Plan Review Details - Permit 18111079
Plan Review Stops For Permit 18111079
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-27 Cont ID  
Sent By jgomez Date 2019-02-27 Time 08:57 Rev Time 0.00
Received By jgomez Date 2019-02-26 Time 08:26 Sent To  
Notes
2019-02-27 08:58:16BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE ENERGY CALCULATIONS FOR THE MAIN
 HOUSE. ONLY COVER PAGE WAS SUBMITTED.
 2-PROVIDE PRODUCT APPROVAL FOR: A)INSWING ARCHED ENTRY
 DOOR SIZE AS SHOWN ON PLANS. B) PROVIDE CURRENT
 POLYSTICK TU-PLUS PRODUCT APPROVAL. FL5259-R10
 SUBMITTED IS TOO OLD. AND CLEARLY IDENTIFY WHICH
 ASSEMBLY IS GOING TO BE USED.
 3- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE
 FOOTING OF PRIVACY WALL WHEN THE WALL IS LOCATED AT THE
 PROPERTY LINE. FOOTING CAN NOT ENCROACH BEYOND THE
 PROPERTY LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-02-22 Cont ID  
Sent By jgomez Date 2019-02-22 Time 18:17 Rev Time 0.00
Received By jgomez Date 2019-02-22 Time 17:43 Sent To  
Notes
2019-02-22 18:24:03NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTES:
 ***(1) BUILDING WILL BE APPROVED WITH PROVISO ONCE THE
 STRUCTURAL ENGINEER UPDATES THE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION. ACCORDING TO DBPR WEBSITE
 THE CERTIFICATE OF AUTHORIZATION #8495 IS NULL AND
 VOID. THE ENGINEER REMOVED THE ENGINERING FIRM NAME BUT
 THE FIRM CERTIFICATE OF AUTHORIZATION #8495 IS SHOWN ON
 THE TITLE BLOCK. REVISE AS REQUIRED.
 CHAPTER 471 F.S.
  
 ***(2) DIGITAL SIGNATURE ON DRAWING S-1.0 IS INVALID.
 THERE IS AN ERROR ON THE SIGNATURE VERIFICATION. PLEASE
 REVISE.
  
  
  
  
 1- OK
  
 2-
  
 3- OK
  
 4- OK
  
 5- ENERGY CALCULATIONS: NEED TO PROVIDE THE ENERGY
 CALCULATIONS FOR THE MAIN HOUSE. ONLY THE ENERGY
 CALCULATIONS FOR THE GUEST SUITE WERE SUBMITTED. SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 RESPONSE:
 ONLY THE COVER PAGE SIGNED BY THE OWNER/AGENT WAS
 PROVIDED. MISSING THE REST OF THE REPORT. UNABLE TO
 REVIEW.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 6- OK
  
 7- OK
  
 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) INSWING ARCHED ENTRY DOOR SIZE AS SHOWN ON PLANS.
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL15001.2 SUBMITTED IS NOT FOR
 INSWING DOOR AND SIZE DOESN'T MATCH SPECIFIED SIZE.
  
 B) OK.
  
 C) OK
  
 D) OK.
  
 E) OK. .
  
 F)POLYSTICK TU-PLUS FLORIDA PRODUCT APPROVAL FL5259-R10
 SUBMITTED IS TOO OLD. PROVIDE CURRENT FLORIDA PRODUCT
 APPROVAL OR MIAMI -DADE NOA. AND CLEARLY IDENTIFY WHICH
 ASSEMBLY IS GOING TO BE USED TO VERIFY DESIGN PRESSURES
 LIMITATIONS. .
  
 G) OK.
  
 H)OK
  
 9- OK
  
 10- OK
  
 11-OK
  
 12- OK
  
 13- OK.
  
 14- OK
  
 15- OK
  
 16-OK
  
 17- STRUCTURAL ENGINEER NEEDS TO HAVE A CURRENT
 ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION. SEC.
 61G15-23.002 AND CHAPTER 471 F.S. COORDINATE WITH DBPR.
  
 RESPONSE:
 REPEAT COMMENT: ACCORDING TO DBPR CERTIFICATE OF
 AUTHORIZATION #8495 FOR THE ENGINEERING COMPANY IS NOT
 VALID. ENGINEER TO UPDATE INFORMATION WITH DBPR.
 OTHERWISE, IT WILL BE REPORTED TO THE BOARD OF
 ENGINEERS AND DBPR.
  
 18- SHEET A-14: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE PRIVACY
 WALLS AND GATES. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 NEED TO PROVIDE ADDITIONAL FOOTING DETAIL WHEN THE WALL
 IS LOCATED AT THE PROPERTY LINE. FOOTING CAN NOT
 ENCROACH BEYOND THE PROPERTY LINE.
  
 19- OK
  
 20- OK
  
 *** NEED SOIL TEST REPORT DIGITAL SIGNATURE OR HARD
 COPY WITH ORIGINAL SIGNATURE
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-15 Cont ID  
Sent By jgomez Date 2019-02-15 Time 18:56 Rev Time 0.00
Received By jgomez Date 2019-02-15 Time 10:54 Sent To  
Notes
2019-02-15 16:55:46NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 IMPORTANT:
 STRUCTURAL ENGINEER NEEDS TO UPDATE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION BEFORE ISSUING PROVISO.
  
 1- OK
  
 2- NO CLEAR. NO PAID RECEIPT SUBMITTED. SEE SAMANTHA
 HILL COMMENTS UNDER THE IMPACT REVIEW STOP.
  
 3- OK
  
 4- OK
  
 5- ENERGY CALCULATIONS: NEED TO PROVIDE THE ENERGY
 CALCULATIONS FOR THE MAIN HOUSE. ONLY THE ENERGY
 CALCULATIONS FOR THE GUEST SUITE WERE SUBMITTED. SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 RESPONSE:
 ONLY THE COVER PAGE SIGNED BY THE OWNER/AGENT WAS
 PROVIDED. MISSING THE REST OF THE REPORT. UNABLE TO
 REVIEW.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 6- OK
  
 7- OK
  
 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) INSWING ARCHED ENTRY DOOR SIZE AS SHOWN ON PLANS.
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL15001.2 SUBMITTED IS NOT FOR
 INSWING DOOR AND SIZE DOESN'T MATCH SPECIFIED SIZE.
  
 B) OK.
  
 C) OK
  
 D) OK.
  
 E) OK. .
  
 F)POLYSTICK TU-PLUS FLORIDA PRODUCT APPROVAL FL5259-R10
 SUBMITTED IS TOO OLD. PROVIDE CURRENT FLORIDA PRODUCT
 APPROVAL OR MIAMI -DADE NOA. AND CLEARLY IDENTIFY WHICH
 ASSEMBLY IS GOING TO BE USED TO VERIFY DESIGN PRESSURES
 LIMITATIONS. .
  
 G) OK.
  
 H)OK
  
 9- OK
  
 10- OK
  
 11-OK
  
 12- OK
  
 13- OK.
  
 14- OK
  
 15- OK
  
 16-OK
  
 17- STRUCTURAL ENGINEER NEEDS TO HAVE A CURRENT
 ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION. SEC.
 61G15-23.002 AND CHAPTER 471 F.S. COORDINATE WITH DBPR.
  
 RESPONSE:
 REPEAT COMMENT: ACCORDING TO DBPR CERTIFICATE OF
 AUTHORIZATION #8495 FOR THE ENGINEERING COMPANY IS NOT
 VALID. ENGINEER TO UPDATE INFORMATION WITH DBPR.
 OTHERWISE, IT WILL BE REPORTED TO THE BOARD OF
 ENGINEERS AND DBPR.
  
 18- SHEET A-14: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE PRIVACY
 WALLS AND GATES. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 NEED TO PROVIDE ADDITIONAL FOOTING DETAIL WHEN THE WALL
 IS LOCATED AT THE PROPERTY LINE. FOOTING CAN NOT
 ENCROACH BEYOND THE PROPERTY LINE.
  
 19- OK
  
 20- OK
  
 *** NEED SOIL TEST REPORT DIGITAL SIGNATURE OR HARD
 COPY WITH ORIGINAL SIGNATURE
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-28 Cont ID  
Sent By jgomez Date 2018-12-28 Time 15:37 Rev Time 0.00
Received By jgomez Date 2018-12-27 Time 08:54 Sent To  
Notes
2018-12-20 17:49:15NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 SEC. R401.3 FBC_RESIDENTIAL:
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE
 APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR
 WHEN OTHERWISE WARRANTED.
  
 SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A
 LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
 2- PROVIDE PLANS WITH COUNTY IMPACT FEES STAMP AND
 PROVIDE COPY OF PAID RECEIPT ( $21.91).
  
 3- IT LOOKS LIKE SECOND FLOOR BEDROOM WINDOWS DON'T
 COMPLY WITH THE EMERGENCY ESCAPE AND RESCUE OPENINGS
 SEC. R310.2.1 FBC-RESIDENTIAL. WINDOW SCHEDULE SPECIFY
 5'-0" HIGH WINDOWS. TYPICALLY, 5-0" HIGH WINDOWS DON'T
 PROVIDE THE 24" CLEAR OPENING HEIGHT. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT SPECIFIED WINDOW
 SIZE PROVIDES 24" CLEAR OPENING AND MIN. TOTAL CLEAR
 OPENING OF 5.7S.F.
 NOTE: CLEARLY SPECIFY ALL WINDOW TYPES IN THE WINDOW
 SCHEDULE TO AVOID CONFLICT/DELAYS.
  
 4- SPECIFY WINDOW SILL HEIGHT OF SECOND FLOOR OPERABLE
 WINDOWS TO VERIFY COMPLIANCE WITH THE WINDOW FALL
 PROTECTION AS REQUIRED BY SEC. R312.2 FBC-RESIDENTIAL.
  
 5- ENERGY CALCULATIONS: NEED TO PROVIDE THE ENERGY
 CALCULATIONS FOR THE MAIN HOUSE. ONLY THE ENERGY
 CALCULATIONS FOR THE GUEST SUITE WERE SUBMITTED. SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
  
 6- GUEST SUITE ENERGY CALCULATIONS SUBMITTED:
 A)THE ENERGY FORM R405-2017 IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM BY THE OWNER OR OWNER?S LEGALLY
 DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 C) NUMBER OF BEDROOMS IS INCORRECT. THIS IS THE GUEST
 SUITE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 D) NEED INSULATION IN FLOOR ABOVE GARAGE AS REQUIRED BY
 SEC. R402.1.2 FBC-ENERGY CONSERVATION. REVISE ITEM #8.
  
 E) ROOF MATERIAL SPECIFIED IS INCORRECT. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F)WINDOWS ORIENTATION AND AREA DON'T MATCH ACTUAL
 ORIENTATION AND AREA SHOWN ON PLANS. REVISE AS REQUIRED
 TO MATCH. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G) WINDOWS OVERHANG SEPARATION DOESN'T MATCH PLANS.
 REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 H) PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS
 SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 7- DESIGNER OF RECORD TO SPECIFY INSULATION IN FLOOR
 ABOVE GARAGE AS REQUIRED BY SEC. R402.1.2 FBC-ENERGY
 CONSERVATION AND SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) INSWING ARCHED ENTRY DOOR AS SHOWN ON PLANS.
  
 B) PROVIDE FLORIDA PRODUCT APPROVAL COVER THAT
 CORRESPONDS TO DRAWINGS SUBMITTED FOR THE FRENCH DOOR.
  
 C) FRENCH DOORS WITH SIDELITES AS SHOWN ON PLANS.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 E) METAL ROOF AS SHOWN ON PLANS.
  
 F)ROOF UNDERLAYMENT NOA SUBMITTED: CLEARLY MARK WHICH
 UNDERLAYMENT IS GOING TO BE USED FOR THE CLAY TILE AND
 WHICH ONE IS GOING TO BE USED FOR THE METAL ROOF SHOWN
 AS SHOWN ON PLANS.
  
 G) SHUTTERS SHOWN ON EXTERIOR ELEVATIONS AND PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 H)ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGNER OF RECORD TO LIST THE FLORIDA
 PRODUCT APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- SPECIFY ON PLANS CARBON MONOXIDE ALARMS BY FIRST
 AND SECOND FLOOR BEDROOMS AS REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL.
  
 11- SPECIFY CEILING CONSTRUCTION ABOVE GARAGE TO SHOW
 COMPLIANCE WITH TABLE R302.6 FBC-RESIDENTIAL.
  
 12- STAIR RAILING DETAIL 3/09 DOESN'T APPLY TO THE
 EXTERIOR OR INTERIOR STAIRS. REVISE AS REQUIRED TO
 MATCH.
 TABLE R301.5 FBC-RESIDENTIAL.
  
 13- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807
 FBC-RESIDENTIAL.
  
 14- SIZE OF GUEST SUITE ENTRY DOOR (D10) DOESN'T COMPLY
 WITH THE EGRESS REQUIREMENTS OF SEC. R311.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 15- PROVIDE WINDOWS AND DOORS STRUCTURAL BUCK DETAILS.
 SPECIFY BUCK SIZE AND FASTENING. SEC. R609.7.1
 FBC-RESIDENTIAL.
  
 16-BATHROOM DOOR #19 ON FIRST FLOOR GUEST SUITE DOESN'T
 COMPLY WITH THE MIN 29" CLEAR OPENING REQUIRED BY SEC.
 R320 FBC-RESIDENTIAL.
  
 17- STRUCTURAL ENGINEER NEEDS TO HAVE A CURRENT
 ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION. SEC.
 61G15-23.002 AND CHAPTER 471 F.S. COORDINATE WITH DBPR.
  
 18- SHEET A-14: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE PRIVACY
 WALLS AND GATES. SEC. R301.1 FBC-RESIDENTIAL.
  
 19- CHIMNEY TERMINATION DOESN'T SEEM TO COMPLY WITH
 SEC. R1003.9 FBC-RESIDENTIAL. REVISE AS REQUIRED OR
 SHOW PROOF OF COMPLIANCE.
  
 20- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE FIREPLACE INCLUDING FLUE AND
 CHIMNEY. SEC. R301.1 FBC-RESIDENTIAL. AND SEC. R1001
 FBC-RESIDENTIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By jleahy Date 2019-02-20 Time 11:07 Rev Time 0.00
Received By jleahy Date 2019-02-20 Time 11:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-07 Cont ID  
Sent By jleahy Date 2018-12-07 Time 11:48 Rev Time 0.00
Received By jleahy Date 2018-12-07 Time 08:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2019-02-07 Cont ID  
Sent By jesmith Date 2019-02-07 Time 09:56 Rev Time 0.00
Received By jesmith Date 2019-02-07 Time 09:53 Sent To  
Notes
2019-02-07 09:55:08A SEPERATE PLAN AND GAS PERMIT IS REQUIRED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By jesmith Date 2019-01-03 Time 13:01 Rev Time 0.00
Received By jesmith Date 2019-01-03 Time 08:46 Sent To  
Notes
2019-01-03 13:01:53FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 GAS COMMENTS
 GAS PLAN NOT SUPPLIED. IS GAS SERVICE AVAILABLE THAT
 WILL SUPPORT THE REQUIREMENTS OF THE RESIDENCE? A
 SEPERATE PERMIT WILL BE REQUIRED FOR THE GAS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES
 G2413.4.1, G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB FBC 107.2.1.
 3. TYPE OF GAS (LP OR NATURAL). WPB FBC 107.2.1. IF
 NATURAL, SHOW METER LOCATION ON THE PLAN. IF LP PROVIDE
 THE FOLLOWING:
 A. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
 B. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED
 PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK
 SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT
 WIND LOAD PER THE FLORIDA BUILDING CODE.
 4.LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE FBC RES SEC. G2413.3,
 G2413.4 AND TABLES G2413.4 (1) THROUGH G2413.4(21).
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE FBC RES
 SEC. G 2413.4.1, G2413.4.2.
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER FBC RES SEC. G2413.2, G2413.4.3.
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC RES
 SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC RES SEC.G2408.1.
 8. SHOW THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB FBC
 107.2.1
 9. PROVIDE APPLICABLE SIZING TABLES USED TO SIZE THE
 GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE FBC RES SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 10. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS WHEN APPLICABLE. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. FBC RES SEC.
 G2421.1.
 11. I HAVE NOTED THREE (3) TANKLESS WATER HEATERS ON
 PLAN SHEET P.01; PLAN SHEET E.03 INDICATES A GAS RANGE,
 A BBQ GRILL (GAS?). ADDITIONALLY A FUTURE GENERATOR IS
 SHOWN ON PLAN SHEET A.02 AS WELL AS E.01 AND E.03.
 INDICATE ALL GAS FIRED APPLIANCES AND EQUIPMENT, PIPING
 DIAGRAMS, CALCULATIONS, ETC. IN AN ORDERLY WAY ON THE
 PLANS. WPB FBC 107.2.1.
 12. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC RES SEC. G 2420.4
 13. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
 14. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC
 RES SEC. G 2407.1 AND G2439.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By fmittner Date 2019-02-15 Time 08:30 Rev Time 0.00
Received By fmittner Date 2019-02-15 Time 08:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By fmittner Date 2018-12-20 Time 15:23 Rev Time 0.00
Received By fmittner Date 2018-12-20 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-03-01 Cont ID  
Sent By jgomez Date 2019-03-01 Time 18:17 Rev Time 0.00
Received By jgomez Date 2019-03-01 Time 15:42 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-02-27 Cont ID  
Sent By jgomez Date 2019-02-27 Time 16:39 Rev Time 0.00
Received By jgomez Date 2019-02-25 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-24 Cont ID  
Sent By cpuell Date 2019-02-24 Time 06:35 Rev Time 0.00
Received By cpuell Date 2019-02-22 Time 08:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-20 Cont ID  
Sent By jleahy Date 2019-02-20 Time 11:08 Rev Time 0.00
Received By jleahy Date 2019-02-04 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-03 Cont ID  
Sent By jesmith Date 2019-01-03 Time 13:03 Rev Time 0.00
Received By jesmith Date 2019-01-03 Time 13:02 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-02-24 Cont ID  
Sent By cpuell Date 2019-02-24 Time 06:36 Rev Time 0.00
Received By cpuell Date 2019-02-24 Time 06:36 Sent To  
Notes
2019-02-24 06:37:45IMPACT FEE OF $21.91 PAID, IMPACT FEE PUT THEIR STAMP
 ON THE PLANS, THEY HAD PREVIOUSLY REVIEWED THE PLANS IN
 PAPER.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-01-03 Cont ID  
Sent By shill Date 2019-01-03 Time 09:58 Rev Time 0.00
Received By shill Date 2019-01-03 Time 09:58 Sent To  
Notes
2019-01-03 09:58:52PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-12-21 Cont ID  
Sent By jgomez Date 2018-12-21 Time 12:03 Rev Time 0.00
Received By jgomez Date 2018-12-21 Time 12:02 Sent To  
Notes
2018-12-21 12:08:15MU-2018-038467. PROVIDE PLANS WITH COUNTY IMPACT FEES
 STAMP AND PROVIDE COPY OF PAID RECEIPT ( $21.91).

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By cmontell Date 2019-02-15 Time 13:48 Rev Time 0.00
Received By cmontell Date 2019-02-15 Time 13:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-12-19 Cont ID  
Sent By cmontell Date 2018-12-19 Time 09:58 Rev Time 0.00
Received By cmontell Date 2018-12-19 Time 09:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By jgomez Date 2019-02-15 Time 11:21 Rev Time 0.00
Received By jgomez Date 2019-02-07 Time 09:45 Sent To  
Notes
2019-02-15 11:22:23APPROVED BY JERRY SMITH ON 02/07/19. SEE APPROVED PLAN.
 MISSED THE OUT STOP. JG.
2019-02-07 09:49:37APPROVED
 PROVISO
 A GAS PERMIT IS REQUIRED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By jesmith Date 2019-01-03 Time 11:37 Rev Time 0.00
Received By jesmith Date 2019-01-03 Time 08:47 Sent To  
Notes
2019-01-03 11:37:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS
 1. KITCHEN: FLOOR PLAN SINK AT WINDOW HAS HORIZONTAL
 DRY VENT EXTENDING FROM THE FIXTURE DRAIN AND WOULD BE
 S-TRAPPED; SEE NOTES C AND D FOR VIOLATIONS. RISER
 DIAGRAM IS CORRECT AS LONG AS VET RISES 6" ABOVE THE
 FLOOD LEVEL RIM BEFORE OFFSETTING (A STUDOR VENT COULD
 ALSO BE USED). THE FLOOR PLAN AND THE RISER DIAGRAM
 NEED TO MATCH PER WPB FBC 107.2.1.
 2. GUEST BATH: LAVATORY AND SHOWER ARE S-TRAPPED AND
 ALSO HAVE HORIZONTAL DRY VENTS EXTENDING FROM THE
 FIXTURE DRAIN; SEE NOTES A, C AND D FOR VIOLATIONS.
 3. MASTER BATHROOM: SHOWER DRAIN HAS TO MUCH FALL; SEE
 NOTE B FOR VIOLATION.
 4. BATH #2: SHOWER IS S-TRAPPED AND HAS A HORIZONTAL
 DRY VENT EXTENDING FROM THE FIXTURE DRAIN; SEE NOTES C
 AND D FOR VIOLATIONS.
 5. LAUNDRY ROOM: SEE NOTES E AND F FOR VIOLATION.
  
