2018-10-30 13:19:03 | RESIDENTIAL (R2) FLOORING SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- INFORMATION SUBMITTED FOR PROFLEX 90 MSC ARE NOT THE |
| COPIES OF THE REQUIRED TESTING. INFORMATION SUBMITTED |
| IS ONLY THE MANUFACTURER'S SPECS. WE NEED COPIES OF THE |
| ACTUAL TESTING THAT MATCHES THIS BUILDING CONSTRUCTION. |
| IN ADDITION, THE INFORMATION SUBMITTED IS FOR BUILDINGS |
| WITH 8" CONCRETE SLAB THICKNESS WITH AN ACOUSTICAL |
| CEILING ASSEMBLY. TYPICALLY, THERE ARE NO BUILDINGS |
| WITH SUSPENDED ACOUSTICAL CEILINGS IN THIS AREA. PLEASE |
| SUBMIT THE INFORMATION REQUESTED IN THE FIRST REVIEW. |
| SEE BELOW. |
| |
| 1- FLOORING SOUND INSULATION MATERIAL: |
| A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE |
| DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION |
| (2017). |
| |
| B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS |
| (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS |
| REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017). |
| |
| C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS |
| (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS |
| REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017). |
| |
| NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND |
| PROPOSED FLOOR FINISH. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |