Plan Review Details - Permit 18100964
Plan Review Stops For Permit 18100964
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-31 Cont ID  
Sent By pvalenti Date 2018-12-31 Time 11:30 Rev Time 0.00
Received By pvalenti Date 2018-12-31 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-14 Cont ID  
Sent By pvalenti Date 2018-12-14 Time 08:42 Rev Time 0.00
Received By pvalenti Date 2018-12-14 Time 08:42 Sent To  
Notes
2018-12-14 09:14:45****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107 THE SUBMITTED UNDERLAYMENT (QEP NATURAL CORK)
 WAS NOT SUBMITTED WITH FLAME SPREAD SPECIFICATIONS FOR
 THE PROPOSED WOOD FLOORING. AT THE CITY, WE DO HAVE
 RECORD OF THIS PRODUCT USED IN CONJUNCTION WITH TILE
 FLOORING BUT NOT WOOD. PLEASE PROVIDE FLAME SPREAD
 SPECIFICATIONS FOR THE UNDERLAYMENT WITHOUT TILE OR
 PROVIDE A DIFFERENT UNDERLAYMENT THAT HAS BEEN TESTED
 FOR THIS CONDITION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-27 Cont ID  
Sent By pvalenti Date 2018-10-27 Time 12:14 Rev Time 0.00
Received By pvalenti Date 2018-10-27 Time 12:14 Sent To  
Notes
2018-10-27 12:21:55 
 ****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIALPROVIDE THE FOLLOWING
 INFORMATION FOR FLOORING SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 *
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED FLOORING
 (TILE/MARBLE/LAMINATE/WOOD/OTHER).
 4. STATED VALUE OF WORK.
 5. EXISTING SITE CONDITIONS:
 A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN
 CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL)
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON
 EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S,
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE
 AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-14 Cont ID  
Sent By pvalenti Date 2018-12-14 Time 09:15 Rev Time 0.00
Received By pvalenti Date 2018-12-12 Time 13:36 Sent To  
Notes
2018-12-13 13:36:41RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-27 Cont ID  
Sent By pvalenti Date 2018-10-27 Time 12:22 Rev Time 0.00
Received By pvalenti Date 2018-10-19 Time 16:07 Sent To I
Notes
2018-10-22 16:07:19BLDG <5K