Plan Review Details - Permit 18110542
Plan Review Stops For Permit 18110542
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 16:19 Rev Time 0.00
Received By cthroop Date 2018-12-20 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By cthroop Date 2018-12-10 Time 14:13 Rev Time 0.00
Received By cthroop Date 2018-12-10 Time 13:54 Sent To FIRE
Notes
2018-12-10 14:16:28BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE SAMPLE OF AWNING FABRIC WITH E-84 FLAME
 SPREAD TEST RESULTS.
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By pleduc Date 2018-12-20 Time   Rev Time 0.00
Received By pleduc Date 2018-12-20 Time 11:15 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By pleduc Date 2018-12-11 Time   Rev Time 0.00
Received By pleduc Date 2018-12-11 Time 11:22 Sent To I
Notes
2018-12-11 11:33:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO OCCUPANCY TYPE INDICATED FOR THE REAR
 BUILDIING INDICATED ON THE SITE PALN.
  
 PLEASE PROVIDE THE OCCUPANCY TYPE PER THE FLORIDA FIRE
 PROTECTION CODE.
  
  
  
 2) THERE ARE FIVE WINDOWS ON THE FRONT OF THE REAR
 BUILDING. HOW MANY FRAME CANOPIES ARE PROPOSED.
  
 PLEASE PROVIDE A HORIZONTAL VIEW SHOWING THE LOCATION
 OF THE PROPOSED.
  
  
  
 3) THERE ARE NO INDICATION OF THE TYPE OF FRABIC OR ANY
 FLAME SPREAD RATING PER THE FFPC.
  
 25.5.1.5 FLAME PROPAGATION PERFORMANCE.
 25.5.1.5.1 ALL MEMBRANE STRUCTURE FABRIC SHALL MEET THE
 FLAME
 PROPAGATION PERFORMANCE CRITERIA CONTAINED IN TEST
 METHOD 2 OF
 NFPA 701, STANDARD METHODS OF FIRE TESTS FOR FLAME
 PROPAGATION OF TEXTILES AND FILMS. [101: 11.9.1.6.1]
 25.5.1.5.2 ONE OF THE FOLLOWING SHALL SERVE AS EVIDENCE
 THAT THE
 FABRIC MATERIALS HAVE THE REQUIRED FLAME PROPAGATION
 PERFORMANCE:
 (1) THE AHJ SHALL REQUIRE A CERTIFICATE OR OTHER
 EVIDENCE OF
 ACCEPTANCE BY AN ORGANIZATION ACCEPTABLE TO THE AHJ.
 (2) THE AHJ SHALL REQUIRE A REPORT OF TESTS MADE BY
 OTHER
 INSPECTION AUTHORITIES OR ORGANIZATIONS ACCEPTABLE TO
 THE
 AHJ. [101: 11.9.1.6.2]
 25.5.1.5.3 WHERE REQUIRED BY THE AHJ, CONFIRMATORY
 FIELD TESTS
 SHALL BE CONDUCTED USING TEST SPECIMENS FROM THE
 ORIGINAL
 MATERIAL, WHICH SHALL HAVE BEEN AFFIXED AT THE TIME OF
 MANUFACTURE
 TO THE EXTERIOR OF THE STRUCTURE. [101: 11.9.1.6.3]
  
 PLEASE PROVIDE THE APPLICABLE CERTIFICATION DOCUMENTS
 AND/OR ACTUAL MATERIAL SAMPLE FOR TESTING.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-12-19 Cont ID  
Sent By aborngra Date 2018-12-19 Time 09:52 Rev Time 0.00
Received By aborngra Date 2018-12-19 Time 09:52 Sent To FIRE
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-12-05 Cont ID  
Sent By aborngra Date 2018-12-05 Time 09:32 Rev Time 0.00
Received By aborngra Date 2018-12-05 Time 09:43 Sent To PC
Notes
2018-12-05 09:40:51PLEASE PROVIDE THE FOLLOWING ON YOUR RESUBMITTAL:
 1. MATERIAL OF THE AWNINGS
 2. SPECIFY ON ELEVATIONS WHICH WINDOWS WILL HAVE AN
 AWNING AND THE SIZE OF THE AWNING. A PHOTOGRAPH OR A
 SKETCH WILL SATISFY THIS REQUIREMENT.
  
  
 FOR A FASTER RESPONSE, PLEASE EMAIL AARON BORNGRABER,
 HISTORIC PRESERVATION PLANNER AT [email protected].
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH - DEVELOPMENT SERVICES
 T: 561-822-1428
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 16:19 Rev Time 0.00
Received By cthroop Date 2018-12-17 Time 14:34 Sent To  
Notes
2018-12-18 14:34:47RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By cpuell Date 2018-12-11 Time 14:12 Rev Time 0.00
Received By cpuell Date 2018-11-14 Time 14:00 Sent To  
Notes
2018-11-15 14:00:23ROUTED TO HISTORIC INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-05 Cont ID  
Sent By aborngra Date 2018-12-05 Time 09:43 Rev Time 0.00
Received By aborngra Date 2018-12-05 Time 09:43 Sent To B
Notes
***NONE***