Plan Review Stops For Permit 18110877 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-03-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-03-19 |
Time |
17:15 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-03-19 |
Time |
16:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-02-06 |
|
|
Cont ID |
|
Sent By |
jduprey |
Date |
2019-02-06 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
jduprey |
Date |
2019-02-06 |
Time |
16:24 |
Sent To |
|
|
Notes |
2019-02-06 16:31:49 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | JOSEAN A. DUPREY E.I., BN, PX | | BUILDING PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6716 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. THE BUCK DETAIL WAS SUBMITTED, HOWEVER THE SIGNATURE | | IS A COPY. PLEASE SUBMITT A COPY WITH THE ORIGINAL | | SIGNATURE. ALSO THIS DETAIL MUST INCLUDE THE WIND | | DESIGN CRITERIA CONSIDERED BY THE ENGINEER. | | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND | | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL | | SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN. | | CODE RULE 61G15-23.001. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-12-21 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-12-21 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-12-21 |
Time |
10:06 |
Sent To |
|
|
Notes |
2018-12-21 16:34:23 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18110877 | | REVIEWED: DECEMBER 21, 2018 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER I | | [email protected] | | 561-805-6718 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC ENERGY = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. [FBC EXISTING 504.1]STATE THE LEVEL OF ALTERATION | | FOR WORK BEING PERFORMED. THIS LOOKS A LEVEL 2 | | ALTERATION SINCE WALLS ARE BEING REMOVED. | | | | 2. [FBC AMENDED 107.3.5] | | PROVIDE DESIGN DATA FOR OPENINGS | | WIND SPEED V ULT = (170) | | WIND SPEED V ASD = (132) | | EXPOSURE CATEGORY = B | | BUILDING CLASSIFICATION = ENCLOSED | | MEAN BLDG. HGT. = ? | | PLEASE PROVIDE AN OPENING SCHEDULE TO SHOW THE SIZES | | AND DESIGN PRESSURES. | | PRESSURES CAN BE USED FROM R301.2(2) WALL ZONE 4 OR 5 | | AS APPROPRIATE. | | | | 3. [FBC AMENDED 107.3.5]PROVIDE IN-FILL DETAIL WHERE | | CMU WALL IS BEING CLOSED UP. INCLUDE EXTERIOR FINISH, | | DOWELS AND INTERIOR INSULATION/FINISH. | | | | NOTE: | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | OF MATERIALS REQUESTED. | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | NEED "VOID", RENDERING THEM NOT USABLE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-02-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-07 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-07 |
Time |
14:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-12-12 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-12-12 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-12-12 |
Time |
07:57 |
Sent To |
|
|
Notes |
2018-12-12 13:56:00 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED | | TO BE SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN. | | PROVIDE CORRECTION. FS 481.229; WPB FBC 107.1, 107.2.1, | | 107.3.5.1.2 | | 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, | | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN | | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, | | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND | | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS | | INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. | | SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. IF | | EXISTING OUTLETS AND SWITCHES ARE REPLACED, AFCI AND | | GFCI TO CODE IS REQUIRED. PROVIDE CORRECTION. NEC | | 210.8, 210.12, 406.4; FBC RE E3902; FBC EX 607.1.1 OR | | 801.1, 801.2, OR 901.2 AS APPLICABLE. | | 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | 210.8(D); FBC RE E3902.10 | | 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | 5. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING | | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS | | NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC | | 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
3 |
Status |
P |
Date |
2019-03-14 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2019-03-14 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2019-03-14 |
Time |
14:03 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2019-02-11 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2019-02-11 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2019-02-11 |
Time |
14:52 |
Sent To |
PC |
|
Notes |
2019-02-11 14:53:12 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITIONS: | | | | 1. ALL WINDOWS MUST FEATURE OGEE DIMENSIONAL MUNTINS. | | A. ALL SINGLE-HUNG WINDOWS WILL FEATURE A 6 OVER 1 | | LAYOUT. | | B. ALL FIXED WINDOWS MUST COPY THE ORIGINAL MUNTIN | | LAYOUT FOUND IN THE ORIGINAL WINDOW. | | 2. ALL REPLACEMENTS WINDOWS MUST FIT THE ORIGINAL | | WINDOW FRAME SIZE. | | 3. ALL WINDOWS SHALL BE CLEAR GLASS OR LOW E. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE EMAIL AARON | | BORNGRABER AT [email protected] OR CALL 561-822-1428. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | | CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES | | T: 561-822-1428 | | [email protected] | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2018-12-11 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2018-12-11 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2018-12-11 |
Time |
11:00 |
Sent To |
|
|
Notes |
2018-12-11 11:00:39 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITIONS: | | | | 1. ALL WINDOWS MUST FEATURE OGEE DIMENSIONAL MUNTINS. | | A. ALL SINGLE-HUNG WINDOWS WILL FEATURE A 6 OVER 1 | | LAYOUT. | | B. ALL FIXED WINDOWS MUST COPY THE ORIGINAL MUNTIN | | LAYOUT FOUND IN THE ORIGINAL WINDOW. | | 2. ALL REPLACEMENTS WINDOWS MUST FIT THE ORIGINAL | | WINDOW FRAME SIZE. | | 3. A SEPARATE DRIVEWAY AND FENCE PERMIT IS REQUIRED FOR | | THE PROPOSED DRIVEWAY AND FENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE EMAIL AARON | | BORNGRABER AT [email protected] OR CALL 561-822-1428. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | | CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES | | T: 561-822-1428 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-03-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-03-19 |
Time |
17:22 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-03-12 |
Time |
13:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-02-12 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2019-02-12 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2019-01-31 |
Time |
13:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-12-27 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-12-27 |
Time |
17:08 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-11-20 |
Time |
16:08 |
Sent To |
|
|
Notes |
2018-11-28 12:50:27 | R33 | 2018-11-20 16:08:58 | LIBRARY |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2019-03-19 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-03-19 |
Time |
17:15 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-03-19 |
Time |
16:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2019-02-14 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-14 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-14 |
Time |
11:36 |
Sent To |
|
|
Notes |
2019-02-14 11:37:55 | MECHANICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 3RD REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. SPCIFICATIONS FOR 2-TON UNIT WERE LOCATED IN PLAN. | | | | 2. PROVIDE RETURN AIR FOR UPSTAIRS BEDROOMS. | | M1602.3 BALANCED RETURN AIR. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2019-02-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-07 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-07 |
Time |
14:22 |
Sent To |
|
|
Notes |
2019-02-07 16:00:59 | MECHANICAL PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE SPECIFICATIONS FOR 2 TON COND. UNIT. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. PROVIDE RETURN AIR FOR UPSTAIRS BEDROOMS. | | M1602.3 BALANCED RETURN AIR. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-12-19 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2018-12-19 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2018-12-19 |
Time |
09:38 |
Sent To |
|
|
Notes |
2018-12-19 09:40:55 | MECHANICAL PLAN REVIEW FAIL | | | | 1 - NEED LEGIBLE PLAN PER 2017 FLORIDA BUILDING CODE - | | BUILDING, SIXTH EDITION SEC. [A]107.2.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. | | | | CHRIS MONTELLO | | 561-805-6733 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-02-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2019-02-07 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2019-02-07 |
Time |
14:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-12-27 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-12-27 |
Time |
16:31 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-12-26 |
Time |
12:27 |
Sent To |
|
|
Notes |
2018-12-27 17:08:46 | PLUMBING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | BUILDING PLANS EXAMINER, PX3169 | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND | | THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON | | RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE. | | | | PROVIDE CLARIFICATION FOR THE FOLLOWING: | | | | 1. CLARIFY THE SCOPE OF WORK IN M-BATH. A. VANITY. B. | | WC. C. SHOWER. | | | | 2. ARCH. FLOOR PLAN STATES EXISTING BUT SHOWS TANKLESS | | WATER HEATER LOCATED AT EXTERIOR WALL OF M-BATH. NOTE | | STATES WH WILL BE LOCATED BACK TO BACK OF OLD WH THAT | | WAS LOCATED IN KITCHEN. PLEASE CLARIFY. | | | | 3. SHOW WATER CLOSETS ON PLAN. | | | | 4. WHAT SIZE SANITARY SERVICES THE WC ON ISOMETRIC | | DRAWING? | | | | 5. PROVIDE DEMENSIONS IN BATHROOMS TO VERIFY REQUIRED | | CLEARANCES. | | | | 6. ARE BOTH SYSTEMS TIED TO BLDG. DRAIN OR BLDG. SEWER? | | IF SEPERATE SYSTEMS ARE TIED TO BLDG. SEWER THEN A | | SECOND VTR WILL BE REQUIRED. | | | | 7. NOTE ON ELECTRICAL PLAN STATES RE-LOCATE WASHER AND | | DRYER. WHERE WILL THEY BE LOCATED? | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2019-03-14 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2019-03-14 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2019-03-14 |
Time |
14:03 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2019-02-11 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2019-02-11 |
Time |
14:54 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2019-02-11 |
Time |
14:53 |
Sent To |
PC |
|
Notes |
2019-02-11 14:54:05 | THE PERMIT HAS BEEN APPROVED WITH THE FOLLOWING | | CONDITIONS: | | | | 1. A SEPARATE DRIVEWAY PERMIT SHALL BE REQUIRED. A HOLD | | SHALL BE PLACED ON THE PERMIT, WHICH SHALL PREVENT THE | | CLOSEOUT OF THE PERMIT IF A DRIVEWAY PERMIT IS NOT | | SUBMITTED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE EMAIL AARON | | BORNGRABER AT [email protected] OR CALL 561-822-1428. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | | CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES | | T: 561-822-1428 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-12-11 |
|
|
Cont ID |
|
Sent By |
aborngra |
Date |
2018-12-11 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
aborngra |
Date |
2018-12-11 |
Time |
11:03 |
Sent To |
|
|
Notes |
2018-12-11 11:04:15 | THE PERMIT HAS FAILED ZONING REVIEW FOR THE FOLLOWING | | REASIONS: | | | | 1. A SEPARATE DRIVEWAY AND FENCE PERMIT IS REQUIRED FOR | | THE PROPOSED DRIVEWAY AND FENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE EMAIL AARON | | BORNGRABER AT [email protected] OR CALL 561-822-1428. | | | | AARON BORNGRABER | | HISTORIC PRESERVATION PLANNER | | CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES | | T: 561-822-1428 | | [email protected] |
|
|