Plan Review Details - Permit 18100747
Plan Review Stops For Permit 18100747
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-10 Cont ID  
Sent By jgomez Date 2018-12-10 Time 16:25 Rev Time 0.00
Received By jgomez Date 2018-12-10 Time 15:43 Sent To  
Notes
2018-12-10 16:10:20BUILDING REVIEW APPROVED WITH PROVISO (NOTE: PROVIDE
 BEFORE INSTALLATION TO AVOID CONFLICTS/DELAYS):
 1-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR NEW GLASS
 BLOCK IN MASTER BATHROOM SHOWER.
 NOTE: NOT FEES FOR THIS SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-27 Cont ID  
Sent By jgomez Date 2018-11-27 Time 11:57 Rev Time 0.00
Received By jgomez Date 2018-11-27 Time 10:59 Sent To  
Notes
2018-11-27 12:07:28BUILDING REVIEW APPROVED WITH PROVISO (NOTE: PROVIDE
 BEFORE INSTALLATION TO AVOID CONFLICTS/DELAYS):
 1-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR NEW GLASS
 BLOCK IN MASTER BATHROOM SHOWER.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-23 Cont ID  
Sent By jleahy Date 2018-10-23 Time 17:20 Rev Time 0.00
Received By jleahy Date 2018-10-23 Time 17:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-12-26 Cont ID  
Sent By lcrespo Date 2018-12-26 Time 15:33 Rev Time 0.00
Received By lcrespo Date 2018-12-26 Time 15:33 Sent To  
Notes
2018-12-26 15:33:5412/26/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-12-10 Cont ID  
Sent By lcrespo Date 2018-12-10 Time 15:20 Rev Time 0.00
Received By lcrespo Date 2018-12-10 Time 15:20 Sent To  
Notes
2018-12-10 15:20:2212/10/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. CSST 2 LBS TABLE WAS NOT SUPPLIED ON P-2 NOTES. WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. THE SIZE ON THE EHD CSST MUST BE
 LABELED AND AT THIS MOMENT IT MAY NOT BE PROPERLY
 SIZED. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SECOND REQUEST, SUBMIT MANUFACTURES SPECIFICATIONS
 FOR THE GRILL, TANK-LESS WATER HEATER AND DRYER. 2017
 FBC-RES. SEC.G2408.1.
 5. SECOND REQUEST, SUBMIT MANUFACTURER?S SPECIFICATIONS
 FOR THE PRESSURE REGULATORS. REGULATORS INSTALLED ON
 THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION, 2017 FBC FUEL GAS RES. SEC.
 G2421.1.
 6. SECOND REQUEST, SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE (CLOTHES DRYERS), 2017 FBC FUEL GAS RES.
 SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS).
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-11-01 Cont ID  
Sent By lcrespo Date 2018-10-31 Time 08:23 Rev Time 0.00
Received By lcrespo Date 2018-10-31 Time 08:23 Sent To  
Notes
2018-10-31 08:24:0311/01/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE INDICATE ON PLANS WHAT CODE CYCLE IS BEING
 USE (E.G. 2017 FBC FUEL GAS 6TH EDITION)
 2. SHOW ALL PIPE SIZES FOR EACH PIPE SIZE, WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 3. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS, WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL,
 TANK-LESS WATER HEATER AND DRYER. 2017 FBC-RES.
 SEC.G2408.1.
 5. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION, 2017 FBC FUEL GAS RES. SEC. G2421.1.
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 (CLOTHES DRYERS), 2017 FBC FUEL GAS RES. SEC. G2407.1
 AND G2439.4 (CLOTHES DRYERS).
 7. SHOW UNIONS FOR REGULATORS ON ISOMETRIC DRAWING,
 2017 FBC FUEL GAS RES SECS. G2413.4.1, G2413.4.2
 8. REGULATOR NOT DRAWN IN ON ISOMETRIC FOR FIRST HOT
 WATER TANK-LESS, SHOW THE LOCATION OF ALL (STEP-DOWN)
 REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH REGULATOR, 2017 FBC FUEL GAS
 RES. SEC. G2420.4.
 9. A SUB GAS PERMIT IS REQUIRED, WPB AMENDMENTS TO THE
 FBC SEC. 105.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-26 Cont ID  
Sent By lcrespo Date 2018-12-26 Time 15:34 Rev Time 0.00
Received By lcrespo Date 2018-12-20 Time 11:08 Sent To  
Notes
2018-12-21 11:08:56RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-10 Cont ID  
Sent By jgomez Date 2018-12-10 Time 16:25 Rev Time 0.00
Received By jgomez Date 2018-12-03 Time 13:39 Sent To I
Notes
2018-12-04 13:39:36RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-27 Cont ID  
Sent By jgomez Date 2018-11-27 Time 12:11 Rev Time 0.00
Received By jgomez Date 2018-10-16 Time 11:07 Sent To I
Notes
2018-10-18 11:07:11R03

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-11-07 Cont ID  
Sent By cmontell Date 2018-11-07 Time 05:34 Rev Time 0.00
Received By cmontell Date 2018-11-07 Time 05:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-01 Cont ID  
Sent By lcrespo Date 2018-11-01 Time 17:26 Rev Time 0.00
Received By lcrespo Date 2018-10-31 Time 08:24 Sent To  
Notes
2018-11-01 17:30:3511/01/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  