Plan Review Details - Permit 18110093
Plan Review Stops For Permit 18110093
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-03-29 Cont ID  
Sent By scwelter Date 2021-03-29 Time 13:25 Rev Time 0.00
Received By scwelter Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-08-22 Cont ID  
Sent By dbattles Date 2019-08-22 Time 09:49 Rev Time 0.00
Received By dbattles Date 2019-08-22 Time 09:49 Sent To  
Notes
2019-08-22 09:49:04PROVISOS:
 EXTERIOR DOORS, MULLIONS
 ROOF HATCHES
 WINDOWS AND MULLIONS
 PANEL WALLS, STOREFRONTS AND WALL LOUVERS
 ROOFING PRODUCTS AND ASSEMBLIES PROVIDED AT SUB PERMIT
 APPLICATION
 LIGHT WEIGHT CONCRETE INSULATION
 ROOF TOP VENTILATORS
 PRE-ENGINEERED AC STANDS
 HANDRAIL AND GUARDRAIL
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 ALL OTHER ITEMS OTHER THAN BMEP
  
 PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A PDF
 VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-08-08 Cont ID  
Sent By dbattles Date 2019-08-08 Time 16:17 Rev Time 0.00
Received By dbattles Date 2019-08-08 Time 16:17 Sent To  
Notes
2019-08-08 16:18:09PROVISOS:
 EXTERIOR DOORS, MULLIONS
 ROOF HATCHES
 WINDOWS AND MULLIONS
 PANEL WALLS, STOREFRONTS AND WALL LOUVERS
 ROOFING PRODUCTS AND ASSEMBLIES PROVIDED AT SUB PERMIT
 APPLICATION
 LIGHT WEIGHT CONCRETE INSULATION
 ROOF TOP VENTILATORS
 PRE-ENGINEERED AC STANDS
 HANDRAIL AND GUARDRAIL
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 ALL OTHER ITEMS OTHER THAN BMEP
  
 PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A PDF
 VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-06-06 Cont ID  
Sent By dbattles Date 2019-06-06 Time 14:27 Rev Time 0.00
Received By dbattles Date 2019-05-21 Time 10:27 Sent To  
Notes
2019-06-06 14:41:563RD REVIEW
 ALL OTHER COMMENTS ARE RESOLVED
  
 15.) REG ? STAIR 110, 210 & 310 IS AN EXIT ACCESS STAIR
 UNDER FBC 1019.3.4 AND VERTICAL OPENINGS ARE ALLOWED
 PER 712.1.12. CLOSELY SPACED SPRINKLER HEADS PER
 903.3.1.1 (ON A SEPARATE PERMIT) WILL BE INSTALLED AT
 VERTICAL OPENINGS ON 1ST AND 2ND FLOORS AND A SOFFIT IS
 PROVIDED WHICH SERVES AS A DRAFT CURTAIN. ALLOWABLE
 EXIT ACCESS TRAVEL DISTANCE FOR ?A? PER 1017.2 IS 250?.
 TRAVEL DISTANCES PROVIDED TO EXTERIOR EXIT ACCESS DOORS
 ARE EQUAL TO OR LESS THAN 202?.
  
 15) 1023.1 FBC[BUILDING] STAIR 310 IS USED FOR EGRESS
 AND SHOULD FOLLOW SECTION 1023 FOR INTERIOR STAIR.
 VERTICAL OPENINGS WILL FOLLOW 712.1.9 AND 404 FOR
 ATRIUMS.
 THE REASON THIS COMMENT REMAINS IS THAT, WHILE YOU MEET
 MOST OF THE REQUIREMENTS FOR 712.1.12, OPENINGS PER
 1019.3 NOTE #1 EXIT ACCESS STAIRWAYS AND RAMPS THAT
 SERVE OR ATMOSPHERICALLY COMMUNICATE BETWEEN ONLY TWO
 STORIES. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN
 TO OTHER STORIES.
 BECAUSE THAT IS AN EXIT STAIR IT SHOULD BE ENCLOSED OR
 ONLY SERVE 2 FLOORS.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-05-03 Cont ID  
Sent By dbattles Date 2019-05-03 Time 11:16 Rev Time 0.00
Received By dbattles Date 2019-05-01 Time 10:10 Sent To  
Notes
2019-05-03 11:19:58 
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18110093
 ADD: 609 8TH ST.
 CONT: COOPER CONSTRUCTION MANAGEMENT & CONSULTING
 TEL: 561-588-5222
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. JAN. 22/ 2019
 ACTION: DENIED
  
 1) OK
  
 2) OK - IN PROGRESS
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  -THE INTENT OF THE COMMENT WAS TO CONVEY THAT IT IS
 ADVANTAGOUS TO UTILIZE ONE FIRE STOPPING CONTRACTOR OR
 MAKE SURE EACH TRADE IS USING THE FIRESTOPPING TYPES.
  
 3) OK.
 -NEW COMMENT: SHEET S0.1 UNDER FOUNDATIONS SECTION B(3)
 STATES SHALLOW FOUNDATIONS AT LEAST 12 INCHES BELOW
 GRADE, BUT THE SOILS REPORTS IS CALLING FOR SHALLOW
 FOUNDATIONS MINIMUM 18 INCHES BELOW. PLEASE COORDINATE
 THE PLANS WITH THE REPORT.
  
 4A) OK. VERIFTY THAT THIS IS NOT EXPOSURE C WITH M.R.H.
 OVER 30 FEET AND B TERRAIN EXTENDING 2600 FEET FROM THE
 SITE.
  
 4B) OK
  
 4C) OK
  
 5) OK- THE FOLLOWING WILL BECOME PROVISOS (NO RESPONSE
 REQUIRED)
 (A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
 (H) HANDRAILS AND GUARDS
 (I) STAGE CURTAINS
  
 5A) OK
  
 5B) OK
  
 6) OK. PROVIDE COPY OF RECORDED UNITY OF TITLE PRIOR TO
 PERMIT ISSUANCE.
  
 7A) OK
  
 7B) OK
  
 7C) OK
  
 7D) THIS WILL TRIPLE THE OCCUPANT LOAD PLEASE PROVIDE A
 NEW ANALYSIS FOR THIS FLOOR FOR EXITING. PLEASE SHOW
 HOW THE OCCUPANTS WILL EXIT SHOW THE EXITING FOR THIS
 FLOOR AND THE ADDITIONAL LOAD FROM THE MEZZANINE. THE
 MEZZANINE OCCUPANT LOAD IS FIGURED IN WITH THE 2ND
 FLOOR OCCUPANT LOAD FOR EXITING. PLEASE PROVIDE THE
 TOTAL OCCUPANT LOAD FOR THE 2ND FLOOR WITH MEZZANINE
 OCCUPANT LOAD. FBC-B 1019.1. 2017 FBC-B 505.2.2 MEANS
 OF EGRESS. THE MEANS OF EGRESS FOR MEZZANINES SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF CHAPTER 10.
 -COMMENT NOT ADDRESSED-SHEET A0.02 BALCONY LEVEL NOW
 STATES 570 OCCUPANTS BELOW, BUT 2 ND FLOOR DOES NOT
 ACCOUNT FOR THE ADDITIONAL NUMBER AT THE 2 ND FLOOR
 EXITS.
  
 7E) OK
  
 7F) OK
  
 7G) OK
  
 7H) OK
  
 7I) OK
  
 7I) OK
  
 7J) OK
  
 7K) OK
  
 7L) OK
  
 8) OK
  
 8B) OK
  
 8C) OK
  
 8C) OK
  
 9) OK
  
 9A) OK
  
 9B) OK
  
 10) OK
  
 11) OK
  
 12) OK
  
 2ND REVIEW 5/3/2019
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 NEW COMMENTS:
 13) 107.3.5 FBC[AMENDED] MEZZANINE/BALCONY LEVEL SHOWS
 RAMS DOWN IN HALLWAY TO GET TO STAGE ELEVATION AND
 SECTIONS ON A3.03 SHOW A 6 INCH STEP FROM HALL MO2 TO
 LOBBY 311.
 -PLEASE SHOW THIS STEP IN PLAN VIEW.
  
 14) 107.3.5 FBC[AMENDED] SHEET A1.03 SHOWS DOOR CALL
 OUT 316 OUTSIDE OF STAIR 326. PLAN DOES NOT SHOW THE
 DOOR SWING, BUT DOOR SCHEDULE DOES HAVE DOOR THERE.
  A) PLEASE REVIEW WHAT IS HERE AND REVISE.
  B) ALSO, LOOK AT DOUBLE DOORS LABLED 130 AND 135 IN
 HALL M02. I DO NOT SEE THESE DOORS ON DOOR SCHEDULE.
  C) DOOR 311 TO ROOF GARDEN. SECTION 1/A3.01 LOOKS LIKE
 DOOR IS AT SAME ELEVATION AS ROOF AND INTERIOR. SECTION
 1/A3.03 LOOKS LIKE THE DOOR MAY BE RAISED. PLEASE
 VERIFY HOW ACCESSIBLE PATH WORKS FROM ELEVATOR P1 TO
 ROOF GARDEN. ALSO, DOES ELEV F1 HAVE A STEP DOWN AT
 MEZZANINE/PATIO LEVEL?
  
 15) 1023.1 FBC[BUILDING] STAIR 310 IS USED FOR EGRESS
 AND SHOULD FOLLOW SECTION 1023 FOR INTERIOR STAIR.
 VERTICAL OPENINGS WILL FOLLOW 712.1.9 AND 404 FOR
 ATRIUMS.
  
 16) 1029.9.1 MINIMUM AISLE WIDTH.
  -COODINATE LIFE SAFETY PLAN WITH FLOOR PLAN TO SHOW
 EXIT ACCESS AISLES. FLOOR PLAN SHOWS TABLES THAT WOULD
 BE IN THE ACCESS AILES SHOWN ON LIFE SAFETY. ALSO,
 REVIEW SECTION 1029.12.1 FOR SEATING AT TABLES NEXT TO
 AISLES.
  
 17) 456.3.2.2 PUBLIC BATHROOMS SHALL BE COMPLETELY
 ENCLOSED AND SHALL HAVE TIGHT-FITTING, SELF-CLOSING
 DOORS OR, IN PUBLIC LODGING ESTABLISHMENTS OR BATHROOMS
 LOCATED OUTSIDE A PUBLIC FOOD SERVICE, HAVE ENTRANCES
 AND EXITS CONSTRUCTED IN SUCH A MANNER AS TO ENSURE
 PRIVACY OF OCCUPANTS.
  -UPDATE DOOR HARDWARE SCHEDULE FOR CLOSERS.
  
 18) 1010.1.10 PANIC AND FIRE EXIT HARDWARE.
  -REVIEW WHICH DOORS REQUIRE EXIT HARDWARE AND ADD TO
 DOOR SCHEDULE.
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By jwitmer Date 2019-01-22 Time 08:46 Rev Time 0.00
Received By jwitmer Date 2019-01-10 Time 11:51 Sent To  
Notes
2019-01-22 08:46:062017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18110093
 ADD: 609 8TH ST.
 CONT: COOPER CONSTRUCTION MANAGEMENT & CONSULTING
 TEL: 561-588-5222
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. JAN. 22/ 2019
 ACTION: DENIED
  
 1) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 2) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING / FL
 S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) COMPLETED. 109.3.6.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 FORMS SENT TO: [email protected] MON. JAN. 14/ 2019
 12:54 PM
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) THE STRUCTURAL SHEET S0.1 UNDER THE HEADING
 EARTHWORK & FOUNDATIONS NOTE A INDICATES THAT THE
 FOUNDATION DESIGN WAS BASED ON THE GEOTECHNICAL
 ENGINEERING REPORT PREPARED BY TERRACON CONSULTANTS,
 INC. (REPORT NO. 185072). DATED JULY 20/2018. PLEASE
 SUBMIT AN ELECTRONIC REPORT WITH ELECTRONIC SIGNATURE
 OR A PAPER REPORT WITH SIGNATURE AND SEAL.
  
 4A) THE SHEET S0.1 GENERAL NOTES, DESIGN CRITERIA (4)
 WIND LOADS OR THE WIND DESIGN CRITERIA IS MISSING THE
 MEAN ROOF HEIGHT FOR MULTIPLIERS FOR THE HEIGHT OF THE
 BUILDING AND EXPOSURE. WIND EXPOSURE. APPLICABLE WIND
 DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED.
 TABLE 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE
 30.3.1. THE CODE ANALYSIS ON SHEET A0.03 DOES STATE THE
 MAXIMUM BUILDING HEIGHT OF 41 FEET 7 INCHES. THIS IS
 NOT GIVEN IN THE WIND DESIGN CRITERIA, AND THE FACTOR
 FOR HEIGHT AND EXPOSURE IS NOT GIVEN, B EXPOSURE @ 40
 FEET. MULTIPLIER OF 1.09 USED.
  
 4B) THE OTHER ISSUE IS IN NOTE 5 ON SHEET S0.4. DESIGN
 VALUES SHOWN IN THIS TABLE ARE ULTIMATE VALUES FOR USE
 WITH LRFD (LOAD RESISTANCE FACTORED DESIGN). THE 2017
 FBC-B USES PRESSURES FOR COMPONENTS AND CLADDING IN
 VULT( ULTIMATE DESIGN WIND SPEED) AND VASD (ALLOWABLE
 OR NOMINAL SERVICE LOADS). THE SAME HOLDS TRUE IN ASCE
 7-10 CHAPTER 30 HOLDS TRUE TO THE USAGE OF THE
 TERMINOLOGY OF VULT AND VASD. THE TERMINOLOGY OF LRFD
 LENDS ITSELF TO MORE LIKE CONCRETE, STEEL AND TIMBER.
  
 4C) PLEASE SUBMIT THE WIND PRESSURES IN VASD SINCE ALL
 PRODUCT APPROVALS ARE PUBLISHED IN VASD, THE INSPECTORS
 DO NOT HAVE THE TIME TO COMPUTE THE VULT TO VASD. FBC-B
 1609.3.1.
  
 5) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 5A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 5B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6) SHEET C6.1& C2.1 SHOWS THE EXISTING BUILDING GOING
 THROUGH THE PROPERTY LINE FOR LOT 4 & 5, AND THE
 PROPOSED 3 STORY ADDITION GOING THROUGH THE PROPERTY
 LINE BETWEEN LOTS 5 & 6. PLEASE PROVIDE IS THE3 LOTS
 GOING TO BE REPLATED. SO NO PROPERTY LINES GO THROUGH
 THE BUILDING AND THE REQUIREMENT FOR 4 HOUR FIRE WALLS
 WILL NOT BE REQUIRED. 2017 FBC-B TABLE 602 & FIRE WALLS
 FBC-B 706.1.1.
  
 7A) SHEET 005-A0.03 CODE ANALYSIS. THE 2017 FLORIDA
 EXISTING BUILDING CODE, PRESCRIPTIVE COMPLIANCE METHOD.
 CHANGE OF OCCUPANCY. 407.1. 407.1 CONFORMANCE. NO
 CHANGE SHALL BE MADE IN THE USE OR OCCUPANCY OF ANY
 BUILDING UNLESS SUCH BUILDING IS MADE TO COMPLY WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING
 FOR THE USE OR OCCUPANCY. CHANGES IN USE OR OCCUPANCY
 IN A BUILDING OR PORTION THEREOF SHALL BE SUCH THAT THE
 EXISTING BUILDING IS NO LESS COMPLYING WITH THE
 PROVISIONS OF THIS CODE THAN THE EXISTING BUILDING OR
 STRUCTURE WAS PRIOR TO THE CHANGE. SUBJECT TO THE
 APPROVAL OF THE BUILDING OFFICIAL, THE USE OR OCCUPANCY
 OF EXISTING BUILDINGS SHALL BE PERMITTED TO BE CHANGED
 AND THE BUILDING IS ALLOWED TO BE OCCUPIED FOR PURPOSES
 IN OTHER GROUPS WITHOUT CONFORMING TO ALL OF THE
 REQUIREMENTS OF THIS CODE FOR THOSE GROUPS, PROVIDED
 THE NEW OR PROPOSED USE IS LESS HAZARDOUS, BASED ON
 LIFE AND FIRE RISK, THAN THE EXISTING USE.
 PLEASE NOTE THE CODE RESEARCH FOUND ON SHEET A0.03 DOES
 INDICATE THAT THERE WERE 2 FLOORS WITH AN R-2
 OCCUPANCY. SO THERE IS A PARTIAL CHANGE OF OCCUPANCY.
 THE NEW OCCUPANCY (ASSEMBLY) IS A MORE STRINGENT USE
 AND OCCUPANCY THAN THE R2.
  
 2017 FBC-EXISTING BUILDING CODE 401.3 DANGEROUS
 CONDITIONS. THE BUILDING OFFICIAL SHALL HAVE THE
 AUTHORITY TO REQUIRE THE ELIMINATION OF CONDITIONS
 DEEMED DANGEROUS. THIS NOTE HOLDS TRUE FOR ALL OF
 COMMENTS 7A- 7_.
  
 7B) PLEASE NOTE SHEET 005-A0.03 CODE ANALYSIS UNDER THE
 HEADING CODE RESEARCH APPLICABLE CODES. THE DESIGNER OF
 RECORD LIST THE APPLICABLE CODES 2017 FBC-EB CHAPTER 4
 PRESCRIPTIVE COMPLIANCE METHOD AND CHAPTER 12 HISTORIC
 BUILDINGS. ON THE LEFT SIDE OF THE SAME PAGE THE WORK
 AREA METHOD, LEVEL 2, LEVEL 3 CHANGE OF OCCUPANCY 10
 WHICH IS UNDER THE WORK AREA METHOD OF COMPLIANCE,
 PLEASE CLARIFY TO WHAT DESIGN METHOD (EXISTING BUILDING
 CODE) THIS PROJECT IS TO BE DESIGNED AND COMPLY?
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. THIS
 REVIEW WILL BE ACCOMPLISHED UNDER THE 2017 FBC-EB
 CHAPTER 4 PRESCRIPTIVE COMPLIANCE METHOD AND CHAPTER 12
 HISTORIC BUILDINGS AND THE 2017 FBC-BUILDING WHERE
 DIRECTED BY CHAPTER 4 PRESCRIPTIVE COMPLIANCE METHOD.
  
 7C) PLEASE NOTE SHEET 005-A0.03 CODE ANALYSIS UNDER THE
 HEADING OCCUPANCY DATA ROOMS 201 BALLROOM, & ROOM 202
 UNDER STAGE ARE TO IN THE SAME ROOM. BALLROOM LENDS ONE
 TO BELIEVE THERE WILL BE DANCING IN THIS ROOM. IN THE
 OCCUPANCY TABLE CHART LIST TABLE 1004.1.2 WITH ASSEMBLY
 UNCONCENTRATED 1/15 NET.
 PLEASE REVIEW TABLE 1004.1.2 OF THE 2017 FBC-B 15 SQ.
 FT. WOULD BE USED FOR TABLES AND CHAIRS, 7 SQ. FT.
 WOULD BE USED FOR CHAIRS ONLY, & 5 SQ. FT. WOULD BE
 USED FOR STANDING. IT WOULD APPEAR THAT DANCING WOULD
 BE THE CLOSEST FIT TO THE USAGE AND 5 SQ. FT. SHOULD BE
 USED FOR THE CODE ANALYSIS FOR THE 2ND FLOOR.
  
 7D) THIS WILL TRIPLE THE OCCUPANT LOAD PLEASE PROVIDE A
 NEW ANALYSIS FOR THIS FLOOR FOR EXITING. PLEASE SHOW
 HOW THE OCCUPANTS WILL EXIT SHOW THE EXITING FOR THIS
 FLOOR AND THE ADDITIONAL LOAD FROM THE MEZZANINE. THE
 MEZZANINE OCCUPANT LOAD IS FIGURED IN WITH THE 2ND
 FLOOR OCCUPANT LOAD FOR EXITING. PLEASE PROVIDE THE
 TOTAL OCCUPANT LOAD FOR THE 2ND FLOOR WITH MEZZANINE
 OCCUPANT LOAD. FBC-B 1019.1. 2017 FBC-B 505.2.2 MEANS
 OF EGRESS. THE MEANS OF EGRESS FOR MEZZANINES SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF CHAPTER 10.
  
 7E) SINCE THE 2017 FBC-B SECTION 1019.3 (MEZZANINE
 LEVEL & 2ND FLOOR) DOES ALLOW FOR OPEN STAIRS (EXIT
 ACCESS STAIRWAYS) FOR 2 STORIES:
 1019.3. (1). EXIT ACCESS STAIRWAYS AND RAMPS THAT SERVE
 OR ATMOSPHERICALLY COMMUNICATE BETWEEN ONLY TWO
 STORIES. SUCH INTERCONNECTED STORIES SHALL NOT BE OPEN
 TO OTHER STORIES. PLEASE SHOW HOW EXITING IS TO OCCUR
 WITH NOT GOING THROUGH THE NEW 3 STORY ADDITION.
  
 7F) MEANS OF EGRESS HEADING. FOR THE MEZZANINE LEVEL
 AND 2ND FLOOR, PLEASE SHOW THE TRAVEL DISTANCE FROM THE
 MOST REMOTE POINT ON THE MEZZANINE LEVEL TO AN EXIT,
 SHOW COMPLIANCE WITH EXIT ACCESS TRAVEL DISTANCE IN
 ACCORDANCE WITH
 2017 FBC-B TABLE 1017.2 ASSEMBLY OCCUPANCY, 250 FEET/
 FIRE SPRINKLERED BUILDING.
  
 7G) THE CODE ANALYSIS SHEET A0.03 UNDER THE HEADING
 MEANS OF EGRESS HAS TAKEN A FACTOR OF 0.2? PER OCCUPANT
 FOR STAIRS AND A FACTOR OF 0.15? FOR OTHER MEANS OF
 EGRESS OTHER COMPONENT WIDTHS. THIS EXCEPTION IS FROM
 THE 2017 FBC-B SECTION 1005.3.1 EXCEPTION 1. THE
 EXCEPTION STATES: IN BUILDINGS EQUIPPED THROUGHOUT WITH
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
 WITH SECTION 903.3.1.1 OR 903.3.1.2 AND AN EMERGENCY
 VOICE/ALARM COMMUNICATION SYSTEM IN ACCORDANCE WITH
 SECTION 907.5.2.2. IN THIS SET OF DOCUMENTS SUBMITTED
 YOU ARE TAKING THE EXCEPTION BUT NO PLANS WERE
 SUBMITTED FOR THE EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 7H) THE CODE ANALYSIS SHEET A0.03 UNDER THE HEADING
 MEANS OF EGRESS LIST UNDER THE STAIR REQUIREMENT A
 SINGLE STAIR AND THE SAME FOR DOORWAYS/ EXITS A SINGLE
 DOOR WAY AS MEETING THE WIDTH REQUIREMENTS. WHEN AN
 OCCUPANT LOAD IS MORE THAN 49 THERE IS REQUIRED 2 MEANS
 OF EGRESS SEE TABLE 1006.1.2 OF THE 2017 FBC-B.
  
 7I) (1) THE CODE ANALYSIS SHEET A0.03 UNDER THE HEADING
 MEANS OF EGRESS LIST UNDER THE STAIR REQUIREMENT
 MINIMUM WIDTH LIST THE FBC 1009.4. PLEASE NOTE THIS IS
 AN OLD CODE SECTION. UNDER THE 2017 FBC-B SECTION
 1011.2 IS WIDTH AND CAPACITY.
  
 7I) (2) THE CODE ANALYSIS SHEET A0.03 UNDER THE HEADING
 MEANS OF EGRESS LIST UNDER THE STAIR REQUIREMENT
 MINIMUM STAIR WIDTH LIST < 50 OCCUPANTS = 36 INCH
 STAIRS (AT MEZZANINE STAIRS). PLEASE BE AWARE IN THE
 2015 IBC COMMENTARY SECTION 1011.2 EXCEPTION 1 STATES:
 THE USE OF THIS EXCEPTION IS LIMITED TO BUILDINGS WHERE
 THE ENTIRE OCCUPANT LOAD OF EACH UPPER STORY AND / OR
 BASEMENT IS LESS THAN 50.
  
 7J) THE CODE ANALYSIS LIST THE EXISTING 3RD FLOOR A R2
 RESIDENTIAL MEZZANINE. SHEET 053-A1.01 LIST THE
 BUILDING AREAS. THE 2ND FLOOR OF THE EXISTING BUILDING
 IS GIVEN AS 4,670 SQ. FT. AND THE EXISTING MEZZANINE
 STAGE AS 2,530 SQ. FT. EQUALS 0.54 PERCENT OF THE 2ND
 FLOOR. MY CALCULATIONS FOR THE 2ND FLOOR ARE 41X89=
 3,649 SQ. FT. AND FOR THE MEZZANINE WITHOUT STAIRS
 BEING DEDUCTED ARE 2,284 SQ. FT. OR 0.62 % OF THE 2ND
 FLOOR, THIS MAKES THE 3RD LEVEL A 3RD FLOOR NOT A
 MEZZANINE WITH A 2 STORY ATRIUM BETWEEN THE 2ND FLOOR
 AND 3RD FLOOR. PLEASE NOTE IF THERE ARE OPEN STAIRS
 THAT COMMUNICATE WITH THE 1ST FLOOR THEN THERE IS A 3
 STORY ATRIUM THAT WOULD COMMUNICATE.
  
 7K) PLEASE NOTE IN THE 2017 FBC DECLARING A BUILDING
 TYPE III-B IS THE EQUIVALENT TO A BUILDING TYPE V IN
 THE 1935 WEST PALM BEACH BUILDING CODE. SECTION 2202.
 TYPE V BUILDINGS SHALL NOT EXCEED A HEIGHT OF 35 FEET
 IN HEIGHT IN WHICH THERE MAY BE NO MORE THAN 2 I/2
 STORIES.
 1935 DEFINITION FOR: HEIGHT OF BUILDING. IS THE
 VERTICAL DISTANCE FROM THE GRADE TO THE HIGHEST POINT
 OF THE COPING OF A FLAT ROOFED BUILDING TO THE DECK
 LINE OF A MANSARD ROOF OR TO THE AVERAGE HEIGHT OF THE
 HIGHEST GABLE OF A PITCH OR HIP ROOF.
  
 7L) PLEASE ALSO NOTE IN THE 1035 WEST PALM BEACH
 BUILDING CODE, THE CODE ONLY MAKES MENTION OF
 MEZZANINES IN BUILDING TYPES I AND II BUILDINGS. WHICH
 IN THE 2017 FBC-B WOULD BE TYPE I-A AND I-B TYPE
 BUILDINGS.
 PLEASE ALSO NOTE THAT UNDER THE 1935 CODE TYPE II
 CONSTRUCTION WAS HEAVY TIMBER BUILDINGS COULD BE UP TO
 65 FEET IN HEIGHT, 5 STORIES, (HEAVY TIMBER BUILDINGS
 CANNOT EXCEED ONE STORY) ROOF CONSTRUCTION HEAVY
 TIMBER, FLOORS AND NON-BEARING PARTITIONS MAYBE OF
 WOOD.
  
 8) STAIR SHAFTS & ELEVATOR SHAFTS:
 8A) STAIR 126 ON THE 2ND FLOOR AND 3RD FLOOR THERE ARE
 DUCTS PENETRATING THE STAIRWELL SHAFT WITH A A/C VENT.
 SEE SHEETS 096-M-102 AND 097-M-103. PLEASE REVIEW:
  
 2017 FBC-B 1023.5 PENETRATIONS. PENETRATIONS INTO OR
 THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY
 FOR INDEPENDENT VENTILATION OR PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL
 RACE-WAY SERVING THE INTERIOR EXIT STAIRWAY AND RAMP
 AND TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714. THERE SHALL NOT BE
 PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT
 STAIRWAYS.
  
 8B) SHEET 097-M-103 IN THE ELEV. F1 THERE APPEARS TO BE
 A 4 INCH DIAMETER SUPPLY THAT DUMPS INTO THE ELECTRIC
 ROOM 315. PLEASE REVIEW THE 2017 FBC-B SECTIONS:
 FBC-B 3002.1 HOISTWAY ENCLOSURE PROTECTION. ELEVATOR
 ENCLOSURES SHALL BE SHAFT ENCLOSURES COMPLYING WITH
 SECTION 713.
  
 FBC-B 713.8.1 PROHIBITED PENETRATIONS. PENETRATIONS
 OTHER THAN THOSE NECESSARY FOR THE PURPOSE OF THE SHAFT
 SHALL NOT BE PERMITTED IN SHAFT ENCLOSURES.
  
 8C)(1) SHEET 056-A1.04 STAIR 126 NOTE # 3 INDICATES THE
 USE OF A ROOF HATCH, SHEET 081-A4.10 STAIR 126 DETAIL
 NO. 7 ALSO SHOWS THE ROOF HATCH. 2017 FBC-B 1023.5
 PENETRATIONS. PENETRATIONS INTO OR THROUGH INTERIOR
 EXIT STAIRWAYS AND RAMPS ARE PROHIBITED EXCEPT FOR
 EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 VENTILATION OR PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT
 COMMUNICATION SYSTEMS AND ELECTRICAL RACE-WAY SERVING
 THE INTERIOR EXIT STAIRWAY AND RAMP AND TERMINATING AT
 A STEEL BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2).
 SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714. THERE SHALL NOT BE PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER PROTECTED OR NOT,
 BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS.
  
 8C)(2) SHEET 056-A1.04 STAIR 126 NOTE # 3 INDICATES THE
 USE OF A ROOF HATCH, SHEET 081-A4.10 STAIR 126 DETAIL
 NO. 7 ALSO SHOWS THE ROOF HATCH. PLEASE NOTE DOOR
 SCHEDULE FOUND ON SHEET 090-A6.02 INDICATES A DOOR #
 401 A BILCO (NOA 14-0708.07) TYPE S ROOF HATCH. PLEASE
 REVIEW 3 OF 10 OF THIS PRODUCT APPROVAL FOR CLEAR
 OPENING SIZE AND COMPLIANCE WITH FBC-B 1011.12.2 ROOF
 ACCESS EXCEPTION. IN BUILDINGS WITHOUT OCCUPIED ROOFS,
 ACCESS TO THE ROOF SHALL BE PERMITTED TO BE A ROOF
 HATCH OR TRAPDOOR NOT LESS THAN 16 SQUARE FEET IN AREA
 AND HAVING A MINIMUM DIMENSION OF 2 FEET.
  
 9) SHEET 056-A1.04 DETAIL # 2 INDICATES THE USE OF A
 CONCRETE PAVER PEDESTAL SYSTEM.
  
 9A) PLEASE INDICATE WHERE THE APPROVED ROOF COVERING IS
 IN THIS DETAIL. THE DETAIL SHOWS CONCRETE PLANK
 STRUCTURAL ROOF DECK SYSTEM, 2 INCH RIGID BOARD
 INSULATION, LIGHTWEIGHT CONCRETE TOPPING, SLOPED TO
 ROOF DRAINS, AND PEDESTAL CONCRETE PAVER SYSTEM?
  
 2017 FBC-B 1503.1. ROOF DECKS SHALL BE COVERED WITH
 APPROVED ROOF COVERINGS SECURED TO THE BUILDING OR
 STRUCTURE IN ACCORDANCE WITH THE PROVISIONS OF THIS
 CHAPTER. ROOF COVERINGS SHALL BE DESIGNED AND INSTALLED
 IN ACCORDANCE WITH THIS CODE AND THE APPROVED
 MANUFACTURER?S INSTRUCTIONS SUCH THAT THE ROOF COVERING
 SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE.
  
 9B) PLEASE SUBMIT THE PRODUCT APPROVAL FOR THE CONCRETE
 PAVER PEDESTAL SYSTEM AND THAT WAS TESTED FOR THIS TYPE
 OF INSTALLATION ONTO LIGHTWEIGHT CONCRETE. 107.2.1.2
 ADDITIONAL INFORMATION REQUIRED.
 2017 FBC-B 1609.5.2 ROOF COVERINGS. ROOF COVERINGS
 SHALL COMPLY WITH SECTION 1609.5.1.
  
 1609.5.1 ROOF DECK. THE ROOF DECK SHALL BE DESIGNED TO
 WITHSTAND THE WIND PRESSURES DETERMINED IN ACCORDANCE
 WITH ASCE 7.
  
 10) A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN
 SINCE THERE WAS A GREAT DEFICIENCY IN PLANS AND
 REQUIRED DOCUMENTATION. A COMPLETE REVIEW DID NOT OCCUR
 IN THE 1ST REVIEW CYCLE, WITH THE NEXT PLAN REVIEW
 CYCLE THERE MAYBE ADDITIONAL NEW REVIEW COMMENTS
 BECAUSE OF, PORTIONS OF PLANS NOT REVIEWED, NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 11) - DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE
 PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-23 Cont ID  
Sent By jpearson Date 2019-04-23 Time 15:00 Rev Time 0.00
Received By jpearson Date 2019-04-23 Time 14:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By jpearson Date 2019-01-08 Time 09:27 Rev Time 0.00
Received By jpearson Date 2019-01-07 Time 17:21 Sent To  
Notes
2019-01-08 09:27:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SPECIFY GROUNDING ELECTRODE CONDUCTOR SIZE AND
 CONNECTIONS. STATING TO "GROUND PER NEC 250" IS NOT
 SUFFICIENT. WPB FBC 107.2.1
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 3. PROVIDE LOAD INFORMATION FOR PANEL KP-1 AND KP-2. IT
 APPEARS THE KITCHEN EQUIPMENT IS MISSING. WPB FBC
 107.2.1
 4. PROVIDE COMPLIANCE WITH NEC 240.87.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2019-08-07 Cont ID  
Sent By rrossano Date 2019-08-07 Time   Rev Time 0.00
Received By rrossano Date 2019-08-07 Time   Sent To  
Notes
2019-08-07 13:00:08PROJECT HAS BEEN SUBMITTED FOR A FORMAL ENGINEERING
 REVIEW DIRECTLY TO THE ENGINEERING DEPARTMENT.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2019-06-06 Cont ID  
Sent By shill Date 2019-06-06 Time 15:28 Rev Time 0.00
Received By shill Date 2019-06-06 Time 15:28 Sent To  
Notes
2019-06-06 15:29:06CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 08:53 Rev Time 0.00
Received By shill Date 2019-04-30 Time 08:53 Sent To  
Notes
2019-04-30 08:53:19CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By shill Date 2019-01-22 Time 08:53 Rev Time 0.00
Received By shill Date 2019-01-22 Time 08:53 Sent To  
Notes
2019-01-22 08:53:25CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-05-17 Cont ID  
Sent By pleduc Date 2019-05-17 Time   Rev Time 0.00
Received By pleduc Date 2019-05-17 Time 16:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-28 Cont ID  
Sent By scaldero Date 2019-03-28 Time 14:47 Rev Time 0.00
Received By scaldero Date 2019-03-28 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2019-01-07 Cont ID  
Sent By scaldero Date 2019-01-07 Time 10:53 Rev Time 0.00
Received By scaldero Date 2019-01-02 Time 09:39 Sent To  
Notes
2019-01-07 10:53:29PERMIT #
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 1) SHEET A0.03: UPDATE THE CODE LIST TO REFERENCE THE
 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2015 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 2) PER NFPA 101: CHAPTERS 12 & 13 (NEW AND EXISTING
 ASSEMBLY OCCUPANCIES) - ASSEMBLY OCCUPANCIES WITH
 OCCUPANT LOADS OF MORE THAN 300...SHALL BE PROVIDED
 WITH AN APPROVED FIRE ALARM SYSTEM.
  
 3) NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2019-08-28 Cont ID  
Sent By gjohnson Date 2019-08-28 Time 17:03 Rev Time 0.00
Received By gjohnson Date 2019-08-28 Time 17:03 Sent To  
Notes
2019-08-28 17:08:37PROVISO COMPLY BEFORE FIRST INSPECTION
  
  
 1. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT
 2"PSI THE SIZING TABLE SHOWN FBCFG TABLE 402.4(3) IS
 LESS THAN 2PSI PLEASE CLARIFY IF THE SYSTEM IS A 2PSI
 IT WILL REQUIRE PRESSER REGULATORS AT EACH GAS
 APPLIANCES. PER FBC FG 410.2
  
 2. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 SYSTEM PRESSURE SHALL BE SHOWN ON RISER THE PRESSURE ON
 THE GAS UTILITIES SIDE OF THE METER IS NOT REQUIRED
 ONLY THE BUILDING SIDE OF THE METER IS REQUIRED
  
 DUE TO THE LACK OF INFORMATION ON WATER HEATER THE
 FOLLOWING COMMENTS SHALL BE ADDRESSED
  
 3. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS
 ISSUED. CAN NOT BE DIFFERED SUBMITTAL
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 OR 2017 FBC-RES.
 SEC.G 2407.1 AND G2439.4 IF THE WATER HEATER IS DIRECT
 VENT PROVIDE MANUFACTURE SPECIFICATIONS TO VERIFY.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL
 GAS CODE SEC. 502 THRU 505.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2019-08-14 Cont ID  
Sent By gjohnson Date 2019-08-14 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2019-08-14 Time 10:28 Sent To  
Notes
2019-08-14 10:29:444TH REVIEW: 18110093
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS: 8/14/19 PLEASE CONTACT ME WITH ANY
 QUESTIONS
  
 THE RESPONSE LETTER DATED 7/18 DOES NOT MATCH MY
 COMMENTS FROM 6/04 PLEASE ADDRESS THE FOLLOWING
 COMMENTS.
  
  
 1. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT
 2"PSI THE SIZING TABLE SHOWN FBCFG TABLE 402.4(3) IS
 LESS THAN 2PSI PLEASE CLARIFY IF THE SYSTEM IS A 2PSI
 IT WILL REQUIRE PRESSER REGULATORS AT EACH GAS
 APPLIANCES. PER FBC FG 410.2
  
 2. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 SYSTEM PRESSURE SHALL BE SHOWN ON RISER THE PRESSURE ON
 THE GAS UTILITIES SIDE OF THE METER IS NOT REQUIRED
 ONLY THE BUILDING SIDE OF THE METER IS REQUIRED
  
 DUE TO THE LACK OF INFORMATION ON WATER HEATER THE
 FOLLOWING COMMENTS SHALL BE ADDRESSED
  
 3. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS
 ISSUED. CAN NOT BE DIFFERED SUBMITTAL
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 OR 2017 FBC-RES.
 SEC.G 2407.1 AND G2439.4 IF THE WATER HEATER IS DIRECT
 VENT PROVIDE MANUFACTURE SPECIFICATIONS TO VERIFY.
  
 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, LENGTH,
 SIZE AND TERMINATION OF THE GAS VENTS PER FBC-2017 FUEL
 GAS CODE SEC. 502 THRU 505.
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 09:01 Rev Time 0.00
Received By gjohnson Date 2019-05-22 Time 16:42 Sent To  
Notes
2019-06-04 09:47:533RD REVIEW: 18110093
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
  
  
 GAS COMMENTS:3RD REQUEST
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 INDICATE TYPE OF PIPE ON THE RISER DIAGRAM. THE BRANCH
 TO THE GENERATOR IS BURIED UNDERGROUND STEEL PIPE SHALL
 NOT BE DIRECT BURIAL IT WILL NEED TO BE SLEEVED,
 PROVIDE A DETAIL SHOWING A SEALED SLEEVE OR RUN PE
 PIPE.
 TYPE OF MATERIAL SHALL BE SHOWN ON GAS PIPING ISOMETRIC
 DRAWING
  
 4. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT
 2"PSI THE SIZING TABLE SHOWN FBCFG TABLE 402.4(3) IS
 LESS THAN 2PSI PLEASE CLARIFY IF THE SYSTEM IS A 2PSI
 IT WILL REQUIRE PRESSER REGULATORS AT EACH GAS
 APPLIANCES. PER FBC FG 410.2
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 SYSTEM PRESSURE SHALL BE SHOWN ON RISER THE PRESSURE ON
 THE GAS UTILITIES SIDE OF THE METER IS NOT REQUIRED
 ONLY THE BUILDING SIDE OF THE METER IS REQUIRED
  
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS
 ISSUED. CAN NOT BE DIFFERED SUBMITTAL
  
 10. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 OR 2017 FBC-RES.
 SEC.G 2407.1 AND G2439.4 IF THE WATER HEATER IS DIRECT
 VENT PROVIDE MANUFACTURE SPECIFICATIONS TO VERIFY.
  
 NEW COMETS:
  
 1. PLEASE SIZE PIPE TO FUTURE KITCHEN. WPB AMENDMENTS
 TO FBC SEC.107.2.1
  
 2. PLACE NOTE ON PLAN SEPARATE PERMIT REQUIRED FOR
 KITCHEN GAS PIPING. WPB AMENDMENTS TO FBC SEC.107.2.1
  
 3. THE 3/4 LINE TO THE WATER HEATER IS UNDERSIZED PER
 TABLE 402.4(3) SHALL BE 1"
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-19 Time 08:18 Rev Time 0.00
Received By gjohnson Date 2019-04-19 Time 08:18 Sent To  
Notes
2019-04-19 08:19:142ND REVIEW: 18110093
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
  
  
 GAS COMMENTS:2ND REQUEST
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 INDICATE TYPE OF PIPE ON THE RISER DIAGRAM. THE BRANCH
 TO THE GENERATOR IS BURIED UNDERGROUND STEEL PIPE SHALL
 NOT BE DIRECT BURIAL IT WILL NEED TO BE SLEEVED,
 PROVIDE A DETAIL SHOWING A SEALED SLEEVE OR RUN PE
 PIPE.
  
 4. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT
 2"WG AND PRESSURE DROP OF 3"WG IT GIVES A TABLE WHICH
 IS LESS THAN 2 PSI AND PRESSURE DROP OF 6"WC PLEASE
 CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1. WHAT DOES
 WG STAND FOR IS IT WATER COLUMN IF THATS THE CASE 2"WC
 IS VERY LOW I'LL NEED TO SEE THE MANUFACTURE SPEC TO
 VERIFY THAT IS SUFFICIENT.
  
  
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 SHOW ON RISER
  
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. WE WILL NEED THESE BEFORE GAS PERMIT IS
 ISSUED.
  
 10.FIRST SECTION OF PIPE AFTER METER IS UNDER SIZED IT
 SHOULD BE 11/4" TO MATCH PIPING UPSTREAM. PER FBC FG
 TABLE 402.3(3) WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 11. SHT. P-902 KEY NOTE #4 WHAT IS AN ACCEPTANCE TANK
 PLEASE CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1.
 PLEASE CHANGE PLAN TO THERMAL EXPANSION TANK SO THAT
 THE FIELD INSPECTOR CAN VERIFY COMPLIANCE.
  
 NEW COMMENT
  
 1. THE VALVE FOR FUTURE PIPING SHALL BE LOCKOUT TYPE
 PLEASE PROVIDE A DETAIL OR NOTE THAT THE FUTURE PIPING
 SHALL BE CAPPED AND HAVE A LOCK OUT VALVE.PER WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-01-18 Cont ID  
Sent By gjohnson Date 2019-01-18 Time 12:07 Rev Time 0.00
Received By gjohnson Date 2019-01-18 Time 10:39 Sent To  
Notes
2019-01-18 12:07:491ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. LABEL METER ON THE RISER IT LOOKS LIKE A RPZ BACK
 FLOW. PER WPB AMEND TO FBC 107.2.1
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3. ON THE GAS INFORMATION BOX IT SHOWS NATURAL GAS BUT
 GIVES PROPANE TOTAL BTU LOAD. PLEASE CLARIFY. WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 4. ON THE GAS INFORMATION BOX IT LIST INLET PRESSURE AT
 2"WG AND PRESSURE DROP OF 3"WG IT GIVES A TABLE WHICH
 IS LESS THAN 2 PSI AND PRESSURE DROP OF 6"WC PLEASE
 CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 5. THE BRANCH WITH 1020 BTU IS UNDERSIZED SHOULD BY 1"
 PER FBC FG TABLE 402.4(4)
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE RISER PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 8. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.
  
 9. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 10. PLEASE SIZE FIRST SECTION OF PIPE AFTER METER. WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 11. SHT. P-902 KEY NOTE #4 WHAT IS AN ACCEPTANCE TANK
 PLEASE CLARIFY. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE
 BELOW THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS. 10.4, 10.5 OF NFPA 96-08.
  
 13. SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
  
 14. SHOW PIPING FOR KITCHEN APPLIANCES. WPB AMENDMENTS
 TO FBC SEC.107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By fmittner Date 2019-06-04 Time 11:35 Rev Time 0.00
Received By fmittner Date 2019-06-04 Time 11:35 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-04-30 Cont ID  
Sent By fmittner Date 2019-04-30 Time 14:56 Rev Time 0.00
Received By fmittner Date 2019-04-30 Time 14:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2019-01-04 Cont ID  
Sent By fmittner Date 2019-01-04 Time 11:04 Rev Time 0.00
Received By fmittner Date 2019-01-04 Time 11:04 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-08-28 Cont ID  
Sent By gjohnson Date 2019-08-28 Time 17:15 Rev Time 0.00
Received By gjohnson Date 2019-08-16 Time 13:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-08-16 Cont ID  
Sent By lmarchan Date 2019-08-16 Time 13:08 Rev Time 0.00
Received By lmarchan Date 2019-07-17 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-06-06 Cont ID  
Sent By shill Date 2019-06-06 Time 16:55 Rev Time 0.00
Received By shill Date 2019-05-10 Time 09:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-05-03 Cont ID  
Sent By dbattles Date 2019-05-03 Time 11:20 Rev Time 0.00
Received By dbattles Date 2019-03-27 Time 15:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-22 Cont ID  
Sent By shill Date 2019-01-22 Time 08:53 Rev Time 0.00
Received By shill Date 2018-12-05 Time 14:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-09-05 Cont ID  
Sent By lmarchan Date 2019-09-05 Time 08:33 Rev Time 0.00
Received By lmarchan Date 2019-05-30 Time 08:10 Sent To  
Notes
2019-08-30 11:46:41RECEIPT - 2019-0904-26 - $63,854.41 - PAID
2019-05-30 08:10:585/30/19 SENT TO IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By jwitmer Date 2019-01-22 Time 08:47 Rev Time 0.00
Received By jwitmer Date 2019-01-10 Time 11:51 Sent To  
Notes
2019-01-22 08:46:56IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-08-14 Cont ID  
Sent By shill Date 2019-08-14 Time 13:30 Rev Time 0.00
Received By ccole Date 2019-08-14 Time 13:30 Sent To  
Notes
2019-08-14 13:31:17PASSED BY C.COLE WORKING REMOTELY
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-06-04 Cont ID  
Sent By ccole Date 2019-06-04 Time 09:40 Rev Time 0.00
Received By ccole Date 2019-06-03 Time 16:22 Sent To  
Notes
2019-06-04 10:08:142ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18110093
 6/4/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A0.02, M-101, & M-102: IT APPEARS THAT SMOKE
 DAMPERS MAY BE MISSING FOR DUCTS PENETRATING SMOKE
 PARTITIONS. PLEASE REVISE THE LIFE SAFETY PLANS TO
 CLEARLY SHOW THE LOCATIONS OF ALL SMOKE PARTITIONS, AND
 REVISE THE MECHANICAL PLANS TO SHOW THE SMOKE DAMPER
 LOCATIONS (IF APPLICABLE)- SEE SECTION 607.5.7 FBC M.
  
 2) M-102: THE PLANS ARE STILL NOT CLEARLY INDICATING
 HOW COMBUSTION AIR AND VENTING FOR THE GAS WATER HEATER
 WILL BE ACCOMPLISHED. THERE IS ONE NEW EXTERIOR WALL
 CAP THAT IS NOTED AS WH EXHAUST AIR AND COMBUSTION
 MAKEUP AIR. TYPICALLY DIRECT VENTS TERMINATE AT THE
 EXTERIOR OF THE BUILDING AND DO NOT REQUIRE A WALL CAP.
 IS THIS A CONCENTRIC VENT THAT WEILL BE BRINGING IN THE
 COMBUSTION AIR? IT MAY BE HELPFUL TO PROVIDE A DETAIL
 OR ENLARGED DRAWING. PLEASE NOTE THAT IF COMBUSTION IS
 TO BE BROUGHT IN THOUGH THE OPENING, IT SHALL BE SIZED
 AND LOCATED IN ACCORDANCE WITH SECTION 304.6.2 FBC FG.
  
 3) PLEASE PROVIDE A MASTER LIST ON THE PLAN OF ALL
 REQUESTED DEFERRED SUBMITTALS INCLUDING, BUT NOT
 LIMITED TO:
  
 A) KITCHEN EQUIPMENT PLANS AND SCHEDULES INCLUDING
 PRODUCT DATA SHEETS FOR GAS-FIRED COOKING APPLIANCES.
 B) KITCHEN HOOD AND EXHAUST SYSTEM PLANS
 C) FIRE SUPPRESSION PLAN.
 D) WALK-IN COOLER AND FREEZER PLANS.
 E) GENERATOR
 G) SITE SPECIFIC WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE CHILLER AND ALL OTHER EXTERIOR MECHANICAL
 EQUIPMENT AND COMPONENTS.
 H) FL. PRODUCT APPROVALS AND/OR MIAMI-DADE NOAS FOR THE
 EXHAUST AND O/A LOUVERS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-24 Cont ID  
Sent By ccole Date 2019-04-24 Time 08:58 Rev Time 0.00
Received By ccole Date 2019-04-22 Time 14:05 Sent To  
Notes
2019-04-24 09:28:372ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18110093
 4/24/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN ACCORDANCE WITH THE ARCHITECT'S NARRATIVE, THE
 KITCHEN COOKING APPLIANCES AND EQUIPMENT, THE KITCHEN
 HOODS AND FIRE SUPPRESSION SYSTEMS WILL BE DONE UNDER
 SEPARATE PERMIT. AS A RESULT, THE NARRATIVE INDICATES
 GAS-FIRED COOKING APPLIANCE SUBMOTTALS, COMBUSTION AIR
 CALCULATIONS, AIR BALANCE CALCULATIONS, AND MAKE UP AIR
 TEMPERATURE COMPLIANCE WILL ALSO BE DEFERRED TO A
 FUTURE DATE. PLEASE PLACE LARGE BOLD NOTES ON THE PLAN
 TO INDICATE THIS FOR PUBIC RECORD AND FOR THE
 CONTRACTORS IN THE FIELD.
  
 2) CLARIFY IF THE GENERATOR IS TO BE UNDER SEPARATE
 PERMIT. IF SO, PLEASE ADD IT TO THE LIST OF DEFERRED
 SUBMITTALS LISTED IN COMMENT #1. OTHERWISE, COMPLY WITH
 ITEMS A-F LISTED BELOW:
  
 A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR, FUEL PIPING, ENGINE EXHAUST PIPE, MUFFLER,
 AND ALL OTHER ASSOCIATED SYSTEM COMPONENTS- SECTION
 304.1 FBC M.
  
 B) SUBMIT THE UL 2200 CERTIFICATE OF COMPLIANCE FOR THE
 GENERATOR- SECTION 915.1 FBC M. THE MANUFACTURER'S
 SPECIFICATIONS AND/OR UL CERTIFICATE SHALL INDICATE THE
 GENERATOR IS IN COMPLIANCE WITH NFPA 37.
  
 C) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FUEL
 TANK THAT INCLUDES THE TANK'S UL LISTING- UL 142 OR UL
 2085- SEE SECTION 21.4.2.1.1 NFPA 30.
  
 D) PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL
 SYSTEM RUN AND LENGTH MEASUREMENT, AND TERMINATION
 LOCATION, AND CLEARANCE DISTANCES GRAVITY OR MECHANICAL
 AIR INTAKES INTO THE BUILDING PLEASE INCLUDE ALL
 COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER.- SEE
 SECTION 8.1- 8.4 NFPA 37, AND SECTION 501.3.1 FBC M.
  
 E) PROVIDE DETAILS AND SPECIFICATIONS FOR NORMAL AND
 EMERGENCY RELIEF VENTING OF THE TANK, INCLUDING VENT
 PIPING RUNS AND TERMINATION LOCATIONS- SECTION 24.13
 NFPA 30.
  
 F) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE
 GENERATOR TO THE STRUCTURAL SLAB- SECTION 301.15 FBC M.
  
 3) SHEET M-102: AS PREVIOUSLY NOTED IN THE 1ST REVIEW,
 THE SUPPLY DUCT AND DIFFUSER ARE PROHIBITED FROM
 PENETRATING INTO THE INTERIOR EXIT STAIRWAY- SECTIONS
 1023.5 & 1023.6 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-09 Cont ID  
Sent By ccole Date 2019-01-09 Time 07:48 Rev Time 0.00
Received By ccole Date 2019-01-09 Time 07:25 Sent To  
Notes
2019-01-09 08:16:561ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110093
 1/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOOD AND FIRE SUPRESSION HOWEVER AN AIR BALANCE
 CALCULATION MUST BE PROVIDED ON THE MAIN SET OF PLANS-
 SECTION 508.1.2 FBC M. PLEASE NOTE THAT THE HOOD PLANS
 SHALL ALSO BE IN COMPLIANCE WITH SECTION 508.1.1 MAKEUP
 AIR TEMPERATURE.
  
 2) SHEET M-101: SHOW THE LOCATION OF THE KITCHEN
 EXHAUST HOOD, EXHAUST DUCT, AND EXHAUST DUCT
 TERMINATION LOCATION- SECTION 107.2.1 WPB.
  
 3) SHEET M-101: THE O/A INTAKES FOR FC-1-3 AND THE HOOD
 MAKEUP AIR APPEAR TO BE LIOCATED WITHIN 10' OF THE
 GENERATOR RADIATOR EXHAUST-. PLEASE SHOW THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS ON THE PLAN- SECTION
 401.4 FBC M.
  
 4) M-101, M-102: VERIFY ALL O/A INTAKES SHOWN ON THE1ST
 AND 2ND FLOORS ARE MEETING THE MINIMUM 10' CLEARANCES
 TO EXHAUST OUTLETS AND DRIVE AND PARKING LOT AREAS PER
 SECTION 401.4 FBC M.
  
 5) M-102: VERIFY THE RA INLET IN MECH RM 222 IS LOCATED
 A MINIMUM 10' CLEAR OF ANY DRAFT HOOD APPLIANCES.
  
 6) M-102, A0.02: CLARIFY WHY FIRE DAMPERS ARE SHOWN FOR
 DUCTS PENETRATING MECH RM 222 AND THE CORRIDOR WALLS.
 THE LIFE SAFETY PLAN DOES NOT SHOW FIRE-RATED WALLS IN
 THOSE LOCATIONS.
  
 7) M-102 & M-103: THE SUPPLY DUCTS ARE PROHIBITED FROM
 PENETRATING AND SUPPLYING AIR TO THE INTERIOR EXIT
 STAIRWAY- SECTIONS 1023.5 & 1023.6 FBC B.
  
 8) PROVIDE AN ENLARGED KITCHEN EQUIPMENT PLAN AND
 EQUIPMENT SCHEDULE. A) SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR GAS-FIRED COOKING APPLIANCES-
 SECTION 107.2.1 WPB. B) INDICATE HOW COMBUSTION AIR IS
 BEING PROVIDED AND PROVIDE A CALCULATION- SECTION 304
 FBC FG.
  
 9) PROVIDE A MECHANICAL ROOF PLAN- SECTION 107.2.1 WPB.
  
 10) GAS WATER HEATER: A) PROVIDE AN EQUIPMENT SCHEDULE
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION 624.1
 FBC FG. B) PROVIDE VENTING AND COMBUSTION AIR PLANS-
 SECTIONS 304 AND 503 FBC FG.
  
 11) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE CHILLER, GENERATOR, AND ALL OTHER EXTERIOR
 MECHANICAL EQUIPMENT- SECTION 301.15 FBC M.
  
 12) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE CHILLER
 AND THE FAN COIL UNITS- SECTION 307.2.1 FBC M.
  
 13) SUBMIT MANUFACTURER'S SPECIFICATIONS AND A FL.
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE LOUVERS-
 SECTION 401.5 FBC M AND RULE 9N-3 FAC.
  
 14) SHOW THE LOCATION OF THE LEVATOR CONTROL ROOM AND
 PROVIDE AN INDEPENDENT VENTILATION OR AIR CONDITIONING
 SYSTEM PER SECTION 3005.2 FBC B.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-08-28 Cont ID  
Sent By gjohnson Date 2019-08-28 Time 17:14 Rev Time 0.00
Received By gjohnson Date 2019-08-28 Time 16:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-08-14 Cont ID  
Sent By gjohnson Date 2019-08-14 Time 10:31 Rev Time 0.00
Received By gjohnson Date 2019-08-14 Time 10:31 Sent To  
Notes
2019-08-14 10:35:51PLUMBING NOTE: PROVISO THESE ITEMS TO BE ADDRESSED
 BEFORE FIRST INSPECTION.
  
 THE VENT FOR THE BAR AREA THRU THE SIDE WALL SHALL
 COMPLY WITH.
 FBC PL 903.6 EXTENSION THROUGH THE WALL.
 VENT TERMINALS EXTENDING THROUGH THE WALL SHALL
 TERMINATE AT A POINT NOT LESS THAN 10 FEET (3048 MM)
 FROM A LOT LINE AND NOT LESS THAN 10 FEET (3048 MM)
 ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL NOT
 TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH SOFFIT
 VENTS. SIDE WALL VENT TERMINALS SHALL BE PROTECTED TO
 PREVENT BIRDS OR RODENTS FROM ENTERING OR BLOCKING THE
 VENT OPENING.
  
  
 A) SEPARATE PERMIT IS REQUIRED FOR BACKFLOW ASSEMBLIES
 PER WPB UTILITIES.
 B) SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR
 C) SEPARATE PERMIT IS REQUIRED FOR GENERATOR AND FUEL
 SYSTEM
 D) SEPARATE PERMIT IS REQUIRED FOR FUEL GAS
 E) KITCHEN IS PERMITTED AS VENILLA SHELL SEPARATE
 PERMIT REQUIRED FOR BUILD OUT OF KITCHEN INCLUDING
 GREASE INTERCEPTOR CALCULATIONS.
  
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL.
 2. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH
 EDITION 2017
 4. A SEPARATE PERMIT IS REQUIRED FOR GREASE INTERCEPTOR
 PER WPB UTILITIES.
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
 6. BACKFLOW DEVICE REQUIRED ON ALL EQUIPMENT CONNECTED
 TO THE POTABLE WATER SYSTEM. FBC PL 608.3, 608.16.1,
 608.16.10
 7. THE ELEVATOR SUMP PUMP SHALL DISCHARGE THROUGH AN
 OIL SEPARATOR OR THE PUMP SHALL BE AN OIL MINDER TYPE.
 PER FBC PL 1003.4
 8. THE GREASE INTERCEPTOR SHALL BE INSTALLED PER
 MANUFACTURE INSTALLATION GUIDE AND HAVE 4? CLEAN ON
 DISCHARGE FOR A SAMPLING PORT. PER WPB UTILITIES DEPT.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 08:04 Rev Time 0.00
Received By gjohnson Date 2019-05-22 Time 16:41 Sent To  
Notes
2019-06-04 08:56:32PLUMBING NOTE:
  
 THE VENT FOR THE BAR AREA THRU THE SIDE WALL SHALL
 COMPLY WITH.
 FBC PL 903.6 EXTENSION THROUGH THE WALL.
 VENT TERMINALS EXTENDING THROUGH THE WALL SHALL
 TERMINATE AT A POINT NOT LESS THAN 10 FEET (3048 MM)
 FROM A LOT LINE AND NOT LESS THAN 10 FEET (3048 MM)
 ABOVE AVERAGE GROUND LEVEL. VENT TERMINALS SHALL NOT
 TERMINATE UNDER THE OVERHANG OF A STRUCTURE WITH SOFFIT
 VENTS. SIDE WALL VENT TERMINALS SHALL BE PROTECTED TO
 PREVENT BIRDS OR RODENTS FROM ENTERING OR BLOCKING THE
 VENT OPENING.
  
  
 A) SEPARATE PERMIT IS REQUIRED FOR BACKFLOW ASSEMBLIES
 PER WPB UTILITIES.
 B) SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR
 C) SEPARATE PERMIT IS REQUIRED FOR GENERATOR AND FUEL
 SYSTEM
 D) SEPARATE PERMIT IS REQUIRED FOR FUEL GAS
 E) KITCHEN IS PERMITTED AS VENILLA SHELL SEPARATE
 PERMIT REQUIRED FOR BUILD OUT OF KITCHEN INCLUDING
 GREASE INTERCEPTOR CALCULATIONS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-04-19 Cont ID  
Sent By gjohnson Date 2019-04-18 Time 15:25 Rev Time 0.00
Received By gjohnson Date 2019-04-17 Time 11:57 Sent To  
Notes
2019-04-18 15:26:142ND REVIEW: 18110093
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A4.05, A4.06, A4.07 SHOW THE DIMENSIONS ON THE
 CLEAR FLOOR SPACE 2ND REQUEST SHALL COMPLY WITH FLORIDA
 ACCESSIBILITY 604.3.1, 608.2.1 , 606.2 ADDITIONAL
 INFORMATION REQUIRED ON PLANS PER WPB AMEND TO FBC
 107.2.1
  
 2.SHT A4.07 SHOW HEIGHT OF SHOWER SEAT SHALL COMPLY
 WITH FLORIDA ACCESSIBILITY 610.3 ADDITIONAL INFORMATION
 REQUIRED ON PLANS PER WPB AMEND TO FBC 107.2.1
  
 3.SHT A4.07 SHOW DIMENSION BETWEEN THE FRONT OF THE
 SHOWER AND THE SIDE WALL OF TOILET. PER WPB AMEND TO
 FBC 107.2.1 FLORIDA ACCESSIBILITY 604.3.1 ADDITIONAL
 INFORMATION REQUIRED ON PLANS PER WPB AMEND TO FBC
 107.2.1
  
 4. PLACE NOTE ON PLAN ALL VENTS SHALL COMPLY WITH. FBC
 PL TABLE 906.1 906.2 ADDITIONAL INFORMATION REQUIRED ON
 PLANS PER WPB AMEND TO FBC 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-18 Cont ID  
Sent By gjohnson Date 2019-01-18 Time 10:29 Rev Time 0.00
Received By gjohnson Date 2019-01-17 Time 11:04 Sent To  
Notes
2019-01-18 10:30:10 
 1ST REVIEW: 18110093
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BATHROOM OPENING INTO THE KITCHEN PREP AREA IS A
 CODE VIOLATION. TOILET ROOMS SHALL NOT OPEN DIRECTLY
 INTO A ROOM USED FOR THE PREPARATION OF FOOD FOR
 SERVICE TO THE PUBLIC. PER FBC PL 403.3.2
  
 2. IN THE MULTI USER BATHROOMS AT LEAST ONE LAVATORY
 SHALL COMPLY WITH 606 AND SHALL NOT BE LOCATED IN A
 TOILET COMPARTMENT. PER FBC ACC 213.3.4
  
 3. SHT A4.07 DETAIL 1 THE 36" INSIDE DIMENSION FOR THE
 TRANSFER SHOWER IS NOT A MINIMUM IT SHALL BE AN EXACT
 36" CLEAR INSIDE DIMENSION. PER FBC ACC 608.2.1
  
 4. PROVIDE A LEGEND FOR THE CLEAR FLOOR SPACE AROUND
 THE ACCESSIBLE FIXTURES OR SHOW DIMENSIONS ON EACH
 SPACE. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. A4.07 DETAIL ONE SHOW A 60X56" CLEAR FLOOR
 SPACE FOR THE TOILET AND A 36"X48" IN FRONT OF THE
 SHOWER WITH 1 END LINED UP WITH CONTROL WALL. PER FBC
 ACC 604.3.1, 608.2.1
  
 6. SHT. A4.07 DETAIL B IS SHOWING A 2'-6" MIN DIMENSION
 FOR THE SHOWER IT SHALL BE 36". PER FBC ACC 608.2.1
  
 7. SHOW COMPLIANCE WITH FBC ACC 610.3 IN TRANSFER-TYPE
 SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A
 POINT WITHIN 3 INCHES OF THE COMPARTMENT ENTRY. THE TOP
 OF THE SEAT SHALL BE 17 INCHES MINIMUM AND 19 INCHES
 MAXIMUM ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL
 COMPLY WITH 610.3.1 OR 610.3.2.
  
 8. SHT. P-105 IT APPEARS THE WATER PIPING RUNNING UNDER
 THE SLAB TO THE BAR IS MISSED LABELED THE KEY NOTE
 STATES IT AT #4 THE PIPING SHOWS #3 PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 9. PROVIDE FIRE STOPPING DETAILS FOR PLASTIC PIPING.
 PER WPB AMEND TO FBC 107.2.1
  
 10. SHT.P-901 PLEASE REMOVE GAS PING FROM WATER
 ISOMETRIC IT IS TO CONGESTED. PER WPB AMEND TO FBC
 107.2.1
  
 11. SHT P-901 PLEASE SHOW THE FOLLOWING ON THE
 ISOMETRIC THE FLOOR LEVELS, VALVES ON THE DROPS AND
 BRANCHES AND LABEL THE FIXTURES. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 12. SHT P-906 IN ADDING UP ALL THE SQFT I CAME OUT WITH
 2554 WHICH MAKES THE HORIZONTAL PIPING UNDER SIZED 6"
 SHOULD RUN TO THE 4TH BRANCH FROM THE END PLEASE SHOE
 SQFT TABLES ON THE PIPING AND INDICATE WHAT SLOPE THE
 PIPING WILL BE INSTALLED. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 13. THE SANITARY SYSTEM SERVING THE BAR SHALL HAVE A
 MINIMUM OF 1 VENT EXTENDING TO THE OUTDOORS. PER FBC PL
 904.1, 904.1.1
  
 14. SHT. P-904 KEY NOTE #4 LIST A 3" VENT THE VENT FOR
 THE GREASE SYSTEM IS TAGGED #4 BUT IS SIZED AS 2"
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 15. SHT. P-904 THE VENT SHOWN BY ITSELF NEXT TO THE 2ND
 + 3RD FLOOR BATHROOM ISOMETRIC IS TAGGED AS #6 IT IS
 SIZED AT 2" THE KEY NOTE #6 LIST IT AT 3" PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 16. ALL VENTS SHALL COMPLY WITH FBC PL TABLE 906.1,
 906.2
  
 17. SHT. P-904 ON THE ISOMETRIC FOR THE GREASE WASTE
 SYSTEM THE FLOOR SINK APPEARS TO BE MISLABELED AS THE
 FLOOR DRAIN AND THE FLOOR DRAIN IS NOT LABELED PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 18. SHT. P-904 PLEASE SHOE P-TRAP ON ALL FLOOR DRAINS
 AND INDICATE TRAP PRIMER. PER FBC PL 1002.1, 1002.4.1
  
 19. SHT. P-902 PLEASE SHOW SHUT OFF VALVES ON THE DROPS
 AND BRANCHES. PER FBC PL 606.1
  
 20. SHT. P-902 INDICATE ON THE ISOMETRIC A TEMPERATURE
 LIMITING DEVISE COMPLYING WITH ASSE 1070 IS REQUIRED ON
 THE LAVATORY'S IN THE BATHROOMS. PER FBC PL 416.5
  
 21. SHT. A-4.07 GRAB BARS SHALL BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM FINISHED FLOOR PER FBC ACC
 609.4
  
 22. SHT. P-902 LABEL UNDERGROUND PIPING ON WATER AND
 GAS. PER WPB AMEND TO FBC 107.2.1
  
 23. PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS. PER
 FBC PL 1003.2
  
 24. THE MOP SINK IN THE KITCHEN AREA SHALL BE INCLUDED
 ON THE GREASE PIPING AND SIZING CALCULATIONS. PER FBC
 PL 1003.3.1
  
 25. PROVIDE PIPING DETAIL FOR GREASE INTERCEPTOR. PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 3 Status P Date 2019-06-04 Cont ID  
Sent By gjohnson Date 2019-06-04 Time 08:57 Rev Time 0.00
Received By gjohnson Date 2019-06-04 Time 08:57 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status F Date 2019-04-18 Cont ID  
Sent By gjohnson Date 2019-04-18 Time 15:29 Rev Time 0.00
Received By gjohnson Date 2019-04-18 Time 15:28 Sent To  
Notes
2019-04-18 15:55:272ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS FOR GREASE INTERCEPTOR:
  
 2ND REQUEST 1. PROVIDE GREASE INTERCEPTOR SIZING
 CALCULATIONS. PER FBC PL 1003.2 INFORMATION REQUIRED IN
 ORDER TO APPROVE THE GREASE INTERCEPTOR ON THIS MASTER
 SUBMITTAL. YOU CAN CONNTACT LEE SCHNEEWEISS FROM THE
 SCHIER FOR SIZING CALCULATIONS HIS NUMBER IS
 800-538-4792
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2019-01-18 Cont ID  
Sent By gjohnson Date 2019-01-18 Time 10:30 Rev Time 0.00
Received By gjohnson Date 2019-01-18 Time 10:30 Sent To  
Notes
2019-01-18 10:37:361ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS FOR GREASE INTERCEPTOR:
  
 1. PROVIDE GREASE INTERCEPTOR SIZING CALCULATIONS. PER
 FBC PL 1003.2
  
 2. THE MOP SINK IN THE KITCHEN AREA SHALL BE INCLUDED
 ON THE GREASE PIPING AND SIZING CALCULATIONS. PER FBC
 PL 1003.3.1
  
 3. PROVIDE PIPING DETAIL FOR GREASE INTERCEPTOR. PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status P Date 2019-01-17 Cont ID  
Sent By gjohnson Date 2019-01-17 Time 13:54 Rev Time 0.00
Received By gjohnson Date 2019-01-17 Time 13:54 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-06-06 Cont ID  
Sent By shill Date 2019-06-06 Time 15:30 Rev Time 0.00
Received By shill Date 2019-06-06 Time 15:30 Sent To  
Notes
2019-06-06 15:31:25ROOF PERMIT APPLICATION WITH PRODUCT APPROVALS REVIEWED
 BY DESIGNER OF RECORD IS REQUIRED PRIOR TO INSTALLATION
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-08-22 Cont ID  
Sent By dbattles Date 2019-08-22 Time 09:49 Rev Time 0.00
Received By dbattles Date 2019-08-22 Time 09:49 Sent To  
Notes
2019-08-08 16:26:37OK - ARCHITECTURAL AND STRUCTURAL SHEETS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-06-06 Cont ID  
Sent By shill Date 2019-06-06 Time 15:39 Rev Time 0.00
Received By shill Date 2019-06-06 Time 15:36 Sent To  
Notes
2019-06-06 15:39:11SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 NEW PAGES SUBMITTED NEXT REVIEW CYCLE REQUIRE
 VERIFICATION.
  
  
2019-06-04 10:09:48MECH PLANS OK

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-04-30 Cont ID  
Sent By shill Date 2019-04-30 Time 09:26 Rev Time 0.00
Received By shill Date 2019-04-30 Time 09:26 Sent To  
Notes
2019-04-30 09:27:07SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISED 5/1: THE CIVIL PAGES ARE SIGNED (TODD
 MCLEOD, PE), BUT THE LANGUAGE REQUIRED BY
 FAC61G15-23.004 IS NOT INCLUDED ON THE SIGNATURE OR
 PLAN. TITLE BLOCK **INCLUDES** CERTIFICATE OF
 AUTHORIZATION (30535). PLEASE RESUBMIT ONLY PAGES WHICH
 CHANGE DUE TO CODE RELATED COMMENTS, BUT ADDRESS FOR
 ANY PLANS SUBMITTED IN THE FUTURE.
  
 2. FMEP ENGINEER COMPANY HAS A CERTIFICATE OF
 AUTHORIZATION THAT IS DELINQUENT AS OF 2/28/19. THE
 NUMBER IS REQUIRED TO BE INCLUDED IN THE TITLE BLOCK,
 FS471. PLEASE ADDRESS, BUT RESUBMIT ONLY PAGES WHICH
 CHANGE DUE TO CODE RELATED COMMENTS.
  
 3. SURVEY IS NOT DIGITALLY SIGNED (LOCATED IN DRAWINGS,
 SHEET A.SI). IF SURVEYOR (JAVIER DE LA ROCHA) DOES NOT
 HAVE A DIGITAL SIGNATURE, A PAPER ORIGINAL WILL BE
 REQUIRED TO BE SUBMITTED TO THE BUILDING DIVISION AFTER
 ALL REVIEWS HAVE PASSED.
  
 4. OTHER PAGES/DOCUMENTS OK, BUT NEW PAGES SUBMITTED
 NEXT REVIEW CYCLE REQUIRE VERIFICATION.
  
  
2019-04-23 14:29:05ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-01-07 Cont ID  
Sent By jpearson Date 2019-01-07 Time 17:21 Rev Time 0.00
Received By jpearson Date 2019-01-07 Time 17:21 Sent To  
Notes
2019-01-07 17:21:11EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. PROVIDE CORRECTION FOR SHEETS AS.1
 AND A5.06. WPB FBC 107.1; FS 471/481

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2019-08-08 Cont ID  
Sent By dbattles Date 2019-08-08 Time 16:18 Rev Time 0.00
Received By dbattles Date 2019-08-08 Time 16:18 Sent To  
Notes
2019-08-08 16:25:31THRESHOLD AGREEMENT APPROVED.
  
 PROVISO:
 PLEASE PROVIDE 3 ORIGINAL COPIES TO DEVELOPMENT
 SERVICES OFFICE.
 401 CLEMATIS STREET (1ST FLOOR)
 PLEASE GIVE TO THE COUNTER WITH SUBMITTAL FORM
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
  

Review Stop Z ZONING
Rev No 6 Status P Date 2019-08-19 Cont ID  
Sent By elevesqu Date 2019-08-19 Time 10:50 Rev Time 0.00
Received By elevesqu Date 2019-08-19 Time 10:50 Sent To  
Notes
2019-08-19 10:50:53THE FOLLOWING ITEMS SHALL BE ADDRESSED WITHIN 30 DAYS
 AND NEW PLANS SHALL BE UPLOADED:
 1. PLEASE SUBMIT A PHOTOMETRIC PLAN FOR THE SITE
 INCLUDING INTERIOR AND ROW LIGHTING AND PROVIDE LIGHT
 POLE DETAIL. ANY FEES ASSOCIATED WITH THE REMOVAL OF
 EXISTING STREET LIGHTS SHALL BE A COST TO THE OWNER.
 2. THE APPLICANT SHALL MOVE THE DUMPSTER ENCLOSURE OUT
 OF THE SIGHT TRIANGLE LINE AND SHALL BUILD THE
 ENCLOSURE TO MEET CITY REQUIREMENTS.
 3. THE PROJECT IS REQUIRED TO COMPLY WITH THE ART IN
 PUBLIC PLACES ORDINANCE.
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED PRIOR TO
 ISSUANCE OF FINAL CO:
 1. PROPERTIES SHALL BE REPLATTED AND UNIFIED PRIOR TO
 ISSUANCE OF FINAL CO. A SIDEWALK EASEMENT IS REQUIRED
 ALONG ROSEMARY AVENUE.
 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 3. THE APPLICANT SHALL COORDINATE WITH THE ZONING
 DEPARTMENT ON THE PLACEMENT OF ABOVE GROUND UTILITIES
 INCLUDING BACKFLOW PREVENTERS, TRANSFORMERS, AND FIRE
 DEPARTMENT CONNECTIONS OUTSIDE OF THE MINIMUM SETBACK
 AREA AND SHALL LANDSCAPE THE UTILITIES FROM THE ROW.
 4. PAVEMENT SHALL BE RESURFACED IN ACCORDANCE WITH CITY
 STANDARDS TO ANY AREA WHERE PAVEMENT MARKINGS ARE
 REMOVED.
 5. THE APPLICANT SHALL COORDINATE WITH THE CITY ON THE
 FINAL CROSS SECTION OF ROSEMARY AVENUE AND CONSIDER
 ELIMINATION OF THE ROSEMARY AVENUE ON-STREET PARKING.
  
 PROVISOS:
 1. ALL CURB CUTS AND STREET CORNERS WITHIN THE PROJECT
 SITE SHALL BE DESIGNED TO MEET ADA COMPLIANT CROSSINGS.
 2. THE APPLICANT SHALL CONTINUE TO COORDINATE WITH THE
 CRA AND CITY ON 8TH STREET AND THE HEART AND SOUL PARK
 FOR A COHESIVE DESIGN.
 3. THE PROJECT IS REQUIRED TO COMPLY WITH THE ART IN
 PUBLIC PLACES ORDINANCE.
 4. THE LANDSCAPE AND IRRIGATION WERE NOT APPROVED
 THROUGH THIS PERMIT. A SEPARATE LANDSCAPE AND
 IRRIGATION PERMIT IS REQUIRED.
 5. THE WALL AND ALL SIGNAGE WERE NOT APPROVED THROUGH
 THIS PERMIT. SEPARATE PERMITS ARE REQUIRED.
 6. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION ADJACENT TO THE
 DEVELOPMENT. THIS WILL BE THROUGH A SEPARATE
 MAINTENANCE AGREEMENT WITH THE CITY
 7. IRRIGATION FOR STREET TREES AND LANDSCAPING IN THE
 RIGHT OF WAYS SHALL BE PROVIDED BY THE APPLICANT,
 SUCCESSORS AND ASSIGNS FROM THE SUBJECT DEVELOPMENT.
 ALL EXISTING CITY IRRIGATION LINES RUNNING TO
 INDIVIDUAL AREAS OR TREES SHALL BE REMOVED AND CAPPED
 IN SUCH A WAY TO ENSURE CITY IRRIGATION SUPPLY LINES
 SHALL REMAIN INTACT AND CONTINUOUS FOR OTHER AREAS
 SERVED BY THE LINES
 8. ALL ROOF-MOUNTED EQUIPMENT SHALL BE SCREENED FROM
 THE ROW AT THE HEIGHT OF THE EQUIPMENT.
 9. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION
  

Review Stop Z ZONING
Rev No 5 Status F Date 2019-08-16 Cont ID  
Sent By elevesqu Date 2019-08-16 Time 08:46 Rev Time 0.00
Received By elevesqu Date 2019-08-16 Time 08:46 Sent To  
Notes
2019-08-16 08:46:30SITE PLANS MATCHING SITE PLAN APPROVAL TO BE UPLOADED
 WITH RESUBMITTAL
  
 LIZ LEVESQUE, URBAN DESING PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 4 Status F Date 2019-06-06 Cont ID  
Sent By elevesqu Date 2019-06-06 Time 16:05 Rev Time 0.00
Received By elevesqu Date 2019-06-06 Time 16:05 Sent To  
Notes
2019-06-06 16:05:27COMMENT FROM ZONING REVIEW STOP 2 NOT ADDRESSED:
  
 PLEASE SEE SITE PLAN COMMENTS FROM Z18050030 2ND REVIEW
 STOP. PLEASE ADDRESS SITE PLAN COMMENTS PRIOR TO
 RESUBMITTING BUILDING PERMIT.
  
 SITE PLAN APPROVAL REQUIRED PRIOR TO BUILDING PERMIT
 APPROVAL.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 3 Status F Date 2019-04-04 Cont ID  
Sent By elevesqu Date 2019-04-04 Time 11:26 Rev Time 0.00
Received By elevesqu Date 2019-04-04 Time 11:26 Sent To  
Notes
2019-04-04 11:26:42COMMENT FROM ZONING REVIEW STOP 2 NOT ADDRESSED:
  
 PLEASE SEE SITE PLAN COMMENTS FROM Z18050030 2ND REVIEW
 STOP. PLEASE ADDRESS SITE PLAN COMMENTS PRIOR TO
 RESUBMITTING BUILDING PERMIT.
  
 SITE PLAN APPROVAL REQUIRED PRIOR TO BUILDING PERMIT
 APPROVAL.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 2 Status F Date 2019-02-22 Cont ID  
Sent By elevesqu Date 2019-02-22 Time 14:53 Rev Time 0.00
Received By elevesqu Date 2019-02-22 Time 14:53 Sent To  
Notes
2019-02-22 14:53:16PLEASE SEE SITE PLAN COMMENTS FROM Z18050030 2ND REVIEW
 STOP. PLEASE ADDRESS SITE PLAN COMMENTS PRIOR TO
 RESUBMITTING BUILDING PERMIT.
  
 SITE PLAN APPROVAL REQUIRED PRIOR TO BUILDING PERMIT
 APPROVAL.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 1 Status F Date 2019-01-16 Cont ID  
Sent By elevesqu Date 2019-01-16 Time 12:20 Rev Time 0.00
Received By elevesqu Date 2019-01-16 Time 12:18 Sent To  
Notes
2019-01-16 12:20:14THE REFERENCED NUMBERED COMMENTS ARE FROM THE FIRST
 SUBMITTAL OF SITE PLAN REVIEW, AND INDICATE WHETHER
 THESE COMMENTS HAVE BEEN ADDRESSED ON THE PLANS
 SUBMITTED FOR BUILDING PERMIT. NEW COMMENTS HAVE BEEN
 INCLUDED AT THE END OF THE PREVIOUS COMMENTS.
  
 1. SATISFIED. PLEASE CONSIDER OPEN AIR STRUCTURES UNDER
 THE HALLWAY AND AREAS CONNECTING TO THE EXISTING
 STRUCTURE ON THE ROOFTOP TERRACE LEVEL TO MEET THE
 DISTRICT HEIGHT REQUIREMENTS.
 2. SATISFIED. PLEASE PROVIDE MORE DETAIL AND HEIGHT OF
 THE STRUCTURES ON THE ROOFTOP TERRACE.
 3. PARTIALLY SATISFIED. CONSIDER THE USE OF PERMEABLE
 SURFACE, ESPECIALLY IN THE PROPOSED SURFACE PARKING
 LOT.
 PLEASE INDICATE LOCATION OF PERMEABLE SURFACE ON SITE
 PLAN.
 4. SATISFIED. THE COLORED RENDERING AND THE PROPOSED
 ELEVATIONS DO NOT APPEAR TO MATCH. PLEASE REVISE
 ACCORDINGLY.
 5. SATISFIED. PLEASE NOTE, PER TABLE IV-38, THE CORRECT
 STREET DESIGNATIONS AND SETBACKS ARE AS FOLLOWS:
 A. FRONT (8TH STREET): RESIDENTIAL- 17'
 B. SIDE (9TH STREET): RESIDENTIAL - 17'
 C. SIDE (HENRIETTA AVE): RESIDENTIAL- 17'
 D. SIDE (ROSEMARY AVE): SECONDARY - 12'
 6. SATISFIED. PLEASE CORRECT THE SITE DATA TABLE, AND
 INCLUDE THE SETBACK DIMENSIONS OF THE PROPOSED ADDITION
 AND PARKING LOTS ON THE SITE PLAN (SHEET A0.04, SHEET
 A1.00).
 7. SATISFIED. PLEASE SHOW EXISTING CURBS AND
 CENTERLINES OF ALL ROADWAYS AND INDICATE WHERE THE
 CURBS WILL BE MODIFIED.
 8. SATISFIED. PLEASE NOTE, IN THE DOWNTOWN MASTER PLAN
 AREA, SETBACKS ARE MEASURED FROM BACK OF CURB, AS
 DEFINED IN SECTION 94-109. WHERE THE CURB LOCATION
 VARIES ALONG A PROPERTY, THE BACK OF CURB SHALL BE
 DEFINED AS THE PREDOMINANT BACK OF CURB LINE FURTHEST
 FROM THE CENTER LINE OF THE ROAD (CURB LOCATION ALONG
 50% OF STREET FRONTAGE). PLEASE AMEND THE SETBACK
 MEASUREMENTS AS NECESSARY.
 9. SATISFIED. PLEASE NOTE, THE MINIMUM REQUIRED
 LANDSCAPE BUFFER FOR PARKING CANNOT BE INCLUDED AS PART
 OF THE REQUIRED SETBACK. PLEASE REVISE ACCORDINGLY.
 10. NOT SATISFIED. PLEASE NOTE, THE MAXIMUM BUILDING
 FOOTPRINT FOR GROUND LEVEL IS 87% AND FOR THE PODIUM IS
 90%. PLEASE PROVIDE DETAIL IN THE TABLE ON THE PERCENT
 BUILDING FOOTPRINT FOR EACH PROPOSED NEW LEVEL. PLEASE
 AMEND THE LABEL FROM "LOT COVERAGE" TO "BUILDING
 FOOTPRINT."
 11. NOT SATISFIED. PARKING CALCULATIONS IS BASED ON NET
 INTERIOR AREA, NOT GROSS AREA. PLEASE INCLUDE THE NET
 INTERIOR AREA AND CALCULATE ACCORDINGLY. PLEASE BREAK
 DOWN THE TABLE INTO REQUIRED AND PROVIDED PARKING.
 12. PARTIALLY SATISFIED. PLEASE SUBMIT AN ILLUSTRATION
 AND TABLE OF THE F.A.R. BREAKDOWN BY EACH SEPARATE
 FLOOR, INCLUDING THE ADDITIONAL PARKING. PLEASE
 SEPARATE THE SQUARE FOOTAGE BY ALLEY, NORTH PROPERTY
 AND SOUTH PROPERTY. PER SECTION 94-79 (HISTORIC
 RESIDENTIAL DESIGN STANDARDS), FAR INCLUDES INTERIOR
 AND ROOFED EXTERIOR STAIRWAYS, ELEVATORS, ESCALATORS
 AND SIMILAR FEATURES. PLEASE REVISE ACCORDINGLY.
 13. NOT SATISFIED. THE APPLICANT SHALL SUBMIT A
 SEPARATE ALLEY ABANDONMENT APPLICATION.
 14. ONGOING. PLEASE NOTE, THE PROPERTIES WILL NEED TO
 BE UNIFIED.
 15. ONGOING. PLEASE NOTE, THIS SITE WILL BE REQUIRED TO
 BE REPLATTED.
 16. SATISFIED. PLEASE INCLUDE ILLUSTRATIONS AND A DATA
 TABLE DEMONSTRATING COMPLIANCE WITH THE ACTIVE USE
 REQUIREMENTS FOR NWD-2, AS REQUIRED BY TABLE IV-38.
 PLEASE NOTE, THE STREET DESIGNATIONS ARE AS FOLLOWS:
 A. 8TH AVENUE: RESIDENTIAL
 B. HENRIETTA AVENUE: RESIDENTIAL
 C. ROSEMARY AVENUE: SECONDARY
 D. 9TH STREET: RESIDENTIAL
 17. SATISFIED. PLEASE INCLUDE ILLUSTRATIONS AND A DATA
 TABLE DEMONSTRATING COMPLIANCE WITH THE TRANSPARENCY
 REQUIREMENTS FOR THE GROUND FLOOR IN NWD-2, AS REQUIRED
 BY TABLE IV-38. PLEASE NOTE, THE STREET DESIGNATIONS
 ARE AS FOLLOWS:
 A. 8TH AVENUE: RESIDENTIAL
 B. HENRIETTA AVENUE: RESIDENTIAL
 C. ROSEMARY AVENUE: SECONDARY
 D. 9TH STREET: RESIDENTIAL
 18. NOT SATISFIED. THE PROPOSED AISLE WIDTHS IN SOME
 SECTIONS OF THE PROPOSED PARKING AREAS APPEAR TO BE TOO
 SMALL. PLEASE LOOK AT SECTION 94-485, FIGURE XV-2 AND
 REVISE ACCORDINGLY.
 THE SIZE OF THE TERMINAL ISLAND CAN BE REDUCED TO 5
 FEET WITH A MINIMUM RADIUS OF TWO AND ONE-HALF FEET AT
 ITS END TO MEET THIS REQUIREMENT.
 19. SATISFIED. THE PROPOSED NUMBER OF ADA PARKING
 SPACES DOES NOT MEET THE REQUIREMENT AS ESTABLISHED BY
 SECTION 94-485, TABLE XV-3. PLEASE REVISE.
 20. SATISFIED. IF PROPOSED ADA PARKING SPACES ARE
 DIAGONAL, THE REQUIRED LENGTH IS 18' AND WIDTH IS 12',
 PER SECTION 94-485 (O)(2). THE PROPOSED DIAGONAL
 PARKING SPACE AREA TO THE EAST OF THE BUILDING ADDITION
 DOES NOT WORK WITH REQUIRED PARKING DEPTHS AND DRIVE
 AISLE WIDTHS. PLEASE CONSIDER ALTERNATIVES.
 21. NOT SATISFIED. THE NUMBER OF ON STREET PARKING
 ALONG HENRIETTA AVENUE IS LABELED AS 5 SPACES BUT THERE
 APPEAR TO ONLY BE 4 SPACES. PLEASE CONFIRM LABELS AND
 TOTAL NUMBERS IN THE SITE DATA TABLE.
 THE NUMBER OF SPACES IS LABELED AS "3" BUT THERE APPEAR
 TO BE 4 SPACES.
 22. PARTIALLY SATISFIED. THE EXISTING ON SITE POWER
 POLES APPEAR TO CREATE PROBLEMS WITH PROPOSED
 SIDEWALKS, ON STREET PARKING AND PROPOSED STREET TREES.
 PLEASE PROVIDE THE LOCATION OF EXISTING POLES, AND
 PROVIDE DETAIL OF POLES BEING REMOVED OR NEWLY PROPOSED
 POLES. PLEASE CONTACT STAFF TO HOLD A SEPARATE MEETING
 TO DISCUSS THE MULTIPLE ISSUES.
 THE EXISTING POWER POLES ALONG ROSEMARY AVENUE CREATE
 AN ACCESSIBILITY ISSUES IN SOME LOCATIONS. THE SIDEWALK
 NEEDS TO BE ADJUSTED AND EXPANDED AT THESE AREAS TO
 AVOID ISSUES. THIS IS SHOWN ON SOME PLANS, HOWEVER THE
 SITE PLAN NEEDS TO SHOW THIS AS WELL.
 23. SATISFIED. THE PROPOSED BUS PARKING DOES NOT WORK
 WITH TURNING RADIUS REQUIREMENTS. PLEASE CONSIDER A BUS
 PULL-OFF OR OTHER ALTERNATIVE.
 24. NOT SATISFIED. THE REQUIRED BICYCLE PARKING FOR
 COMMERCIAL DEVELOPMENTS IS 1 PER 15 REQUIRED PARKING
 SPACES WITHIN A SECURED STORAGE AREA. THE REQUIREMENT
 FOR PUBLIC USE IS ONE SPACE PER EVERY 100 FEET OF
 STREET FRONTAGE. PLEASE INCLUDE THE DIMENSIONS OF THE
 STREET FRONTAGES AND DEMONSTRATE COMPLIANCE OF THE
 SEPARATE BICYCLE PARKING REQUIREMENTS IN THE SITE DATA
 TABLE. THE BICYCLE PARKING NUMBER IN THE SITE DATA
 TABLE DOES NOT APPEAR TO MATCH WHAT IS ON THE SITE
 PLAN. PLEASE UPDATE WITH RESUBMITTAL MEETING THE CITY
 REQUIREMENTS.
 25. SATISFIED. PLEASE REVISE FROM WALL-MOUNTED BIKE
 RACKS TO GROUND MOUNTED BIKE RACKS ALONG THE NORTH SIDE
 OF THE BUILDING.
 26. NOT SATISFIED. PLEASE INCLUDE BICYCLE RACK DETAIL,
 MEETING CITY STANDARDS. STAFF WILL PROVIDE DETAIL.
 PLEASE SHOW EXACT LOCATION OF PROPOSED BICYCLE RACKS
 AND DIMENSIONS ON THE SITE PLAN.
 27. NOT SATISFIED. PLEASE PROVIDE ADDITIONAL
 FENESTRATION ALONG THE NORTH FACADE OF THE PROPOSED NEW
 ADDITION, AS IT IS FACING THE PRIMARY PARKING LOT FOR
 THE BUILDING USE. BLANK WALLS CANNOT BE VISIBLE BY THE
 GENERAL PUBLIC. BLANK WALL MEANS ANY PORTION OF A
 FA?ADE THAT HAS AN AREA GREATER THAN 20 PERCENT OF THE
 ENTIRE FA?ADE ELEVATION THAT IS ABSENT OF FENESTRATION
 AND IS ABSENT OF A PLANAR BREAK OF AT LEAST TWO FEET IN
 DEPTH. PLEASE ILLUSTRATE COMPLIANCE WITH BLANK WALL
 REGULATIONS.
 28. NOT SATISFIED. PER SECTION 94-109, TABLE IV-4, ON
 FACADES ENCLOSING ACTIVE USES (E.G., THE KITCHEN,
 BATHROOMS), FENESTRATION MUST COVER A MINIMUM OF 15% OF
 THE FACADE AREA. PLEASE PROVIDE ADDITIONAL FENESTRATION
 ALONG THE EAST FACADE OF THE PROPOSED BUILDING
 ADDITION.
 29. NOT SATISFIED. PER SECTION 94-109, TABLE IV-4, ON
 FACADES ENCLOSING NON-ACTIVE USES, ARCHITECTURAL
 TREATMENT SHALL BE PROVIDED. SEE SECTION 94-109,
 DEFINITIONS AND MINIMUM REQUIREMENTS FOR ARCHITECTURAL
 TREATMENT REQUIREMENTS, SPECIFICALLY FOR THE EAST
 FACADE OF THE PROPOSED ADDITION. PLEASE ADD MORE
 ARCHITECTURAL TREATMENT TO THE PROPOSED ADDITION.
 30. NOT SATISFIED. PER SECTION 94-109, TABLE IV-4, AT
 THE GROUND FLOOR, HORIZONTAL PROJECTIONS WITH A MINIMUM
 CUMULATIVE HORIZONTAL LENGTH OF 50% OF THE BUILDING
 FRONTAGE SHALL BE PROVIDED. IT APPEARS THAT THE
 FRONTAGES, ESPECIALLY THE NORTH AND EAST ELEVATION MAY
 NOT MEET THIS REQUIREMENT. PLEASE REVISE AND PROVIDE
 ILLUSTRATIONS SHOWING THE LENGTH OF HORIZONTAL
 PROJECTIONS ALONG THE GROUND FLOOR FRONTAGES TO SATISFY
 THIS REQUIREMENT.
 31. NOT SATISFIED. PLEASE PROVIDE DIMENSIONS AND DETAIL
 OF PROPOSED AWNINGS AND CANOPIES. SEE TABLE IV-5:
 PROJECTION STANDARDS FOR REGULATIONS.
 32. NOT SATISFIED. PLEASE SEE SECTION 94-110(D) FOR
 SIGNAGE REQUIREMENTS FOR COMMERCIAL AND MIXED-USES
 WITHIN RESIDENTIAL ENCLAVE PLANNING AREAS. PLEASE
 PROVIDE DETAIL OF ANY NEWLY PROPOSED SIGNS, AND ADD A
 NOTE SAYING "SIGNAGE WILL BE REVIEWED SEPARATELY AT
 TIME OF SIGN PERMITTING" TO THE PLANS.
 33. PARTIALLY SATISFIED. PLEASE INCLUDE A SEPARATE OPEN
 SPACE PLAN AND TABLE MEETING THE REQUIREMENTS OF
 SECTION 94-109 TABLE IV-6 AND TABLE IV-7. PLEASE NOTE,
 REQUIRED LANDSCAPE BUFFERS CANNOT BE INCLUDED IN OPEN
 SPACE CALCULATIONS.
 PRIVATE OPEN SPACE IS LESS THAN WHAT IS REQUIRED. IN
 THIS CASE, AS THERE IS NO PUBLIC SPACE REQUIREMENT, THE
 PLAZA CAN BE COUNTED. ADDITIONALLY, PER SECTION
 94-112(B)(1)(C)(3), PROPOSED DEVELOPMENTS WHICH VACATE
 AN ENTIRE ALLEY WITHIN A BLOCK SHALL PROVIDE AN OPEN
 SPACE EQUAL TO THE SIZE OF THE VACATED ALLEY AT A RATIO
 OF 1:1 IN ADDITION TO THE MINIMUM OPEN SPACE
 REQUIREMENT. CONSIDERING THE CREATION OF THE HEART AND
 SOUL PARK, STAFF CAN PRESENT THE PARK AS CONSIDERATION
 FOR THIS REQUIREMENT. PLEASE ILLUSTRATE INTENT OF THIS
 ON THE OPEN SPACE PLAN WITH INDICATED SQUARE FOOTAGE OF
 THE ALLEY.
 34. SATISFIED. PLEASE CONSIDER AN OPEN SPACE
 AMENITY/SEATING AREA IN THE REAR OF THE BUILDING FOR
 KITCHEN STAFF/EMPLOYEES, WHICH COULD THEN BE CONSIDERED
 IN THE OPEN SPACE CALCULATIONS.
 35. PARTIALLY SATISFIED. PLEASE INCLUDE PLANTING ON THE
 ROOFTOP TERRACE TO PROVIDE A ROOFTOP GARDEN AREA.
 PLEASE INCLUDE DETAIL OF PROPOSAL AND AMENITIES.
 PLEASE INCLUDE DETAIL OF ROOFTOP AMENITIES ON HARDSCAPE
 PLAN.
 36. NOT SATISFIED. PER SECTION 94-113(E), CURBS AND
 WHEEL STOPS, ALL LANDSCAPED AREAS AND PLANT MATERIALS
 WITHIN OR ADJACENT TO VEHICULAR USE AREAS SHALL BE
 PROTECTED FROM VEHICULAR ENCROACHMENT BY WHEEL STOPS,
 CURBS, OR OTHER SIMILAR DEVICES. PLEASE DEMONSTRATE
 COMPLIANCE.
 PLEASE USE A D-CURB INSTEAD OF WHEEL STOPS FOR
 LANDSCAPE PROTECTION.
 37. NOT SATISFIED. PER SECTION 94-113(D), STREET
 LIGHTS, STREET LIGHTING SHALL BE PROVIDED TO ATTAIN THE
 APPROPRIATE FOOTCANDLE MEASUREMENT NECESSARY FOR SAFE
 PEDESTRIAN AND VEHICULAR MOVEMENT. LIGHT FIXTURE AND
 POLES SHALL MEET THE CITY APPROVED STANDARD. PLEASE
 PROVIDE LOCATION AND DETAIL OF LIGHT FIXTURES.
 PLEASE SUBMIT PHOTOMETRIC PLANS AND LIGHT FIXTURE
 DETAILS.
 38. SATISFIED. PER SECTION 94-113(D), SIDEWALKS, A
 SIDEWALK WITH A MINIMUM OF EIGHT FEET CLEAR WIDTH SHALL
 BE PROVIDED ALONG THE BUILDING FRONTAGE. PLEASE REVISE
 ACCORDINGLY.
 39. SATISFIED. PER SECTION 94-113(F), SURFACE PARKING
 LOTS SHALL MEET THE MINIMUM GROUND FLOOR SETBACK
 REQUIREMENTS AS PROVIDED IN THE SUBDISTRICT BUILDING
 REQUIREMENTS TABLE. A FIVE-FOOT LANDSCAPE BUFFER SHALL
 BE PROVIDED AROUND THE ENTIRE PERIMETER OF THE SURFACE
 LOT IN ADDITION TO THE GROUND FLOOR SETBACK TO VISUALLY
 SCREEN PARKING AREAS.
 40. ONGOING. PARKING SHALL COMPLY WITH SECTION
 94-113(F) FOR LANDSCAPING REQUIREMENTS.
 LANDSCAPE REQUIREMENTS SHALL BE REVIEWED THROUGH
 SEPARATE LANDSCAPE PERMIT. SEE NEW COMMENT #45.
 41. PARTIALLY SATISFIED. PLEASE INCLUDE DETAIL AND
 DIMENSIONS OF THE PROPOSED DUMPSTER ENCLOSURE AREA,
 MEETING THE REGULATIONS OF SECTION 94-315.
 PLEASE INCLUDE DETAIL OF TRASH RECEPTACLE ENCLOSURE,
 INCLUDING MATERIAL AND HEIGHT, MEETING THE
 SPECIFICATIONS OF SECTION 94-315(A).
 42. SATISFIED. CAN VISITORS ENTER THROUGH THE BACK OF
 THE BUILDING? PLEASE PROVIDE DETAIL INTO BUILDING
 ENTRANCES FROM EIGHTH STREET AND FROM THE PARKING LOT.
 PLEASE CONSIDER PEDESTRIAN CONNECTIVITY INCLUDING
 CROSSWALKS, AND DISTINGUISHED PRIMARY ENTRANCES.
 43. SATISFIED. PLEASE CLEAN UP LABELS ON THE PLAN THAT
 ARE REMAINING FROM THE FIRST SUBMITTAL OR OTHERWISE
 MISPLACED.
 44. SATISFIED. PLEASE REMOVE THE LABEL READING
 "PROPOSED 3RD FLOOR-PLAN" FROM SHEET A1.03 AND RELABEL
 AS "PROPOSED ROOFTOP TERRACE" OR SOMETHING SIMILAR.
  
 NEW COMMENTS JANUARY 16, 2019
 45. PLEASE NOTE, A SEPARATE LANDSCAPE PLAN WILL BE
 REQUIRED.
 46. PLEASE NOTE, A SEPARATE FENCE PERMIT WILL BE
 REQUIRED FOR THE PROPOSED METAL FENCE. IN THIS
 DISTRICT, FENCES SHALL BE A MAXIMUM HEIGHT OF FOUR
 FEET. PLEASE REVISE HEIGHT ON PLANS.
 47. THE LANDSCAPE AND HARDSCAPE PLANS DO NOT MATCH THE
 NEW BUILDING FOOTPRINT AND ON STREET PARKING SPACE
 LAYOUT AND HAVE DISCREPANCIES IN PROPOSED LANDSCAPING.
 PLEASE ADJUST ACCORDINGLY.
 48. PLEASE INCLUDE A TREE REMOVAL/RELOCATION PLAN WITH
 RESUBMITTAL.
 49. ARE GATES PROPOSED TO ACCESS THE PARKING LOT?
 PLEASE NOTE, A QUEUING DISTANCE OF AT LEAST 20 FEET IS
 REQUIRED PER SECTION 94-111(P).
 50. PLEASE SHOW ANY ABOVE GROUND UTILITIES,
 TRANSFORMERS, BACKFLOW PREVENTERS, ETC. ON THE SITE
 PLAN. THESE SHALL NOT BE LOCATED WITHIN THE MINIMUM
 SETBACK.
 51. PLEASE ENLARGE THE INTERNAL SIDEWALK WITHIN THE
 PLAZA THAT LEADS FROM THE ADA PARKING TO THE 8TH STREET
 ENTRANCE TO ALLOW FOR BETTER PEDESTRIAN ACCESS.
 52. PLEASE ADD SIDEWALK AND SETBACK DIMENSIONS ON THE
 HARDSCAPE PLAN SHEET HP-1.
 53. THE PROPOSED LOCATION OF THE WALL/FENCE ON THE
 HARDSCAPE PLAN DOES NOT MATCH THE PROPOSED LOCATION ON
 THE LANDSCAPE PLAN. PLEASE CLARIFY AND REVISE
 ACCORDINGLY.
 54. THIS PROJECT HAS NOT RECEIVED SITE PLAN APPROVAL.
 PLEASE SUBMIT FOR SITE PLAN APPROVAL BEFORE BUILDING
 PERMIT CAN BE REVIEWED FURTHER.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  
  