 NOTES
 A. FBC RES P3105.2 FIXTURE DRAINS.
 THE TOTAL FALL IN A FIXTURE DRAIN RESULTING FROM PIPE
 SLOPE SHALL NOT EXCEED ONE PIPE DIAMETER, NOR SHALL THE
 VENT PIPE CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR
 WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP.
  
 B. FBC RES P3105.2 FIXTURE DRAINS.
 THE TOTAL FALL IN A FIXTURE DRAIN RESULTING FROM PIPE
 SLOPE SHALL NOT EXCEED ONE PIPE DIAMETER, NOR SHALL THE
 VENT PIPE CONNECTION TO A FIXTURE DRAIN, EXCEPT FOR
 WATER CLOSETS, BE BELOW THE WEIR OF THE TRAP. SHOWER
 DRAIN ROLLS UP TO CROSS OVER 3? BRANCH IS PROHIBITED
 UNLESS REVENTED AT THE HIGHER ELEVATION.
  
 C. FBC RES P3104.3 P3104.4 VENT CONNECTION TO DRAINAGE
 SYSTEM.
 A DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 P3104.4 VENTS SHALL RISE VERTICALLY TO A POINT 6? ABOVE
 THE FLOOD LEVEL RIM OF THE HIGHEST FIXTURE BEING SERVED
  
 D. FBC RES P3201.5 PROHIBITED TRAP DESIGNS.
 S-TRAPS ARE PROHIBITED; SEE ALL
  
 E. FBC RES P2601.1, FBC PL 406.2 THE FIXTURE DRAIN FOR
 THE STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL
 CONNECT TO A 3? OR LARGER FIXTURE BRANCH OR STACK.
  
 F. WPB FBC 107.2.1 LAUNDRY SINK SHOWN ON SECOND FLOOR
 PLAN VIEW SHALL BE SHOWN ON THE SANITARY RISER DIAGRAM
  
 DIGITAL PLANS HAVE BEEN REDLINED AND MAY BE REVIEWED
 FOR ADDITIONAL CLARIFICATION
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-02-27 Cont ID  
Sent By jgomez Date 2019-02-27 Time 09:01 Rev Time 0.00
Received By jgomez Date 2019-02-27 Time 09:01 Sent To  
Notes
2019-02-27 09:06:38BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE CURRENT POLYSTICK TU-PLUS PRODUCT APPROVAL.
 FL5259-R10 SUBMITTED IS TOO OLD. AND CLEARLY IDENTIFY
 WHICH ASSEMBLY IS GOING TO BE USED.
  
  
 APPROVED ROOFING PRODUCT APPROVALS:
  
 -METAL ROOF NOA 14-0520.08
 -TARCO UNDERLAYMENT NOA 16-1116.09.
 - CLAY TILE NOA 18-0604.04.
 - TILE ADHESIVE NOA 17-0322.03.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-02-20 Cont ID  
Sent By jgomez Date 2019-02-20 Time 11:30 Rev Time 0.00
Received By jgomez Date 2019-02-20 Time 11:26 Sent To  
Notes
2019-02-20 11:33:371- POLYSTICK TU-PLUS FLORIDA PRODUCT APPROVAL
 FL5259-R10 SUBMITTED IS TOO OLD. PROVIDE CURRENT
 FLORIDA PRODUCT APPROVAL OR MIAMI -DADE NOA. AND
 CLEARLY IDENTIFY WHICH ASSEMBLY IS GOING TO BE USED TO
 VERIFY DESIGN PRESSURES LIMITATIONS.
  
