Plan Review Stops For Permit 18110627 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2019-01-24 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2019-01-24 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2019-01-24 |
Time |
12:53 |
Sent To |
|
|
Notes |
2019-01-24 13:04:47 | PROVISO: | | PROVIDE PRODUCT APPROVALS FOR DOORS 101,102 AND 104 IN | | A SUBMITTAL, OR PROVIDE TO INSPECTOR IF THE INSPECTOR | | WILL ACCEPT THGEM IN THE FIELD. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-12-31 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-12-31 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-12-28 |
Time |
15:41 |
Sent To |
|
|
Notes |
2018-12-31 09:07:43 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18110627 | | REVIEWED: DECEMBER 28, 2018 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER I | | [email protected] | | 561-805-6718 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC ENERGY = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO | | MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE. | | CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION. | | THE ENERGY CALCULATIONS IN SUPPORTING DOCUMENTS IS LOAD | | CALCS ONLY. PLEASE PROVIDE ADDITIONAL CALCULATIOND TO | | INCLUDE DATA USED TO DETERMINE HVAC LOAD CALCULATIONS. | | | | 2. [FBC AMENDED 107.2.1.2]PROVIDE STAIRCASE AND GUARD | | RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. | | | | 3. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR | | DOOR 101 103 AND 104, OR INDICATE THAT YOU WOULD LIKE | | IT DEFERED. | | | | NOTE: | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | OF MATERIALS REQUESTED. | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | NEED "VOID", RENDERING THEM NOT USABLE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-01-28 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-01-28 |
Time |
16:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-12-06 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-12-06 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-12-06 |
Time |
16:41 |
Sent To |
|
|
Notes |
2018-12-06 16:41:19 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | OUTLETS NEEDED AT THE FRONT AND REAR OF STRUCTURE. | | E3901.7 OUTDOOR OUTLETS. | | NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY | | ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6 | | FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE | | INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH | | DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL. | | BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM | | INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE | | RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE | | BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE | | LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE | | THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)] | | | | STRUCTURE SHALL HAVE A GROUNDING SYSTEM INSTALLED PER | | E3607.3 | | E3607.3 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) | | OR BRANCH CIRCUIT(S). | | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH | | CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR | | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH | | SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S) | | SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION | | E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS | | ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING | | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) | | REQUIRED IN SECTION E3608 SHALL BE INSTALLED. | | [250.32(A)] | | | | MAINS NEED TO BE GROUPED | | E3601.6 SERVICE DISCONNECT REQUIRED. | | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN | | A BUILDING OR OTHER STRUCTURE FROM THE SERVICE ENTRANCE | | CONDUCTORS. (230.70) | | | | SMOKE ALARMS | | R314.2.2 ALTERATIONS, REPAIRS AND ADDITIONS. | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | EXCEPTIONS: | | 1.WORK INVOLVING THE EXTERIOR SURFACES OF DWELLINGS, | | SUCH AS THE REPLACEMENT OF ROOFING OR SIDING, THE | | ADDITION OR REPLACEMENT OF WINDOWS OR DOORS, OR THE | | ADDITION OF A PORCH OR DECK, ARE EXEMPT FROM THE | | REQUIREMENTS OF THIS SECTION. | | 2.INSTALLATION, ALTERATION OR REPAIRS OF PLUMBING OR | | MECHANICAL SYSTEMS ARE EXEMPT FROM THE REQUIREMENTS OF | | THIS SECTION |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2018-12-18 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2018-12-18 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2018-12-18 |
Time |
08:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-01-28 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-01-18 |
Time |
15:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2019-01-10 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-10 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-12-03 |
Time |
08:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2019-02-01 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2019-02-01 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-01-29 |
Time |
10:52 |
Sent To |
|
|
Notes |
2019-02-01 14:00:30 | RECEIPT MU-2019-3226 - $0.00 DUE | | | 2019-01-29 10:52:18 | 1/29/19 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2018-12-31 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-12-31 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-12-31 |
Time |
09:15 |
Sent To |
|
|
Notes |
2018-12-31 09:17:14 | [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER I | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2019-01-02 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2019-01-02 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2019-01-02 |
Time |
13:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-01-26 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-26 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-26 |
Time |
10:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2019-01-10 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-10 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-10 |
Time |
09:39 |
Sent To |
|
|
Notes |
2019-01-10 10:25:58 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. THE ADDRESS ON THE PLAN SHEETS IS 221 EDGEWOOD DR | | THIS IS INCORRECT THAT ADDRESS DOES NOT EXIST THE | | PERMIT APPLICATION STATES THE ADDRESS AS 215 PLEASE | | CORRECT ON PLAN SHEETS. PER FBC AMEND TO FBC 107.2.1 | | 2. I COULD NOT LOCATE THE MASTER BUILDING PERMIT | | APPLICATION IT APPEARS THAT IT DID NOT GET UPLOADED | | PLEASE CLARIFY. PER FBC AMEND TO FBC 107.2.1 | | 3. A CLEAN OUT IS REQUIRED ANY BRANCH OF THE BUILDING | | DRAIN EXISTS THE BUILDING AND CONNECTS TO THE BUILDING | | SEWER PLEASE SHOW ON ISOMETRIC DRAWING. PER FBC RES | | P3005.2.3 | | 4. PLEASE PLACE NOTE ON THE PLANS. [THE SHUT OF VALVES | | FOR THE STACKABLE WASHING MACHINE SHALL BE ACCESSIBLE | | PER FBC RES P2903.9.3] [THE WATER HEATER AND PIPING | | SHALL COMPLY WITH THE FBC ENERGY R403.5] | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2019-01-28 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2019-01-28 |
Time |
16:19 |
Sent To |
|
|
Notes |
2019-01-26 10:23:46 | 1/26/19 DIG SIG ON PLUMB OK/GPJ |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2018-12-31 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-12-31 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-12-31 |
Time |
09:07 |
Sent To |
|
|
Notes |
2018-12-31 09:09:05 | INITIAL REVIEW - ALL SHEETS OK | | ANY NEW SHEETS SUBMITTED WILL NEED TO BE DIGITALLY | | SIGNED. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-12-18 |
|
|
Cont ID |
|
Sent By |
mcurz |
Date |
2018-12-18 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2018-12-18 |
Time |
08:40 |
Sent To |
|
|
Notes |
|
|