Plan Review Details - Permit 18110236
Plan Review Stops For Permit 18110236
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-01-08 Cont ID  
Sent By jduprey Date 2019-01-08 Time 11:59 Rev Time 0.00
Received By jduprey Date 2019-01-08 Time 11:57 Sent To  
Notes
2019-01-08 11:59:46BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DRAWINGS SUBIMTTED MUST BE SIGN BY THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5) AND F.S. 481.229.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-21 Cont ID  
Sent By pvalenti Date 2018-11-21 Time 16:15 Rev Time 0.00
Received By pvalenti Date 2018-11-21 Time 16:15 Sent To E
Notes
2018-11-21 16:18:46****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION INCLUDING THE
 FASTENING/ANCHORING DETAILS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-01-08 Cont ID  
Sent By jleahy Date 2019-01-08 Time 15:46 Rev Time 0.00
Received By jleahy Date 2019-01-08 Time 15:46 Sent To  
Notes
2019-01-08 15:47:20NEED TO SHOW ELECTRIC CIRCUITS AND DISCONNECT
 600.6(A)(1)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By jleahy Date 2018-11-27 Time 15:58 Rev Time 0.00
Received By jleahy Date 2018-11-27 Time 15:58 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-08 Cont ID  
Sent By jleahy Date 2019-01-08 Time 15:48 Rev Time 0.00
Received By jleahy Date 2018-12-18 Time 13:31 Sent To  
Notes
2018-12-19 13:32:01RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-27 Cont ID  
Sent By jleahy Date 2018-11-27 Time 15:59 Rev Time 0.00
Received By jleahy Date 2018-11-06 Time 14:03 Sent To  
Notes
2018-11-07 14:03:27ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status F Date 2019-01-07 Cont ID  
Sent By mcruz Date 2019-01-07 Time 15:26 Rev Time 0.00
Received By mcruz Date 2019-01-07 Time 15:25 Sent To B
Notes
2019-01-07 15:26:55ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO 94-210(P)(4) - A SINGLE SIGN SHALL BE
 AFFIXED TO THE EXTERIOR OF THE FACADE AND SHALLNOT
 EXCEED 36" IN HEIGHT BY 60 PERCENT OF THE WIDTH OF EACH
 SIDE OF THE BUILDING. **NEW PLAN SHOWS 2 NEON SIGNS.
 **THE CODE ALLOWS A SIGN ON THE EXTERIOR OF THE FACADE,
 THE PROPOSED IS SIGN ON THE INTERIOR.
 2) SHOW ON PLAN THAT ALL FASTNERS OF SIGNS SHALL BE
 CONCEALED. EXPOSED RACEWAYS, TRANSFORMERS, BALLASTS AND
 ELECTRICAL WIRING ARE NOT ALLOWED. NO SIGNS WITH
 VISIBLE BACKS ARE PERMITTED.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-14 Cont ID  
Sent By mcruz Date 2018-11-14 Time 11:15 Rev Time 0.00
Received By mcruz Date 2018-11-14 Time 09:56 Sent To B
Notes
2018-11-14 11:15:26ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PURSUANT TO 94-210(P)(4) - A SINGLE SIGN SHALL BE
 AFFIXED TO THE EXTERIOR OF THE FACADE AND SHALLNOT
 EXCEED 36" IN HEIGHT BY 60 PERCENT OF THE WIDTH OF EACH
 SIDE OF THE BUILDING.
 2) SHOW ONPLAN THAT ALL FASTNERS OF SIGNS SHALL BE
 CONCEALED. EXPOSED RACEWAYS, TRANSFORMERS, BALLASTS AND
 ELECTRICAL WIRING ARE NOT ALLOWED. NO SIGNS WITH
 VISIBLE BACKS ARE PERMITTED.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  