  
 APPROVED ROOFING PRODUCT APPROVALS:
  
 -METAL ROOF NOA 14-0520.08
 -TARCO UNDERLAYMENT NOA 16-1116.09.
 - CLAY TILE NOA 18-0604.04.
 - TILE ADHESIVE NOA 17-0322.03.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-12-28 Cont ID  
Sent By jgomez Date 2018-12-28 Time 15:39 Rev Time 0.00
Received By jgomez Date 2018-12-28 Time 15:38 Sent To  
Notes
2018-12-28 15:41:201-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) METAL ROOF AS SHOWN ON PLANS.
  
 B)ROOF UNDERLAYMENT NOA SUBMITTED: CLEARLY MARK WHICH
 UNDERLAYMENT IS GOING TO BE USED FOR THE CLAY TILE AND
 WHICH ONE IS GOING TO BE USED FOR THE METAL ROOF SHOWN
 AS SHOWN ON PLANS.
  
  
 SUBMITTED PRODUCT APPROVALS:
 A) CLAY TILE
 B) UNDERLAYMENT.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2019-03-02 Cont ID  
Sent By shill Date 2019-03-02 Time 14:39 Rev Time 0.00
Received By shill Date 2019-03-02 Time 14:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2019-03-01 Cont ID  
Sent By jgomez Date 2019-03-01 Time 18:17 Rev Time 0.00
Received By jgomez Date 2019-03-01 Time 17:59 Sent To  
Notes
2019-03-01 18:05:28SOIL TEST REPORT DOESN'T HAVE A DIGITAL SIGNATURE.
 PROVIDE HARD COPY OF SOIL TEST REPORT WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S.
  
  
  
  
2019-03-01 15:42:473/1/19 HARD COPIES ROUTED TO JGOMEZ

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2019-02-27 Cont ID  
Sent By jgomez Date 2019-02-27 Time 16:39 Rev Time 0.00
Received By jgomez Date 2019-02-27 Time 16:34 Sent To I
Notes
2019-02-27 16:39:16SOIL TEST REPORT DOESN'T HAVE A DIGITAL SIGNATURE.
 PROVIDE HARD COPY OF SOIL TEST REPORT WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-02-22 Cont ID  
Sent By jgomez Date 2019-02-22 Time 18:29 Rev Time 0.00
Received By jgomez Date 2019-02-22 Time 18:28 Sent To  
Notes
2019-02-22 18:32:101) DIGITAL SIGNATURE ON DRAWING S-1.0 IS INVALID. THERE
 IS AN ERROR ON THE SIGNATURE VERIFICATION. PLEASE
 REVISE.
  
 2) SOIL TEST REPORT DOESN'T HAVE A DIGITAL SIGNATURE.
 PROVIDE HARD COPY OF SOIL TEST REPORT WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 F.S.
  
 3) SURVEY DOESN'T HAVE A DIGITAL SIGNATURE. PROVIDE
 HARD COPY WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 472 F.S.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By jleahy Date 2019-02-20 Time 11:08 Rev Time 0.00
Received By jleahy Date 2019-02-20 Time 11:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-12-28 Cont ID  
Sent By jgomez Date 2018-12-28 Time 15:10 Rev Time 0.00
Received By jgomez Date 2018-12-28 Time 15:10 Sent To  
Notes
2018-12-28 15:12:591-DOCUMENTS SUBMITTED ARE NOT DIGITALLY SIGNED. AFTER
 ALL PLAN REVIEWS HAVE PASSED, SUBMIT ONE PAPER ORIGINAL
 AT THE BUILDING DIVISION. THIS INCLUDES THE FOLLOWING
 DOCUMENTS:
  
 A) ALL STRUCTURAL DRAWINGS
  
 B) SURVEY
  
 C) SOIL TEST REPORT.
  
 2- STRUCTURAL ENGINEER NEEDS TO HAVE A CURRENT
 ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION. SEC.
 61G15-23.002 AND CHAPTER 471 F.S.
 COORDINATE WITH DBPR.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-02-15 Cont ID  
Sent By fmittner Date 2019-02-15 Time 08:30 Rev Time 0.00
Received By fmittner Date 2019-02-15 Time 08:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By fmittner Date 2018-12-20 Time 15:23 Rev Time 0.00
Received By fmittner Date 2018-12-20 Time 15:23 Sent To  
Notes
2018-12-20 15:24:03REQUIRES A SEPARATE LANDSCAPE, DRIVEWAY AND FENCE
 PERMIT


Account Summary | Usage Policy | Privacy Policy