Plan Review Details - Permit 18110620
Plan Review Stops For Permit 18110620
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 16:15 Rev Time 0.00
Received By shill Date 2018-12-08 Time 16:15 Sent To  
Notes
2018-12-08 16:15:46***PASSED W/REDLINES****
 ***PROVISO***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OCCUPANCY CLASSIFICATION IS R2, NOT R3, SEE FBC
 CHAPTER 3.
  
 2. GOVERNING CODE IS FBC 2017 **BUILDING**, NOT
 RESIDENTIAL. THIS BUILDING IS A HIGH RISE. REMOVED
 REFERENCE TO RESIDENTIAL FBC 301.
  
 3. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD ARE
 TO BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION, FBC B
 1609.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-05 Cont ID  
Sent By jpearson Date 2018-12-05 Time 09:47 Rev Time 0.00
Received By jpearson Date 2018-12-05 Time 09:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-11-20 Cont ID  
Sent By scaldero Date 2018-11-20 Time 11:01 Rev Time 0.00
Received By scaldero Date 2018-11-20 Time 11:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-13 Cont ID  
Sent By jesmith Date 2018-12-13 Time 14:41 Rev Time 0.00
Received By jesmith Date 2018-12-13 Time 14:41 Sent To  
Notes
2018-12-08 16:16:5512/8 REMOVED FROM BOARD, ROUTED TO JES DESK / S.HILL
  
  
2018-11-15 15:33:41B21
 **TRAVELLING TOGETHER - 18110616 & 18110620**

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-13 Cont ID  
Sent By jesmith Date 2018-12-13 Time 14:41 Rev Time 0.00
Received By jesmith Date 2018-12-13 Time 14:39 Sent To  
Notes
2018-12-13 14:41:25APPROVED
 PLUMBING PROVISO
  
 1. CHANGING BATHTUB TO A SHOWER REQUIRES CHANGE OF
 PIPING BELOW FLOOR. PROVIDE FIRE RATING OF ELEVATED
 FLOOR AND PROVIDE ASSEMBLY FOR DEALING WITH THE FLOOR
 PENETRATION COMPLYING WITH FBC 714.4 THROUGH 714.4.1.2.
 PROVIDE AS A DEFERRED SUBMITTAL AS ALLOWED BY WPB FBC
 107.3.4.1.
 A) SUBMITTALS TO BE SUBMITTED, APPROVED AND IN PLACE
 PRIOR TO ROUGH INSTALLATION AND INSPECTION
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715