Plan Review Details - Permit 18101210
Plan Review Stops For Permit 18101210
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-02 Cont ID  
Sent By cthroop Date 2019-01-02 Time 17:04 Rev Time 0.00
Received By cthroop Date 2019-01-02 Time 16:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-26 Cont ID  
Sent By cthroop Date 2018-12-26 Time 15:23 Rev Time 0.00
Received By cthroop Date 2018-12-26 Time 12:31 Sent To  
Notes
2018-12-26 15:31:14BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-12-06 Cont ID  
Sent By cmontell Date 2018-11-07 Time 06:11 Rev Time 0.00
Received By cthroop Date 2018-12-06 Time 10:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-01-02 Cont ID  
Sent By cthroop Date 2019-01-02 Time 17:04 Rev Time 0.00
Received By jpearson Date 2019-01-02 Time 08:09 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-12-24 Cont ID  
Sent By jpearson Date 2018-12-24 Time 13:09 Rev Time 0.00
Received By jpearson Date 2018-12-24 Time 13:09 Sent To  
Notes
2018-12-24 13:09:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BE SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. FS 481.229; WPB FBC 107.1, 107.2.1,
 107.3.5.1.2 (PER FLORIDA ADMINISTRATIVE CODE, RULE
 61G15-23.001, THE PROVIDED DOCUMENT IS NOT ACCEPTABLE.
 SEE RULE BELOW.)
  
 61G15-23.001 SIGNATURE, DATE AND SEAL SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN, DATE AND SEAL:
 (A) ALL FINAL PLANS, PRINTS, SPECIFICATIONS, REPORTS,
 OR OTHER DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE
 AND BEING FILED FOR PUBLIC RECORD;
 (B) ALL FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER?S REPRESENTATIVE.
 (2) ADDITIONAL FINAL AND NON-FINAL DOCUMENTS.
 (A) A PROFESSIONAL ENGINEER MAY SIGN, DATE AND SEAL
 DOCUMENTS REQUIRED BY ANY PUBLIC ENTITY OR ANY
 PROVISION OF CONTRACT WHICH REQUIRES THE SIGNING,
 DATING AND SEALING OF ADDITIONAL ORIGINAL DOCUMENTS.
 (B) A PROFESSIONAL ENGINEER SHALL NOT SIGN, DATE AND
 SEAL ANY DOCUMENTS WHICH ARE NOT FINAL DOCUMENTS UNLESS
 THE PROFESSIONAL ENGINEER STATES ANY LIMITATIONS ON THE
 USE OF THOSE DOCUMENTS ON THE FACE OF THOSE DOCUMENTS
 BY USING TERMS SUCH AS ?PRELIMINARY,? ?FOR REVIEW
 ONLY,? ?NOT FOR CONSTRUCTION,? OR ANY OTHER SUITABLE
 STATEMENT WHICH DENOTES THAT THE DOCUMENTS ARE FOR
 LIMITED USE, ARE NOT FINAL AND ARE NOT INTENDED FOR
 PERMIT, CONSTRUCTION, OR BIDDING PURPOSES.
 (3) A PROFESSIONAL ENGINEER MAY ONLY SIGN, DATE AND
 SEAL ENGINEERING PLANS, PRINTS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS IF THAT PROFESSIONAL ENGINEER WAS IN
 RESPONSIBLE CHARGE, AS THAT TERM IS DEFINED IN
 SUBSECTION 61G15-18.011(1), F.A.C., OF THE PREPARATION
 AND PRODUCTION OF THE ENGINEERING DOCUMENT AND THE
 PROFESSIONAL ENGINEER HAS THE EXPERTISE IN THE
 ENGINEERING DISCIPLINE USED IN PRODUCING THE
 ENGINEERING DOCUMENT(S) IN QUESTION. PROFESSIONAL
 ENGINEERS WORKING FOR LOCAL, STATE OR FEDERAL
 GOVERNMENT AGENCIES SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AND SHALL INDICATE THE NAME AND
 ADDRESS OF THE AGENCY ON ALL DOCUMENTS THAT ARE
 REQUIRED TO BE SIGNED, DATED AND SEALED.
 (4) ADDITIONAL REQUIREMENTS FOR PLANS OR PRINTS,
 ENGINEERING SPECIFICATIONS AND CALCULATIONS, AND
 ENGINEERING REPORTS OR OTHER DOCUMENTS. WHEN AN
 ENGINEER SIGNS, DATES AND SEALS ANY OF THE FOLLOWING
 TYPES OF DOCUMENTS PLANS OR PRINTS UNDER THE PROVISIONS
 OF SECTION 471.025, F.S., AND SUBSECTION (1) OF THIS
 RULE, THE FOLLOWING ADDITIONAL INFORMATION MUST BE
 INCLUDED:
 (A) PLANS AND PRINTS. EVERY SHEET WITHIN THE PLANS AND
 PRINTS MUST BE SIGNED, DATED AND SEALED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 1. A TITLE BLOCK SHALL BE USED ON EACH SHEET OF PLANS
 OR PRINTS AND SHALL CONTAIN THE PRINTED NAME, ADDRESS,
 AND LICENSE NUMBER OF THE ENGINEER WHO HAS SIGNED,
 DATED AND SEALED THE PLANS OR PRINTS.
 2. IF THE ENGINEER SIGNING, DATING AND SEALING
 ENGINEERING PLANS OR PRINTS IS PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS; THE TITLE BLOCK
 SHALL CONTAIN THE PRINTED NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS.
 (B) ENGINEERING SPECIFICATIONS AND CALCULATIONS. AN
 INDEX SHEET SHALL BE USED AND SHALL BE SIGNED, DATED
 AND SEALED BY EACH PROFESSIONAL ENGINEER WHO IS IN
 RESPONSIBLE CHARGE OF ANY PORTION OF THE ENGINEERING
 SPECIFICATIONS OR CALCULATIONS.
 1. THE INDEX SHEET MUST BE SIGNED, DATED AND SEALED BY
 THOSE PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF
 THE PRODUCTION AND PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATIONS OR CALCULATIONS, WITH
 SUFFICIENT INFORMATION ON THE INDEX SHEET SO THAT THE
 USER WILL BE AWARE OF EACH PORTION OF THE
 SPECIFICATIONS OR CALCULATIONS FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE.
 2. THE INDEX SHEET SHALL INCLUDE AT A MINIMUM:
 A. THE PRINTED NAME, ADDRESS AND LICENSE NUMBER OF EACH
 ENGINEER IN RESPONSIBLE CHARGE OF THE PRODUCTION OF ANY
 PORTION OF THE CALCULATIONS OR SPECIFICATIONS.
 B. IF THE ENGINEER SIGNING, DATING AND SEALING
 CALCULATIONS OR SPECIFICATIONS IS PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS; THE PRINTED NAME,
 ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS.
 C. IDENTIFICATION OF THE PROJECT, BY ADDRESS OR BY LOT
 NUMBER, BLOCK NUMBER, SECTION OR SUBDIVISION AND CITY
 OR COUNTY.
 D. IDENTIFICATION OF THE APPLICABLE BUILDING CODE AND
 CHAPTER(S) AND FLORIDA FIRE PREVENTION CODE, WHEN
 APPLICABLE, THAT THE DESIGN IS INTENDED TO MEET.
 E. IDENTIFICATION OF ANY COMPUTER PROGRAM USED FOR
 ENGINEERING THE SPECIFICATIONS OR CALCULATIONS.
 (C) ENGINEERING REPORTS OR OTHER DOCUMENTS.
 1. A SIGNATURE PAGE OR COVER LETTER SHALL BE USED AND
 SHALL BE SIGNED, DATED AND SEALED BY EACH PROFESSIONAL
 ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF
 THE REPORT WITH SUFFICIENT INFORMATION PROVIDED SO THAT
 THE USER WILL BE AWARE OF EACH PORTION FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE.
 2. IF THE ENGINEER SIGNING, DATING AND SEALING AN
 ENGINEERING REPORT OR OTHER DOCUMENT IS PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE
 PRINTED NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS SHALL BE PLACED ON
 THE SIGNATURE PAGE OR COVER LETTER.
 (D) THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED AS
 PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, PRINTS,
 SPECIFICATION, REPORTS OR OTHER DOCUMENTS IMMEDIATELY
 ADJACENT TO THE SIGNATURE OF THE PROFESSIONAL ENGINEER.
 RULEMAKING AUTHORITY 471.008, 471.025 FS. LAW
 IMPLEMENTED 471.025, 471.033(1)(A), (E), (J) FS.
 HISTORY?NEW 1-8-80, AMENDED 6-23-80, FORMERLY
 21H-23.01, 21H-23.001, AMENDED 4-1-97, 2-5-04, 8-8-05,
 11-16-09, 2-2-12, 11-3-15, 10-26-16.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By jpearson Date 2018-11-07 Time 11:18 Rev Time 0.00
Received By jpearson Date 2018-11-07 Time 09:12 Sent To  
Notes
2018-11-07 11:18:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BE SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. FS 481.229; WPB FBC 107.1, 107.2.1,
 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-02 Cont ID  
Sent By cthroop Date 2019-01-02 Time 17:04 Rev Time 0.00
Received By cthroop Date 2018-12-28 Time 10:18 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-26 Cont ID  
Sent By cthroop Date 2018-12-26 Time 15:23 Rev Time 0.00
Received By cthroop Date 2018-12-14 Time 14:10 Sent To  
Notes
2018-12-17 14:10:45R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-06 Cont ID  
Sent By cthroop Date 2018-12-06 Time 10:22 Rev Time 0.00
Received By cthroop Date 2018-10-25 Time 15:26 Sent To  
Notes
2018-10-26 15:26:30R09

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-11-07 Cont ID  
Sent By cmontell Date 2018-11-07 Time 06:16 Rev Time 0.00
Received By cmontell Date 2018-11-07 Time 06:13 Sent To  
Notes
2018-11-07 06:15:15PER SCOPE NO MECHANICAL WORK TO BE DONE

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-01-02 Cont ID  
Sent By cthroop Date 2019-01-02 Time 17:04 Rev Time 0.00
Received By cthroop Date 2019-01-02 Time 16:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-26 Cont ID  
Sent By cthroop Date 2018-12-26 Time 15:23 Rev Time 0.00
Received By cthroop Date 2018-12-26 Time 12:31 Sent To  
Notes
2018-12-26 15:32:56PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 08:45 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 08:43 Sent To  
Notes
2018-12-06 08:44:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BE SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. FS 481.229; WPB FBC 107.1, 107.2.1,
 107.3.5.1.2
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
 18101210 9402 BRIDGEPORT RD
  
  
  