Plan Review Details - Permit 18101364
Plan Review Stops For Permit 18101364
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By pvalenti Date 2018-12-18 Time 13:44 Rev Time 0.00
Received By pvalenti Date 2018-12-18 Time 13:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-14 Cont ID  
Sent By pvalenti Date 2018-11-14 Time 14:44 Rev Time 0.00
Received By pvalenti Date 2018-11-14 Time 14:44 Sent To  
Notes
2018-11-14 14:45:38PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED PV
  
 DEMO ONLY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-11 Cont ID  
Sent By jpearson Date 2018-12-11 Time 10:01 Rev Time 0.00
Received By jpearson Date 2018-12-11 Time 10:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By jpearson Date 2018-11-07 Time 08:47 Rev Time 0.00
Received By jpearson Date 2018-11-07 Time 08:47 Sent To  
Notes
2018-11-07 08:47:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL
 PERMIT APPLICATION TO [email protected] AND CC
 [email protected] AND [email protected] SO WE RECEIVE IT
 ALSO. WHEN THIS EMAIL IS RECEIVED ONE OF THE REVIEWERS
 WILL APPROVE THE PLAN REVIEW. THE ORIGINAL PERMIT
 APPLICATION MUST BE SUBMITTED WHEN THE PERMIT IS PICKED
 UP. WPB FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-12-17 Cont ID  
Sent By pleduc Date 2018-12-17 Time   Rev Time 0.00
Received By pleduc Date 2018-12-17 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-11-02 Cont ID  
Sent By pleduc Date 2018-11-02 Time   Rev Time 0.00
Received By pleduc Date 2018-11-01 Time 12:10 Sent To  
Notes
2018-11-02 09:43:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET G 004 - UNDER SECTION210000 FIRE SUPRRESSION
 THERE IS AN INDICATING TO REFER TO BUILDING FIRE
 PROTECTION DRAWINGS.
  
 THERE ARE NO FIRE PROTECTION DRAWINGS SUBMITTED.
  
 PLEASE REVIEW, CORRECT OR CLARIFY.
  
  
  
  
 2) SHEET LS 101 - THERE ARE SHADED INDICATIONS THAT THE
 KITCHEN AREA IS NOT IN THE SCOPE OF WORK. HOWEVER,
 SHEET ID 109 CLEARLY SHOWS WORK IN THE KITCHEN AREA.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) THERE ARE NO INDCATIONS OF COMPLIANCE WITH THE
 CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE OR
 OTHER CURRENT EDITIONS OF APPLICABLE CODES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE
  
  
  
 4) THE FIRE ALARM AND FIRE SPRINKLERS SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT THE CONSTRUCTION PERIOD.
  
 ALL WORK ON THE FA AND FS SHALL BE DONE UNDER SEPRATE
 SHOP DRAWING PERMITS BY CERTIFIED CONTRACTORS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE
 NOTE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-20 Cont ID  
Sent By lmarchan Date 2018-12-20 Time 08:01 Rev Time 0.00
Received By lmarchan Date 2018-12-10 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-26 Cont ID  
Sent By cpuell Date 2018-11-26 Time 12:11 Rev Time 0.00
Received By cpuell Date 2018-10-31 Time 11:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-20 Cont ID  
Sent By tklarge Date 2018-12-20 Time 03:35 Rev Time 0.00
Received By tklarge Date 2018-12-20 Time 03:09 Sent To  
Notes
2018-12-20 03:32:561) THE FLOOR PLAN LAYOUT ON SHT. LS-101 DOES NOT MATCH
 THE FLOOR PLAN LAYOUT ON SHT. ID-101. ALTHOUGH THE
 SHADED AREA IS NOT IN THE SCOPE OF WORK, THE
 CONFIGURATION/LAYOUT OF TENANT SPACE #2 ON SHEET ID-101
 SHOWS PARTITIONS, CORRIDORS, DOORS AND WHAT APPEARS TO
 BE SINK YET SHEET LS-101 SHOWS NONE OF THIS. CLARIFY.
 2ND REQUEST.
 2) THE PLANS SHALL BEAR THE DIGITAL SIGNATURE AND SEAL
 OF THE DESIGN PROFESSIONAL WHO CREATED THE PLANS. FL.
 ADMIN. CODE RULE 61G1-16.005.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-11-26 Cont ID  
Sent By tklarge Date 2018-11-26 Time 11:05 Rev Time 0.00
Received By tklarge Date 2018-11-26 Time 10:59 Sent To  
Notes
2018-11-26 11:05:171) THE FLOOR PLAN LAYOUT ON SHT. LS-101 DOES NOT MATCH
 THE FLOOR PLAN LAYOUT ON SHT. ID-101. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-11 Cont ID  
Sent By jpearson Date 2018-12-11 Time 10:17 Rev Time 0.00
Received By jpearson Date 2018-12-11 Time 10:17 Sent To  
Notes
2018-12-11 10:17:43PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE. IT APPEARS THERE IS NO THIRD PARTY
 VERIFICATION WITH THE EXISTING SIGNATURES. PROVIDE
 CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By jpearson Date 2018-11-07 Time 08:45 Rev Time 0.00
Received By jpearson Date 2018-11-07 Time 08:45 Sent To  
Notes
2018-11-07 08:45:10PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE. PROVIDE CORRECTION. WPB FBC 107.1;
 FS 471/481