Plan Review Details - Permit 18101134
Plan Review Stops For Permit 18101134
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By dbattles Date 2019-01-14 Time 16:43 Rev Time 0.00
Received By dbattles Date 2019-01-14 Time 14:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By dbattles Date 2018-12-10 Time 15:05 Rev Time 0.00
Received By dbattles Date 2018-12-07 Time 16:17 Sent To  
Notes
2018-12-10 15:05:59****CORRECTIONS****
 W.P.B. PERMIT: 18101134
 REVIEWED: DECEMBER 10, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. COVER SHEET STATES THE USE AS MERCHANTILE.
 [FBC 304] LISTS CARWASH AS BUSINESS GROUP.
 PLEASE BASE OCCUPANCY AND LOAD CALCULATIONS ON
 BUSINESS.
  
 2. SHEET SP-2 SHOWS THREE NEW CONCRETE PADS AT EACH NEW
 DOOR. SHEET A-1 SHOWS PADS ON NEW STORE ONLY. IS THERE
 A PAD AT THE ADA RESTROOM? UPDATE TO MATCH.
 HOW ARE THESE TWO NEW AREAS ACCESIBLE WITH PROPOSED
 STEP FROM LANDINGS OF 5.5 INCHES?
 [FBC A402.1]PROVIDE ACCESSIBLE ROUTE FROM PARKING LOT
 (BOTH NEW AREAS)
  
 3. [FBC 107.3.5]SHEET A-4 SHOW DETAILS 3/A4 AND 4/A4
 SHOW EXISTING CEILING ABV. NEW FRAMED CEILING. SHEET
 A-1 SAYS DROP CEILING. PLEASE CLARIFY WHAT IS EXISTING
 STRUCTURE THAT NEW WALLS ARE CONNECTING TO, WHAT TYPE
 OF CEILING IS IT AND CONNECTORS BEING USED TO CONNECT
 TO EXISTING?
  
 4. [FBC ENERGY C401.2]ENERGY COOLING CALCULATIONS WERE
 MADE FOR 350 SQ. FT. THE NEW A/C AREA IS 280 ACCORDING
 TO COVER SHEET. PLEASE ADJUST ENERGY CALCULATIONS FOR
 AREA WITH A/C AT 280.
  
 5. [FL.STATUTE 553.842]PRODUCT APPROVAL FOR STOREFRONT
 SYSTEM IS EXPIRED.
 PLEASE PROVIDE UPDATED VERSION FOR NOA 16-0208.13.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-21 Cont ID  
Sent By jpearson Date 2019-02-21 Time 09:36 Rev Time 0.00
Received By jpearson Date 2019-02-21 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-01-18 Cont ID  
Sent By jpearson Date 2019-01-18 Time 09:55 Rev Time 0.00
Received By jpearson Date 2019-01-16 Time 08:45 Sent To  
Notes
2019-01-18 09:55:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 (RESPONSE LETTER STATES THAT A CONTRACT WAS PROVIDED,
 BUT THERE IS NO CONTRACT IN THE PACKAGE. PROVIDE AS
 PREVIOUSLY REQUESTED.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By jpearson Date 2018-11-06 Time 12:04 Rev Time 0.00
Received By jpearson Date 2018-11-06 Time 11:13 Sent To  
Notes
2018-11-06 12:04:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. LOAD CALCULAITON PROVIDED SHOWS A LOAD OF 384 AMPS,
 WHICH EXCEEDS THE CAPACITY OF THE SERVICE FEEDERS.
 PROVIDE CORRECTION. NEC 310.15(B)(16)
 3. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 4. PROVIDE SHOW WINDOW OUTLET PER NEC 210.62.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-10 Cont ID  
Sent By scaldero Date 2019-01-10 Time 11:37 Rev Time 0.00
Received By scaldero Date 2019-01-10 Time 11:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-26 Cont ID  
Sent By pleduc Date 2018-10-26 Time   Rev Time 0.00
Received By pleduc Date 2018-10-26 Time 13:26 Sent To I
Notes
2018-10-26 13:28:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-02-26 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-29 Time 15:33 Sent To  
Notes
2019-01-30 15:33:33B30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-24 Cont ID  
Sent By mcruz Date 2019-01-24 Time 13:31 Rev Time 0.00
Received By mcruz Date 2019-01-04 Time 13:43 Sent To PC
Notes
2019-01-07 13:43:59B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-17 Cont ID  
Sent By gjohnson Date 2018-12-17 Time 09:44 Rev Time 0.00
Received By gjohnson Date 2018-10-24 Time 15:15 Sent To  
Notes
2018-10-25 15:15:40B30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By dbattles Date 2018-12-10 Time 15:06 Rev Time 0.00
Received By dbattles Date 2018-12-10 Time 15:06 Sent To  
Notes
2018-12-10 15:06:45DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-02-26 Cont ID  
Sent By ccole Date 2019-02-26 Time 12:19 Rev Time 0.00
Received By ccole Date 2019-02-26 Time 12:19 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-01-17 Cont ID  
Sent By ccole Date 2019-01-17 Time 11:13 Rev Time 0.00
Received By ccole Date 2019-01-17 Time 11:00 Sent To  
Notes
2019-01-17 11:39:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18101134
 1/17/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: SHOW HOW OUTSIDE AIR IS BEING PROVIDED
 FOR THE OCCUPANTS PER SECTION 401.2 AND PROCVIDE A
 VENTILATION CALCULATION. IF MECHANICAL VENTILATION IS
 TO BE PROVIDED, SHOW THE DUCT AND AIR INLET, AND
 INDICATE HOW THE O/AWILL BE AUTOMATICALLY CONTROLLED
 PER SECTION C403.2.4.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-11-07 Cont ID  
Sent By cmontell Date 2018-11-07 Time 06:30 Rev Time 0.00
Received By cmontell Date 2018-11-07 Time 06:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-02-19 Cont ID  
Sent By jesmith Date 2019-02-19 Time 08:54 Rev Time 0.00
Received By jesmith Date 2019-02-19 Time 08:54 Sent To  
Notes
2019-02-19 08:54:10APPROVED
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTORS
 APPROVAL
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-01-22 Cont ID  
Sent By gjohnson Date 2019-01-22 Time 16:51 Rev Time 0.00
Received By gjohnson Date 2019-01-22 Time 16:51 Sent To Z
Notes
2019-01-22 17:03:402ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT ADDRESSED
 THERE ARE MAJOR DESIGN FLAWS IN THIS PLAN I I'M
 REQUESTING A MEETING WITH THE DESIGN PROFESSIONAL TO GO
 OVER COMMENTS. SEE CONTACT INFO BELOW.
  
 1. THE SANITARY FROM THE NEW BATHROOM SHALL NOT
 DISCHARGE TO THE RECLAIMED WATER SYSTEM IT SHALL
 DISCHARGE DIRECTLY TO CITY SEWER. PER FBC PL 301.3
  
 2.THE NEW BATHROOM FIXTURE SHALL BE CONNECTED TOGETHER
 AND VENTED BY THE LAVATORY. PER FBC PL 912.1
  
 3. PLEASE SHOW CITY SEWER ON SITE PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 4. A TRAP PRIMER IS REQUIRED ON ANY NEW FLOOR DRAINS.
 PER FBC PL 1002.4.1
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 PER FBC PL 416.5
  
 6. PROVIDE WATER ISOMETRIC OF NEW BATHROOM INCLUDING
 WATER HEATER . PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 7. SHOW LOCATION OF WATER HEATER ON THE FLOOR PLAN. PER
 WPB AMEND TO FBC 107.2.1
  
 8. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDE FOR THE WATER HEATER IT SHALL COMPLY WITH FBC
 ENERGY TABLE 404.2
  
 9. THE SITE PLAN SHOWS A PROPOSED WATER METER LOCATION
 IF THEY ARE INSTALLING A NEW METER A NEW BACKFLOW WILL
 BE REQUIRED PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT
 WILL BE REQUIRED FOR THE NEW BACKFLOW. PER WPB
 UTILITIES DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-17 Cont ID  
Sent By gjohnson Date 2018-12-17 Time 08:27 Rev Time 0.00
Received By gjohnson Date 2018-12-17 Time 07:04 Sent To  
Notes
2018-12-17 09:05:051ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SANITARY FROM THE NEW BATHROOM SHALL NOT
 DISCHARGE TO THE RECLAIMED WATER SYSTEM IT SHALL
 DISCHARGE DIRECTLY TO CITY SEWER. PER FBC PL 301.3
  
 2.THE NEW BATHROOM FIXTURE SHALL BE CONNECTED TOGETHER
 AND VENTED BY THE LAVATORY. PER FBC PL 912.1
  
 3. PLEASE SHOW CITY SEWER ON SITE PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
 4. A TRAP PRIMER IS REQUIRED ON ANY NEW FLOOR DRAINS.
 PER FBC PL 1002.4.1
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 PER FBC PL 416.5
  
 6. PROVIDE WATER ISOMETRIC OF NEW BATHROOM INCLUDING
 WATER HEATER . PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 7. SHOW LOCATION OF WATER HEATER ON THE FLOOR PLAN. PER
 WPB AMEND TO FBC 107.2.1
  
 8. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTILLATION
 GUIDE FOR THE WATER HEATER IT SHALL COMPLY WITH FBC
 ENERGY TABLE 404.2
  
 9. THE SITE PLAN SHOWS A PROPOSED WATER METER LOCATION
 IF THEY ARE INSTALLING A NEW METER A NEW BACKFLOW WILL
 BE REQUIRED PLEASE PLACE NOTE ON PLAN A SEPARATE PERMIT
 WILL BE REQUIRED FOR THE NEW BACKFLOW. PER WPB
 UTILITIES DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By mcruz Date 2019-01-24 Time 13:31 Rev Time 0.00
Received By mcruz Date 2019-01-24 Time 13:22 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-15 Cont ID  
Sent By mcruz Date 2018-11-15 Time 14:12 Rev Time 0.00
Received By mcruz Date 2018-11-15 Time 13:52 Sent To PC
Notes
2018-11-15 14:12:45ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) COVER SHEET STATES SCOPE OF WORK INCLUDES ADDING A
 OFFICE SPACE, HOWEVER, THE PLAN STATES RETAIL SPACE,
 PLEASE CLARIFY.
 2) SHOW PARKING SPACE FOR ADDITION OF OFFICE OR RETAIL.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]