Plan Review Details - Permit 18100869
Plan Review Stops For Permit 18100869
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-19 Cont ID  
Sent By fgiaquin Date 2018-11-19 Time 06:22 Rev Time 0.00
Received By fgiaquin Date 2018-11-19 Time 06:19 Sent To M
Notes
2018-11-19 06:21:39PROVISO:
  
 PROVIDE LOAD CALCULATION BEFORE FINAL INSPECTION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-23 Cont ID  
Sent By fgiaquin Date 2018-10-23 Time 06:20 Rev Time 0.00
Received By fgiaquin Date 2018-10-23 Time 06:06 Sent To I
Notes
2018-10-23 06:19:59ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. PERMIT APPLICATION UNCLEAR, IS A BRAND NEW COOLER
 BEING INSTALLED OR ONLY NEW COOLING EQUIPMENT FOR
 EXISTING COOLER? SPEC SHEETS GIVING DO NOT SPECIFY THE
 MODEL # AND SIZE OF UNIT BEING INSTALLED. MORE
 INFORMATION NEEDED. FBC 107.2.1
  
 3. PROVIDE UL OR OTHER NRTL LISTING FOR NEW EQUIPMENT
 FOR PRODUCT APPROVAL. NEC 90.7, 110.2, 110.3B
  
 4. VALUE SEEMS LOW. PROVIDE COPY OF SIGNED CONTRACT.
 SIGNED BY BOTH OWNER AND CONTRACTOR.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-26 Cont ID  
Sent By cmontell Date 2018-11-26 Time 06:26 Rev Time 0.00
Received By cmontell Date 2018-11-26 Time 06:26 Sent To  
Notes
2018-11-15 16:10:37RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-23 Cont ID  
Sent By fgiaquin Date 2018-10-23 Time 06:20 Rev Time 0.00
Received By fgiaquin Date 2018-10-18 Time 14:22 Sent To  
Notes
2018-10-19 14:23:24ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-26 Cont ID  
Sent By cmontell Date 2018-11-26 Time 06:26 Rev Time 0.00
Received By cmontell Date 2018-11-26 Time 06:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-22 Cont ID  
Sent By cmontell Date 2018-10-22 Time 14:50 Rev Time 0.00
Received By cmontell Date 2018-10-22 Time 14:50 Sent To  
Notes
***NONE***