Plan Review Details - Permit 18110726
Plan Review Stops For Permit 18110726
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-11-19 Cont ID  
Sent By pleduc Date 2018-11-19 Time   Rev Time 0.00
Received By pleduc Date 2018-11-19 Time 14:24 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-01-11 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-07 Time 13:33 Sent To  
Notes
2019-01-08 13:33:29RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-01-02 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-26 Time 12:38 Sent To  
Notes
2018-12-27 12:38:49RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-12-11 Time   Rev Time 0.00
Received By lmarchan Date 2018-11-15 Time 09:26 Sent To  
Notes
2018-11-16 09:26:13ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-01-11 Cont ID  
Sent By ccole Date 2019-01-11 Time 15:40 Rev Time 0.00
Received By ccole Date 2019-01-11 Time 15:40 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-01-02 Cont ID  
Sent By ccole Date 2019-01-02 Time 10:53 Rev Time 0.00
Received By ccole Date 2019-01-02 Time 10:53 Sent To I
Notes
2019-01-02 11:00:322ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18110726
 12/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #2 FROM THE FIRST REVIEW (PRINTED BELOW) STILL
 EXISTS. THE ENGINEER'S LETTER ADDRESSING THE COMMENT
 DOES NOT PROVIDE ANY EVIDENCE THAT THE HVAC SYSTEM IN
 THE KITCHEN HAS BEEN SIZED TO CONDITION THE ADDED
 COOLING LOAD IMPOSED BY THE MAKEUP AIR. PLEASE PROVDE
 CALCULATIONS TO VERIFY COMPLIANCE.
  
 2) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M MAKEUP
 AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By ccole Date 2018-12-11 Time 08:29 Rev Time 0.00
Received By ccole Date 2018-12-10 Time 17:15 Sent To I
Notes
2018-12-11 08:40:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110726
 12/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MAIN PERMIT PLANS FOR THE MEDICAL REHAB
 RENOVATION SHOWS THE GREASE DUCT TO BE ENCLOSED IN A
 2HR RATED FIRE WRAPPING. THE SUBMITTED HOOD PLANS SHOW
 A 3" CLEARANCE REDUCTION METHOD PER NFPA 96 WHERE THE
 DUCT PENETRATES THE COMBUSTIBLE ROOF ASSEMBLY. THE
 ENGINEER OF RECORD FOR THE MEDICAL WAY REHAB ERIC
 SVOBODA PE. MUSTL PROVIDE A SHOP DRAWING APPROVAL ON
 THE PLANS- SECTION 107.2.1 WPB.
  
 2) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M MAKEUP
 AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  