Notes |
2018-11-28 07:15:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. INCORRECT CONDUIT AND WIRE SIZE FOR PRIMARY AND | | SECONDARY CONDUCTORS FOR TRANSFORMER. PROVIDE | | CORRECTION. 110.14C1A2, 215.3A, 240.21C | | | | 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | LOADS. NEC 220; | | | | 3. CITY PLACE APPROVAL STAMP NEEDED ON PLANS. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-01-17 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
|
Time |
07:04 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2019-01-11 |
Time |
14:48 |
Sent To |
|
|
Notes |
2019-01-14 14:48:20 | RESUB ROUTED TO FGIAQUINTO |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-11-28 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-11-28 |
Time |
07:25 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-11-19 |
Time |
16:32 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2019-03-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2019-03-18 |
Time |
13:07 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2019-03-18 |
Time |
13:07 |
Sent To |
|
|
Notes |
2019-03-18 13:08:14 | MONUMENT SIGNS REQUIRE SEPARAE PERMITS WITH PLANS. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |