Plan Review Details - Permit 18101150
Plan Review Stops For Permit 18101150
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-26 Cont ID  
Sent By jpearson Date 2018-10-26 Time 10:59 Rev Time 0.00
Received By jpearson Date 2018-10-26 Time 10:59 Sent To P
Notes
2018-10-26 10:59:15APPROVED WITH PROVISO: HOUSE PANEL TO COMPLY WITH NEC
 230.71, NOT TO EXCEED 6 MAIN DISCONNECTS FOR SERVICE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-11-07 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-24 Time 16:03 Sent To I
Notes
2018-10-25 16:04:00REVISION ROUTED TO JPEARSON

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-08 Cont ID  
Sent By skennedy Date 2018-11-08 Time 11:11 Rev Time 0.00
Received By skennedy Date 2018-11-08 Time 11:11 Sent To  
Notes
2018-11-08 11:13:181ST REVIEW FBC-2017 MECHANICAL
 PERMIT REVISION #18101150
 11/7/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: APPROVED WITH PROVISO
  
 1) SHEET M1.1 SHOWS A CHANGE IN THE AC SYSTEM FROM A
 1.5 TON TO A 2.0 TON SYSTEM. PLEASE REVISE THE
 EQUIPMENT SCHEDULE SHOWN ON SHEET M2.1.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By ccole Date 2018-11-07 Time 12:54 Rev Time 0.00
Received By ccole Date 2018-11-07 Time 12:54 Sent To  
Notes
2018-11-07 12:57:521ST REVIEW FBC-2017 MECHANICAL
 PERMIT REVISION #18101150
 11/7/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1 SHOWS A CHANGE IN THE AC SYSTEM FROM A
 1.5 TON TO A 2.0 TON SYSTEM. PLEASE REVISE THE
 EQUIPMENT SCHEDULE SHOWN ON SHEET M2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-30 Cont ID  
Sent By gjohnson Date 2018-10-30 Time 09:39 Rev Time 0.00
Received By gjohnson Date 2018-10-30 Time 09:19 Sent To  
Notes
***NONE***