2018-10-23 06:19:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY |
| THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| 471.025; WPB FBC 107.2.1, 107.3.5 |
| |
| 2. PERMIT APPLICATION UNCLEAR, IS A BRAND NEW COOLER |
| BEING INSTALLED OR ONLY NEW COOLING EQUIPMENT FOR |
| EXISTING COOLER? SPEC SHEETS GIVING DO NOT SPECIFY THE |
| MODEL # AND SIZE OF UNIT BEING INSTALLED. MORE |
| INFORMATION NEEDED. FBC 107.2.1 |
| |
| 3. PROVIDE UL OR OTHER NRTL LISTING FOR NEW EQUIPMENT |
| FOR PRODUCT APPROVAL. NEC 90.7, 110.2, 110.3B |
| |
| 4. VALUE SEEMS LOW. PROVIDE COPY OF SIGNED CONTRACT. |
| SIGNED BY BOTH OWNER AND CONTRACTOR. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |