Plan Review Details - Permit 18101024
Plan Review Stops For Permit 18101024
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-29 Cont ID  
Sent By jwitmer Date 2018-10-29 Time 07:53 Rev Time 0.00
Received By jwitmer Date 2018-10-29 Time 07:16 Sent To  
Notes
2018-10-29 07:54:482017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18101024
 ADD: 1551N. FLAGLER SUITE: 1018
 CONT: DELCO CONSTRUCTION
 TEL: 561-436-4106
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 29/2018
 ACTION: BUILDING PROVISO
 ? 1) 2017 FBC-B 2509.2 BASE FOR TILE.
 MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND
 SHOWER AREAS AND WALL AND CEILING PANELS IN SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 RECOMMENDATIONS. WATER-RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C840 AND THE MANUFACTURER?S
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840.
 TABLE 2509.2
 BACKERBOARD MATERIALS
 MATERIAL STANDARD
 GLASS MAT GYPSUM BACKING PANEL ASTM C1178
 NONASBESTOS FIBER-CEMENT BACKER BOARD ASTM C1288 OR ISO
 8336, CATEGORY C
 NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER
 UNIT ASTM C1325
 2509.3 LIMITATIONS.
 WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED
 IN THE FOLLOWING LOCATIONS:
 1. 1.OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2.WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER/ BUILDING
 DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6717/ FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-11-06 Cont ID  
Sent By jpearson Date 2018-11-06 Time 09:32 Rev Time 0.00
Received By jpearson Date 2018-11-06 Time 07:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-24 Cont ID  
Sent By pleduc Date 2018-10-24 Time   Rev Time 0.00
Received By pleduc Date 2018-10-24 Time 11:19 Sent To I
Notes
2018-10-24 11:29:02THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THERE ARE NO INDICATIONS OF EXISTING (OR NOT) OF FIRE
 SPRINKLER AND/OR FIRE ALARM PROTECTION WITHIN THE
 PROPOSED WORK AREA LIMITS.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 09:38 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 09:38 Sent To  
Notes
2018-10-23 15:27:17B17

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 09:37 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 08:50 Sent To  
Notes
2018-12-06 09:37:531ST REVIEW: APPROVED
 REVISION REQUIRED
 PROVIDE REVISION CALLING OUT UL LISTED ASSEMBLY FOR
 FLOOR PENETRATION OF RELOCATED BATHTUB AND ABANDONED
 FLOOR PENETRATION REPAIR PER WPB FBC 107.2.1. REVISION
 SHALL BE IN PLACE PRIOR TO 1ST INSPECTION.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
 18101024 1551 N FLAGLER DR PH L18
  
  