Plan Review Details - Permit 18101067
Plan Review Stops For Permit 18101067
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-27 Cont ID  
Sent By dbattles Date 2018-12-27 Time 14:00 Rev Time 0.00
Received By dbattles Date 2018-12-27 Time 13:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By dbattles Date 2018-12-06 Time 08:28 Rev Time 0.00
Received By dbattles Date 2018-12-05 Time 16:21 Sent To  
Notes
2018-12-06 08:29:05****CORRECTIONS****
 W.P.B. PERMIT: 18101067
 REVIEWED: DECEMBER 6, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.2.1]ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
 PLEASE ADD NAME AND SIGNATURE OF DESIGNER TO EACH SHEET
 WITHIN THE PLANS (SEAL IS NOT REQUIRED)
 A) SHEET 01 JUST ADD NAME.
 B) SHEETS 02-05 NEED NAME AND SIGNATURE.
  
 2. [FBC R702.4.1]GENERAL. CERAMIC TILE SURFACES SHALL
 BE INSTALLED
 IN ACCORDANCE WITH ANSI A108.1, A108.4, A108.5,
 A108.6, A108.11, A118.1, A118.3, A136.1 AND A137.1.
 R702.4.2 BACKER BOARDS. MATERIALS USED AS BACKERS FOR
 WALL TILE IN TUB AND SHOWER AREAS AND WALL PANELS IN
 SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN TABLE R702.4.2,
 AND
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 RECOMMENDATIONS.
 VERIFY GYPSUM LIMITATIONS IN PRODUCT SPEC SHEET THAT
 PRODUCT CAN BE INSTALLED IN SHOWER AREA.
  
 3. [FBC R308.4.5]GLAZING AND WET SURFACES
 SAFETY GLASS TO BE USED AT SHOWER CATEGORY
 CLASSIFICATION II OR A.
  
 NOTE:
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-11-05 Cont ID  
Sent By fgiaquin Date 2018-11-05 Time 11:14 Rev Time 0.00
Received By fgiaquin Date 2018-11-05 Time 10:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-27 Cont ID  
Sent By dbattles Date 2018-12-27 Time 14:00 Rev Time 0.00
Received By dbattles Date 2018-12-21 Time 14:41 Sent To  
Notes
2018-12-26 14:41:49RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-13 Cont ID  
Sent By jesmith Date 2018-12-13 Time 11:26 Rev Time 0.00
Received By jesmith Date 2018-12-13 Time 11:26 Sent To  
Notes
2018-12-08 10:52:3112/8 REMOVED FROM BOARD; ROUTED TO JES DESK
  
  
2018-10-24 16:01:32R40

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-13 Cont ID  
Sent By jesmith Date 2018-12-13 Time 11:26 Rev Time 0.00
Received By jesmith Date 2018-12-13 Time 11:24 Sent To  
Notes
2018-12-13 11:25:59PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. THERE WILL BE UNDERGROUND MODIFICATIONS OF SOME
 EXISTING FIXTURE DRAINS. AN UG INSPECTION IS REQUIRED
 PER WPB FBC 110.3.C.1
 3. ABANDONED WATER CLOSET FIXTURE DRAIN SHALL BE
 PERMANENTLY CAPPED WITH A FITTING WHICH IS COMPATIBLE
 WITH THE EXISTING MATERIAL AND IS CODE COMPLIANT. A
 SCHEDULE 40 PVC CAP FOR AN EXISTING PVC DRAIN IS
 ACCEPTABLE FOR THIS APPLICATION AS IT WILL NOT AFFECT
 THE SANITARY CONDITION OF THE SYSTEM.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  


Account Summary | Usage Policy | Privacy Policy