Plan Review Details - Permit 18111043
Plan Review Stops For Permit 18111043 |
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
P |
Date |
2019-02-14 |
|
|
Cont ID |
|
Sent By |
rrossano |
Date |
2019-02-14 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2019-02-14 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2019-01-07 |
|
|
Cont ID |
|
Sent By |
RRossano |
Date |
2019-01-07 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2019-01-07 |
Time |
|
Sent To |
I |
|
Notes |
2019-01-07 16:17:09 | PASSED WITH PROVISO: ENGINEERING IS WORKING WITH | | APPLICANT TO EVALUATE CITY'S POINT OF SERVICE FOR | | FIRELINE AND DOMESTIC SERVICE, INCLUDING LOCATION OF | | RPPA AND DCDA. BOTH BACKFLOW PREVENTION DEVICES MUST BE | | THE LEAD-FREE TYPE AND UNIVERSITY OF SOUTHERN | | CALIFORNIA APPROVED. BACKFLOWS ARE PRIVATE THEREFORE | | THEY MUST BE INSTALLED JUST INSIDE THE PROPERTY | | FOLLOWING THE CITY'S POINT OF SERVICE.THEY CAN BE | | INSTALLED HORIZONTALLY OR VERTICALLY. PLEASE SUBMIT | | SPEC SHEETS TO CITY OF WPB CUSTOMER SERVICE DEPT ON | | BACKFLOW PREVENTORS USED. YOU MAY REFERENCE CITY | | BACKFLOW STANDARD DETAIL WHERE DCDA IS SHOWN. | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | CONCERNS, THANKS. | | | | MANNY GONZALEZ | | SENIOR ENGINEERING PROJECT COORDINATOR | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2018-12-11 |
|
|
Cont ID |
|
Sent By |
RRossano |
Date |
2018-12-11 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2018-12-11 |
Time |
|
Sent To |
I |
|
Notes |
2018-12-11 14:32:25 | THIS APPLICATION REQUIRES AN ENGINEERING SUBMITTAL. | | PLEASE CONTACT: | | | | MANNY GONZALEZ | | SENIOR ENGINEERING PROJECT COORDINATOR | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | | | THANK YOU. | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2018-12-04 |
|
|
Cont ID |
|
Sent By |
RRossano |
Date |
2018-12-04 |
Time |
|
Rev Time |
0.00 |
Received By |
rrossano |
Date |
2018-12-04 |
Time |
|
Sent To |
I |
|
Notes |
2018-12-04 07:13:46 | THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS | | AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE | | DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER | | UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT | | PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW: | | HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W | | EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P | | ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19 | | 60045731D3658206F27451722716EF | | | | THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | FOUND HERE: | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | MS,-PERMITS-APPLICATIONS | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | CONCERNS, THANKS. | | | | RICK ROSSANO | | PROJECT COORDINATOR | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1098 | | FAX: (561) 494-1116 | | MOBILE: (561) 246-9525 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | | | MANNY GONZALEZ | | SENIOR ENGINEERING PROJECT COORDINATOR | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-12-10 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-12-10 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-12-10 |
Time |
11:10 |
Sent To |
ENG |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-12-03 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-12-03 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-12-03 |
Time |
10:45 |
Sent To |
ENG |
|
Notes |
2018-12-03 10:51:25 | SENT TO ENGINEERING DUE TO UNDERGROUND VAULT AND NEW | | BACKFLOW. | | | | PML | 2018-12-03 10:50:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) SHEET FP O - THERE IS AN INDICATION UNDER PROJECT # | | AS VALUE STORE IN HOLLYWOOD FL. | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | 2) THERE ARE NO MANUFACTURESE SPECIFICATION SHEETS FOR | | THE PROPOSED BACKFLOW. | | | | PLEASE PROVIDE THE APPLICABLE SPEC SHEETS TO ENSURE | | THEY MEET THE CITY ENGINEERING SPECIFICATIONS. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-12-12 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-12-12 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-12-06 |
Time |
14:37 |
Sent To |
|
|
Notes |
2018-12-07 14:37:23 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-12-04 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-12-04 |
Time |
13:51 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-11-26 |
Time |
16:22 |
Sent To |
|
|
Notes |
2018-11-27 16:22:41 | ROUTED TO FIRE INBOX |
|
|
|