THE OPEN SHELVES THEY
 WILL NEED TO SHOW HOW THEY COMPLY WITH:
  
 3J)(1) 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 3J)(2) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 3K) THE LS-1 SHEET NOR THE A-1 SHEET SHOW ANY TABLES OR
 CHAIRS IN THE COMMUNITY SPACE WHEREAS THE E1, M1 AND P1
 SHEETS ALL SHOW TABLES AND CHAIRS. PLEASE SHOW
 COMPLIANCE WITH THE 2017 ACCESS. CODE:
  
 3K)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 3K)(2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 3K)(3) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 3K)(4) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 3L) THE BOTTOM OF SHEET A-1 THERE IS A NOTE FOR
 ALTERNATE PRICING. THE WEST PALM BEACH CHAPTER 1
 ADMINISTRATION SECTION 107.2.1 DOES NOT ALLOW FOR
 ALTERNATES. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 4A) BOTH THE M1 AND E1 BOTH SHOW NEW ROOF TOP UNITS
 PLEASE PROVIDE PRODUCT APPROVAL FOR THE NEW ROOF TOP
 CURB. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) ROOF TOP CURBS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 2017 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
  
 5) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY WIND
 DESIGN CRITERIA FOR THE REPLACEMENT OVERHEAD GARAGE
 DOOR NOR THE ROOF TOP A/C UNITS.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY
 STRUCTURAL INFORMATION OF HOW THE ROOF TOP DECK IS TO
 BE CUT NOR ROOF FRAMING TO BE STRENGTHEN FOR THE
 ADDITIONAL WEIGHT AND POINT LOADING OF THE ROOF JOIST.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) 2017 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL
 BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF
 HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE
 ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO PREVENT THE PASSAGE OF A SPHERE 21 INCHES IN
 DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT,
 FAN OR COMPONENT.
  
 8) 2017 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE
 PROVIDED WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN
 10 FEET OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE
 OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2019-04-02 Cont ID  
Sent By jpearson Date 2019-04-02 Time 11:02 Rev Time 0.00
Received By jpearson Date 2019-04-02 Time 10:53 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-06 Cont ID  
Sent By jpearson Date 2019-03-06 Time 08:27 Rev Time 0.00
Received By jpearson Date 2019-03-06 Time 06:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-25 Cont ID  
Sent By jpearson Date 2018-12-25 Time 07:17 Rev Time 0.00
Received By jpearson Date 2018-12-25 Time 07:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-03-26 Cont ID  
Sent By pleduc Date 2019-03-26 Time   Rev Time 0.00
Received By pleduc Date 2019-03-26 Time 10:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-02-13 Cont ID  
Sent By pleduc Date 2019-02-13 Time   Rev Time 0.00
Received By pleduc Date 2019-02-13 Time 14:15 Sent To  
Notes
2019-02-13 14:18:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) FOR VERIFICATION PURPOSES, PLEASE PROVIDE THE
 MANUFACTURE'S SPECIFICATION SHEETS FOR THE "VENTLESS
 OVEN" IN THE LAB AREA TO THE FIRE INSPECTOR ON
 INSPECTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-12-03 Cont ID  
Sent By pleduc Date 2018-12-03 Time   Rev Time 0.00
Received By pleduc Date 2018-12-03 Time 14:26 Sent To  
Notes
2018-12-03 14:57:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) SHEET A 1 - THERE IS AN INDICATION OF A LAB;
 HOWEVER, THERE IS NO INDICATION OF WHAT THIS LAB IS
 BEING USED FOR.
  
 PLEASE PROVIDE DETAIL INFORMATION OF THE TYPE OF WORK
 PERFORMED WITHIN THIS LAB..
  
  
  
  
 2) SHEET CS 1 - THERE ARE INDICATIONS OF SEPARATE
 OCCUPANCY LOADS; HOWEVER, THERE IS NO OCCUPANCY
 CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE.
  
 PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION AND WHETHER
 IT IS MIXED OR SEPARATED. (IT APPEARS TO BE SPEPARATED
 ON SHEET A 1, NEED FOR CLARIFICATION PURPOSES)
  
  
  
  
 3) SHEET A 1 - THERE IS AN INDICATION OF OVEN WITHIN
 THE LAB ROOM. THERE IS NO INDICATION OF WHAT THIS OVEN
 IS USED FOR AND OR ANY VENTING REQUIREMENTS.
  
 PLEASE PROVIDE DETAILS.
  
 ANY PROPOSED VENTING SHALL BE PER NFPA 96 AND UNDER
 SEPARATE SHOP DRAWINGS. PROVIDE AN APPLICABLE NOTE.
  
  
  
  
 4) SHEET A 1 - 1 HOUR FIRE WALLS ARE INDICATED AROUND
 THE LAB ROOM. PER # 2 ABOVE WHAT IS THE REQUIRED RATING
 OF THE SEPARATION OF OCCUPANCIES. IT MAY BE 2 HOURS.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH APPLICABLE
 FIRE CODE REFERNECES.
  
  
  
  
 5) SHEET A 1 - C2 RATED WALLS ARE INDICATED AROUND THE
 LAB, HOWEVER, AT THE BATHROOM AREA THE RATING STOPS AT
 THE DOOR EXPOSING THE INTERIOR OF THE BATHROOMS TO THE
 HAZARD.
  
 THE BATHROOM WALLS ARE REQUIRED TO BE HAVE THIS RATING.
 FOR DISSCUSSION PURPOSES, THE OUTSIDE BATHROOM WALLS
 INCLUDING THE DOORS WOULD NOT BE REQUIRED TO BE RATED.
 THE RATING WOULD STOP AT THE WALLS DIRECTLY IN CONTACT
 WITH THE LAB.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 6) SHEET A 1 - THERE IS AN INDICATION OF B2 WALLS (BY
 DOOR 21) THAT APPEAR TO REQUIRE C2 RATINGS.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH FIRE CODE
 REFERENCES.
  
  
  
  
 7) SHEET A 1 - THERE ARE INDICATIONS OF B WALLS AROUND
 THE ELECTRIC ROOM. THERE IS NO CALL OUT FOR B WALLS. IN
 ADDITION, THERE WALLS APPEAR TO REQUIRE C2 RATINGS.
  
 PLEASE REIVEW AND CORRECT OR JUSTIFY WILL FIRE CODE
 REFERENCES.
  
  
  
  
 8) SHEET A 2 - THE DOOR SCHEDULE HAS INDICATIONS OF C
 LABELS.
  
 FOR CLARIFICATION PURPOSES PLEASE PROVIDE FIRE RATING
 TIME FOR THESE DOORS PER THE FFPC AND ENSURE THE ARE IN
 COMPLIANCE WITH ANY CHANGES TO # 2 & 4.
  
  
  
  
 9) SHEET E 2 - THERE ARE TWO (2) EXITS INDICATED FOR
 THE LAB AREA. BASED ON THE CLASSIFICATION OF THIS
 OCCUPANCY AND BEING SEPARATED FOR THE OTHER
 OCCUOPANCIES, THESE TWO (2) EXITS MAY BE REQUIRED PER
 THE FFPC TO BE SEPARATED BY 1/2 THE DIAGONAL OF THE
 SPACE SERVED.
  
 THESE EXITS APPEAR TO TOO CLOSE TO EACH OTHER TO MEET
 THIS REQUIREMENT.
  
 PER NFPA 101, CHAPTER 7,
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5..
  
  
  
 PLEASE REVIEW THE OCCUPANCY OF THE LAS PER THE FFPC AND
 THE REQUIRED EIXTING AND CORRECT IF APPLICABLE.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-04-02 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-22 Time 15:23 Sent To  
Notes
2019-04-02 09:12:47JPEARSON'S DESK
2019-03-25 15:23:17C05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-08 Cont ID  
Sent By gjohnson Date 2019-03-08 Time 13:33 Rev Time 0.00
Received By gjohnson Date 2019-02-06 Time 14:34 Sent To  
Notes
2019-02-07 14:34:55C07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-15 Cont ID  
Sent By gjohnson Date 2019-01-15 Time 07:30 Rev Time 0.00
Received By gjohnson Date 2018-11-27 Time 12:40 Sent To  
Notes
2018-11-29 12:40:58C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-01-03 Cont ID  
Sent By jwitmer Date 2019-01-03 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2019-01-03 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-03-28 Cont ID  
Sent By ccole Date 2019-03-28 Time 15:17 Rev Time 0.00
Received By ccole Date 2019-03-28 Time 15:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-08 Cont ID  
Sent By ccole Date 2019-03-08 Time 08:12 Rev Time 0.00
Received By ccole Date 2019-03-07 Time 17:12 Sent To  
Notes
2019-03-08 08:24:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18111103
 3/8/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN REFERENCE TO COMMENT #1 FROM THE 1ST REVIEW, THE
 REQUESTED MSDS SHEETS FOR THE MATERIALS BEING TESTED
 WERE NOT SUBMITTED.
  
 2) IN REFERENCE TO COMMENT #5 FROM THE 1ST REVIEW,
 PLEASE SUBMNIT MANUFACTURER'S SPECIFICATIONS FOR THE
 SLOW COOKER.
  
 3) NEW COMMENT, SHEET M-1: SMOKE DETECTORS ARE REQUIRED
 IN THE SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER
 SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION
 CAN BE APPLIED IF THE MANUFACTURER'S SPECIFICATIONS
 INDICATE THE SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER
 2000 CFMS OF SUPPLY AIR.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By ccole Date 2019-01-02 Time 16:55 Rev Time 0.00
Received By ccole Date 2019-01-02 Time 15:56 Sent To  
Notes
2019-01-02 17:18:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18111103
 1/2/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A HAZARDOUS EXHAUST SYSTEM MAY BE REQUIRED FOR THE
 MATERIALS TESTING LAB UNLESS THE EXCEPTION UNDER
 SECTION 510.2 FBC M IS MET. PLEASE REVIEW THE CODE
 SECTION AND EXCEPTION COPIED BELOW. EVIDENCE OF
 COMPLIANCE WILL REQUIRE A NARRATIVE THAT DESCRIBES THE
 PROCESSES THAT OCCUR IN THE LAB, A LIST OF MATERIALS TO
 BE TESTED, A LIST OF CHEMICALS USED IN THE TESTING
 PROCESS, AND THE QUANTITIES OF MATERIALS AND CHEMICALS
 TO BE USED AND STORED IN THE LAB. SEE ALSO SECTION
 414.1.3 AND PROVIDE MSDS SHEETS FOR ALL MATERIALS AND
 CHEMICALS.
  
 510.2 WHERE REQUIRED.
 A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER
 OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF
 HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST
 SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE
 POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS:
  
 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT
 IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER
 FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED
 ROOM TEMPERATURE.
  
 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 4 IS PRESENT IN ANY CONCENTRATION.
  
 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS
 EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION
 OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY.
  
 EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1,
 EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE
 EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A
 HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN
 CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL
 CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION
 TOXICITY.
  
 2) : REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC M. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR. CONCERNING THE HOTEL TOUCHDOWN, LAN AND WORK
 ROOMS, PLEASE CLARIFY WHAT FUNCTIONS TAKE PLACE IN THE
 ROOMS AND HOW THE VENTILATION IS BEING SIZED.
  
 3) SHEET M-1: PROVIDE AN EQUIPMENT SCHEDULE FOR EF-2 IN
 THE LAB AND INDICATE HOW THE FAN WAS SIZED- PROVIDE AN
 EXHAUST VENTILATION CALCULATION AND A SEQUENCE OF
 OPERATION. PLEASE NOTE THAT EXHAUST AT A RATE OF 1.0
 CFMS PER SF. IS REQUIRED FOR A LAB IN ACCORDANCE WITH
 TABLE 403.3.1.1 FBC M.
  
 4) M-1: THE EXHAUST TERMINATION FOR THE HOOD IN THE LAB
 APPEARS TO BE WITHIN THE REQUIRED MINIMUM 10' CLEARANCE
 TO THE ENTRY DOOR AND THE OVERHEAD DOOR- SEE SECTION
 501.3.1 FBC M AND SHOW COMPLIANCE.
  
 5) M-1: LAB EXHAUST HOOD: A) CLARIFY THE PURPOSE AND
 FUNCTION OF THE HOOD. WHAT IS THE PROCESS THAT OCCURS
 UNDER THE HOOD AND WHAT FUMES, DUSTS, MISTS ETC. ARE
 BEING EXHAUSTED. B) PROVIDE AN EQUIPMENT SCHEDULE FOR
 THE HOOD AND SUBMIT MANUFACTURER'S SPECIFICATIONS. C)
 PROVIDE ENLARGED DIMENSIONED ELEVATION AND PLAN VIEWS
 OF THE HOOD THAT INDICATE REQUIRED INSTALLATION AND
 CLEARANCE HEIGHTS ETC.
  
 6) M-1: INDICATE HOW O/A IS BEING PROVIDED AND
 CONTROLLED FOR AHU'S 1, 2, & 3.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-04-02 Cont ID  
Sent By jesmith Date 2019-04-02 Time 08:52 Rev Time 0.00
Received By jesmith Date 2019-04-02 Time 08:17 Sent To  
Notes
2019-04-02 08:52:01APPROVED
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. MSDS SHEETS ON ANY CHEMICALS THAT ARE BEING USED IN
 THE TEST LAB ARE PART OF THE APPROVED
 PLANS/DOCUMENTATION.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-08 Cont ID  
Sent By gjohnson Date 2019-03-08 Time 11:39 Rev Time 0.00
Received By gjohnson Date 2019-03-08 Time 11:39 Sent To  
Notes
2019-03-08 11:39:51PROVISO:
  
 1ST REVIEW: 18111103
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-1 THE NOTE UNDER THE ELECTRIC WATER COOLER IS
 STATING CODE SECTION 404.2 FBC PLUMBING THIS SECTION
 DOES NOT EXIST WATER COOLERS SHALL COMPLY WITH FBC PL
 410 AND FBC ACC 211, 602 PLEASE PROVIDE DETAILS SHOWING
 COMPLIANCE WITH FBC ACC 602.2, 602.4, 602.5, 602.7, 306
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 694.6 FLUSH
 CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND
 OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. FLUSH
 CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE WATER
 CLOSET.
  
 3. PROVIDE MSDS SHEETS ON ANY CHEMICALS THAT ARE BEING
 USED. PER WPB AMEND TO FBC 107.2.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-15 Cont ID  
Sent By gjohnson Date 2019-01-15 Time 07:29 Rev Time 0.00
Received By gjohnson Date 2019-01-14 Time 08:29 Sent To  
Notes
2019-01-15 07:29:531ST REVIEW: 18111103
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-1 THE NOTE UNDER THE ELECTRIC WATER COOLER IS
 STATING CODE SECTION 404.2 FBC PLUMBING THIS SECTION
 DOES NOT EXIST WATER COOLERS SHALL COMPLY WITH FBC PL
 410 AND FBC ACC 211, 602 PLEASE PROVIDE DETAILS SHOWING
 COMPLIANCE WITH FBC ACC 602.2, 602.4, 602.5, 602.7, 306
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 694.6 FLUSH
 CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND
 OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. FLUSH
 CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE WATER
 CLOSET.
  
 3.PLEASE PROVIDE A DESCRIPTION OF THE FOLLOWING. PER
 WPB AMEND TO FBC 107.2.1
 A) TYPE OF TESTING BEING DONE IN THE LAB.
 B) THE TYPE OF CHEMICALS BEING USED.
 C) THE AMOUNTS OF THE CHEMICALS THAT ARE BEING STORED.
 D) HOW THE CHEMICALS ARE BEING STORED.
 E) THE AMOUNT AND TYPE THAT IS BEING DISCHARGED TO THE
 SANITARY.
  
 4. PROVIDE MSDS SHEETS ON ANY CHEMICALS THAT ARE BEING
 USED. PER WPB AMEND TO FBC 107.2.1
  
 5. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACES
 FOR THE TOILET LAVATORY AND WATER FOUNTAIN. PER FBC ACC
 604.3.1, 602.2, 606.2
  
 6. SHT P-2 UNDER THE THE NOTES AT THE BOTTOM OF THE
 PLAN SHEET #2 IS REFERENCING CODE SECTION FBC 2318.15
 AND 2510.5.11 THAT DO NOT EXIST OR DO NOT APPLY TO
 PLUMBING FIXTURE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 7. SHT P-2 UNDER THE THE NOTES AT THE BOTTOM OF THE
 PLAN SHEET #3 IS REFERENCING CODE SECTION FBC PL 424.4
 THAT APPLIES TO GANG SHOWERS THERE ARE NO SHOWERS SHOWN
 ON PLAN PLEASE CLARIFY . PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P-2 THE PLUMBING FIXTURE SCHEDULE IS LISTING A
 DROP IN LAVATORY SINK THE PLANS SHOW A WALL HUNG IF THE
 DROP IN IS BEING USED PROVIDE DETAIL OF VANITY TOP
 COMPILING WITH FBC ACC 606.2 AND 606.3
 OR REVISE PLUMBING SCHEDULE TO LIST WALL HUNG LAVATORY.
  
 9. THE FLOOR DRAIN IN THE LAB ARE NOT VENTED ON THE
 SANITARY ISOMETRIC SHALL COMPLY WITH FBC PL 901.2, 919
  
 10. A BACKFLOW DEVISE IS REQUIRED FOR THE REFRIGERATOR
 ICE MAKER A NOTE ON THE PLAN WILL SUFFICE. PER FBC PL
 608.3
  
 11. PLEASE INDICATE ON THE PLAN THE LEVEL OF ALTERATION
 PER FBC EXISTING CH5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-07 Cont ID  
Sent By ajones Date 2018-12-07 Time 09:50 Rev Time 0.00
Received By ajones Date 2018-12-07 Time 09:50 Sent To  
Notes
***NONE***