2018-12-07 16:38:01 | 1) CLARIFY THE REASON FOR THE CFH NUMBERS AT THE GAS |
| OUTLETS AND ALSO AT THE PE PIPE. |
| 2) SHOW THE SIZE OF THE GALVANIZED PIPE AT THE OUTLET |
| OF THE GAS METER. |
| 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS |
| APPLIANCES. THE APPLIANCES SHALL BE LISTED AND LABELED |
| PER 2017 FBC-FUEL GAS SEC. 301.3. |
| 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| 5) THE DESCRIPTION OF WORK ON THE APPLICATION NOTES |
| THAT THE GAS LINE WILL BE RUNNING UNDER THE HOUSE. IS |
| THE INTENT TO INSTALL THE PIPING UNDER A SLAB OR IN A |
| CRAWL SPACE? PE PIPING IS ONLY PERMITTED TO BE |
| INSTALLLED OUTDOORS UNDERGROUND ONLY. INSTALLING IT |
| ABOVEGROUND IN A CRAWL SPACE IS A VIOLATION OF THE CODE |
| AND NOT PERMITTED. SECONDLY, GAS PIPING UNDER A |
| BUILDING IS ONLY PERMITTED WHEN THERE IS NO OTHER WAY |
| TO INSTALL IT. THE INSTALLATION SCOPE OF THIS PORTION |
| OF THE WORK IS VAGUE AND VIOLATES THE GAS CODE SEC. |
| 404.14. CLARIFY. |
| 6) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE |
| DRYER AND STOVE AND SUPPLY COMBUSTION AIR CALCULATIONS |
| PER 2017 FBC-FUEL GAS SEC.304.1. |
| |