Plan Review Details - Permit 18100912
Plan Review Stops For Permit 18100912
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-29 Cont ID  
Sent By dbattles Date 2019-01-29 Time 10:47 Rev Time 0.00
Received By dbattles Date 2019-01-29 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By dbattles Date 2018-10-29 Time 08:17 Rev Time 0.00
Received By dbattles Date 2018-10-29 Time 08:17 Sent To  
Notes
2018-10-29 08:18:06****CORRECTIONS****
 W.P.B. PERMIT: 18100912
 REVIEWED: OCTOBER 29, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC TABLE R301.2(2)]
 PROVIDE PROJECT DATA:
 OCCUPANCY = ___ (R-3 FOR SINGLE FAMILY)
 TYPE OF WALL CONSTRUCTION = _________(ARE THE WALLS
 MASONRY, CONCRETE OR WOOD FRAMED)?
 RISK CATEGORY = ___(II)?
 EXPOSURE CATEGORY = ___(B,C OR D)?
 BUILDING CLASSIFICATION = __________(ENCLOSED)?
 MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT
 MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF
 PEAK)
 WIND SPEED V ULT = _____(170)?
 WIND SPEED V ASD = _____(132)?
 COMPONANT & CLADDING:
 FBC TABLE R301.2(2)
 DESIGN PRESSURE = +___ & -___
 R301.2(3) CHECK EXPOSURE AND M.R.H. TO DETERMINE IF
 ADJUSTMENT FACTOR NEEDED.
 MULTIPLE DESIGN PRESUURES BY THE ADJUSTMENT FACTOR IF <
 OR > 1.00
  
 2. [FBC TABLE R301.2(2)]PROVIDE PRESSURE ON EACH
 WINDOW/DOOR AND INDICATE IF THE OPENING IS IN THE
 INTERIOR OR EXTERIOR ZONE.
  
 3. [FBC R310.2.1]MARK ON PLAN SHEET WHICH WINDOW ARE
 FOR EMERGENCY ESCAPE
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-10-25 Cont ID  
Sent By fmittner Date 2018-10-25 Time 13:42 Rev Time 0.00
Received By fmittner Date 2018-10-25 Time 13:42 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-29 Cont ID  
Sent By dbattles Date 2019-01-29 Time 10:48 Rev Time 0.00
Received By dbattles Date 2019-01-25 Time 14:52 Sent To  
Notes
2019-01-28 14:52:57RESUB ROUTED TO DBATTLES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-29 Cont ID  
Sent By dbattles Date 2018-10-29 Time 08:18 Rev Time 0.00
Received By dbattles Date 2018-10-19 Time 13:33 Sent To  
Notes
2018-10-22 13:34:13ROUTED TO HISTORIC INBOX