Plan Review Details - Permit 18110946
Plan Review Stops For Permit 18110946
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-12-26 Cont ID  
Sent By tklarge Date 2018-12-26 Time 09:00 Rev Time 0.00
Received By tklarge Date 2018-12-26 Time 07:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By tklarge Date 2018-12-11 Time 06:30 Rev Time 0.00
Received By tklarge Date 2018-12-10 Time 06:05 Sent To I
Notes
2018-12-10 08:52:461) INDICATE ON BOTH SETS OF PLANS IF THE TANK WILL BE
 FILLED WITH LP GAS AT THE TIME OF INSTALLATION OR WILL
 REMAIN EMPTY. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE DISTANCE FROM THE END OF THE TANK TO THE
 EDGE OF THE DRIVEWAY. CONTAINERS LOCATED WITHIN 10 FEET
 OF A DESIGNATED PARKING LOCATION SHALL CCOMPLY WITH
 NFPA 58 SEC.6.6.6.1 (B), (C), (E).
 3) A CORROSION PROTECTION SYSTEM SHALL BE INSTALLED ON
 NEW INSTALLATIONS OF UNDERGROUND STEEL CONTAINERS PER
 NFPA 58 SEC. 6.6.6.1 (I). SUBMIT INFORMATION & DETAILS
 AS TO HOW THE REQUIRED CATHODIC PROTECTION WILL BE
 PROVIDED.THE CORROSION PROTECTION SHALL INCCLUDE THE
 FOLLOWING:
 1) A CONTAINER COATING COMPLYING WITH NFPA 58
 SEC.5.2.1.11.
 2) A CATHODIC PROTECTION SYSTEM THAT CONSISTS OF A
 SACRIFICIAL ANODE(S) OR AN IMPRESSED CURRENT ANODE.
 3) A MEANS TO TEST THE PERFORMANCE OF THE CATHODIC
 PROTECTION SYSTEM IN ACCORDANCE WITH NFPA 58 SEC.
 6.17.3.
 SHOW THE NUMBER/TYPE OF ANODE, WWIRE SIZE ETC.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-26 Cont ID  
Sent By tklarge Date 2018-12-26 Time 09:00 Rev Time 0.00
Received By tklarge Date 2018-12-13 Time 13:18 Sent To  
Notes
2018-12-14 13:18:53RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By tklarge Date 2018-12-11 Time 06:30 Rev Time 0.00
Received By tklarge Date 2018-11-21 Time 14:49 Sent To P
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved