2018-12-11 08:40:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18110726 |
| 12/11/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE MAIN PERMIT PLANS FOR THE MEDICAL REHAB |
| RENOVATION SHOWS THE GREASE DUCT TO BE ENCLOSED IN A |
| 2HR RATED FIRE WRAPPING. THE SUBMITTED HOOD PLANS SHOW |
| A 3" CLEARANCE REDUCTION METHOD PER NFPA 96 WHERE THE |
| DUCT PENETRATES THE COMBUSTIBLE ROOF ASSEMBLY. THE |
| ENGINEER OF RECORD FOR THE MEDICAL WAY REHAB ERIC |
| SVOBODA PE. MUSTL PROVIDE A SHOP DRAWING APPROVAL ON |
| THE PLANS- SECTION 107.2.1 WPB. |
| |
| 2) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M MAKEUP |
| AIR TEMPERATURE. |
| |
| THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F |
| (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS |
| OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE |
| HVAC SYSTEM. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |