Plan Review Details - Permit 18100671
Plan Review Stops For Permit 18100671
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-03-05 Cont ID  
Sent By jgomez Date 2019-03-05 Time 11:32 Rev Time 0.00
Received By jgomez Date 2019-03-05 Time 08:08 Sent To  
Notes
2019-03-05 11:15:52BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) BALCONY
 UNDERLAYMENT THAT IS DESIGNED TO BE INSTALLED WITH
 FINISH FLOOR SPECIFIED ON PLANS. NOTE: FLINTASTIC
 MODIFIED BITUMEN ROOF SYSTEM PRODUCT APPROVAL
 FL16709-R4 SPECIFIED ON BALCONY FLOOR CONSTRUCTION
 DETAIL ON SHEET A-010 IS NOT GOOD FOR CERAMIC TILE.
  
 2) ARCHITECT TO APPROVE (NOT SIGNING/SEALING) PRODUCT
 APPROVAL.
  
 3-LABEL FOR WINDOWS & DOORS SHOWING THE U-FACTOR & SHGC
 FACTOR SPECIFIED ON THE ENERGY CALCULATIONS IS
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-01-23 Cont ID  
Sent By jgomez Date 2019-01-23 Time 15:44 Rev Time 0.00
Received By jgomez Date 2019-01-23 Time 12:00 Sent To  
Notes
2019-01-23 15:45:42BUILDING REVIEW APPROVED WITH PROVISO:
  
 NOTE:
 THERE ARE SOME PRODUCT APPROVALS THAT WERE CHANGED FROM
 PREVIOUS REVIEWS. I TOLD DAVID BOWDEN TO TAKE BACK ALL
 PRODUCT APPROVALS AND RESUBMIT ONLY THE ONES THAT ARE
 GOING TO BE INSTALLED TO AVOID CONFLICTS/DELAYS. ALSO,
 I TOLD HIM TO IDENTIFY ON ALL PRODUCT APPROVALS THE
 LOCATION OF PRODUCT APPROVALS SUBMITTED. FOR EXAMPLE,
 ENTRY DOOR, STAIRWAY WINDOWS, ETC.
  
 1-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
  
 A) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE
 INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS. NOTE:
 FLINTASTIC MODIFIED BITUMEN ROOF SYSTEM PRODUCT
 APPROVAL FL16709-R4 SPECIFIED ON BALCONY FLOOR
 CONSTRUCTION DETAIL ON SHEET A-010 IS NOT GOOD FOR
 CERAMIC TILE.
  
 B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS/ELEVATIONS.
  
 C) CASEMENT WINDOWS SIZE AS SPECIFIED ON WINDOW
 SCHEDULE. SEE PLANS/ELEVATIONS.
  
 D)OUTSWING ENTRY DOORS WITH SIDELITES AS SHOWN ON
 PLANS/ELEVATIONS.
  
 E) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 2) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- ENERGY CALCULATIONS SUBMITTED (RESCHECK):
 A) LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED.
 B) BLOWER DOOR TEST WILL BE REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-10 Cont ID  
Sent By jgomez Date 2019-01-10 Time 09:27 Rev Time 0.00
Received By jgomez Date 2019-01-10 Time 08:39 Sent To  
Notes
2019-01-10 08:56:25NEW SINGLE FAMILY RESIDENCE (R3), THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1-OK. PROVISO. LOT DRAINAGE TO BE VERIFIED FOR FINAL
 INSPECTION.
  
 2-LOT SPLIT. ADDRESSING NEED TO BE COORDINATED BEFORE
 ISSUANCE OF PERMIT.
  
 3- AREAS CORRECTED. VALUATION WAS UPDATED TO $608,478
 AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS. . THE PERMIT
 FEE BALANCE IS $10,479.41.
  
 4- OK.
  
 5- OK.
  
 6- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R307.1
 FBC-RESIDENTIAL. PROVISO: CHECK FOR READILY ACCESSIBLE
 LOCATION. .
  
 7- STAIRWAY WINDOW SYSTEM BY STAIRWAY:
 A) SHEET A-003 SPECIFIES "STAIRWAY WINDOW SYSTEM DETAIL
 (BY OTHER)". PROVIDE COMPLETE INFORMATION AS A DEFERRED
 SUBMITTAL (NO FEES). SEC. R301.1 FBC-RESIDENTIAL.
 WINDOW SYSTEM TO BE REVIEWED/APPROVED BY ARCHITECT
 PRIOR TO SUBMITTAL.
  
 B) ARCHITECT TO PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR WALL FRAMING AT STAIRWAY SUPPORTING
 THE WINDOW SYSTEM. SEC. R301.1 FBC-RESIDENTIAL.
  
 8- OK.
  
 ORIGINAL COMMENT:
 9- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON THE
 EXTERIOR ELEVATIONS SEEM TO BE LOW FOR A TWO STORY
 BUILDING LOCATED IN EXPOSURE "C" AND A WIND SPEED OF
 175MPH AS SPECIFIED ON PLANS. . ALSO, SOME WINDOWS ARE
 LOCATED IN END ZONE NOT INTERIOR (SEE NOTE "A" ON
 FIGURE R301.2(7) FOR MIN. END ZONE DIMENSION). REVISE
 AS REQUIRED, INCLUDING THE GARAGE DOORS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 ENGINEER LETTER FROM WILLIAM F. STUHRKE, PHD, PE IS
 INCORRECT:
 (A) BUILDING EXPOSURE WAS CHANGED FORM EXPOSURE C TO
 EXPOSURE B. THIS SEEMS TO BE INCORRECT. ACCORDING TO
 SEC. R301.2.1.4 AND SEC. R301.2.1.4.1 THIS BUILDING IS
 LOCATED IN EXPOSURE C NOT B. REVISE INFORMATION IN ALL
 PLANS AS REQUIRED OR PROVIDE COMPLETE ENGINEER ANALYSIS
 FOR EACH WIND DIRECTION. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 (B)CLARIFY IF DESIGN PRESSURES SHOWN ON THE EXTERIOR
 ELEVATIONS ARE GIVEN AS ULTIMATE WIND SPEED OR NOMINAL
 WIND SPEED. SEC. R301.2.1.3 FBC-RESIDENTIAL.
  
 (C)THE ADDRESS IS INCORRECT.
  
 (D)ENGINEER STATES THAT THERE ARE NO WINDOWS LOCATED IN
 ZONE 5. THIS IS INCORRECT. THERE ARE SOME WINDOWS THAT
 ARE LOCATED WITHIN 4 FEET OF THE CORNER. REVISE ALL
 RELEVANT INFORMATION AS REQUIRED.
  
 (E)NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY F. S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS. NOTE: THIS IS NOT A DIGITAL SUBMITTAL. HARD
 COPIES ARE REQUIRED.
  
 ORIGINAL COMMENT:
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE STONE VENEER SHOWN ON THE EXTERIOR
 ELEVATIONS TO SHOW COMPLIANCE WITH THE WIND RESISTANCE
 SEC. R703.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISE BATHROOM BUMP METAL FRAMING ENCLOSURE DETAIL ON
 SHEET A-010. THIS DETAIL SPECIFIES STUCCO. REVISE TO
 MATH PROPOSED STONE VENEER. SEC. R301.1
 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 BALCONY FLOOR CONSTRUCTION. ALSO SPECIFY WATERPROOFING
 AND FINISH FLOOR. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 BALCONY FLOOR CONSTRUCTION DETAIL ON SHEET A-010
 DOESN'T SPECIFY FINISH FLOOR. COORDINATE WITH SELECTED
 ASSEMBLY W-4 FROM FLORIDA PRODUCT APPROVAL FL16709-R4
 SUBMITTED.
  
 12-OK.
  
 13- OK.
  
 14- OK.
  
 15- OK.
  
  
 16- OK.
  
 17- OK.
  
 18- OK.
  
 19- SHEET 004:
 A) OK.
 B) OK.
 C) OK.
  
 20- OK.
  
 21- OK.
  
 22- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) OK.
 B) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE
 INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS.
 DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR FINISH
 FLOORING. NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO
 BE INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ZONES.
 NOTE: THIS NEEDS TO BE COORDINATED WITH ITEM #11 ABOVE.
  
 C) OK.
  
 NOTE: PRODUCT APPROVALS WILL BE REVIEWED ONCE BUILDING
 EXPOSURE AND DESIGN PRESSURES ARE REVISED. SEE ITEM #9
 ABOVE.
  
 D) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS/ELEVATIONS.
  
 E) CASEMENT WINDOWS SIZE AS SPECIFIED ON WINDOW
 SCHEDULE. SEE PLANS/ELEVATIONS.
  
 F) INSWING ENTRY DOORS WITH SIDELITES AND TRANSOM ABOVE
 AS SHOWN ON PLANS/ELEVATIONS.
 NOTE: NOA 18-0503.06 SUBMITTED IS FOR OUTSWING ENTRY
 DOORS ONLY.
  
 G)WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 H)WINDOW SYSTEM SHOWN BY THE STAIRWAY.
  
 23- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 24- ENERGY CALCULATIONS SUBMITTED (RESCHECK):
 A) LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED.
 B) BLOWER DOOR TEST WILL BE REQUIRED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-01-04 Cont ID  
Sent By jgomez Date 2019-01-04 Time 18:04 Rev Time 0.00
Received By jgomez Date 2019-01-03 Time 17:04 Sent To  
Notes
2019-01-03 17:33:13NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1-OK. PROVISO. LOT DRAINAGE TO BE VERIFIED FOR FINAL
 INSPECTION.
  
 2-LOT SPLIT. ADDRESSING NEED TO BE COORDINATED BEFORE
 ISSUANCE OF PERMIT.
  
 3- AREAS CORRECTED. VALUATION WAS UPDATED TO $608,478
 AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS. . THE PERMIT
 FEE BALANCE IS $10,479.41.
  
 4- OK.
  
 5- OK.
  
 6- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R307.1
 FBC-RESIDENTIAL. PROVISO: CHECK FOR READILY ACCESSIBLE
 LOCATION. .
  
 7- SEMI COMPLIED. PROVIDE COMPLETE INFORMATION FOR
 STAIRWAY WINDOW SYSTEM.
  
 8- OK.
  
 ORIGINAL COMMENT:
 9- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON THE
 EXTERIOR ELEVATIONS SEEM TO BE LOW FOR A TWO STORY
 BUILDING LOCATED IN EXPOSURE "C" AND A WIND SPEED OF
 175MPH AS SPECIFIED ON PLANS. . ALSO, SOME WINDOWS ARE
 LOCATED IN END ZONE NOT INTERIOR (SEE NOTE "A" ON
 FIGURE R301.2(7) FOR MIN. END ZONE DIMENSION). REVISE
 AS REQUIRED, INCLUDING THE GARAGE DOORS. SEC. R301.2.1
 FBCD-RESIDENTIAL.
  
 RESPONSE:
 ENGINEER LETTER FROM WILLIAM F. STUHRKE, PHD, PE IS
 INCORRECT:
 (A) BUILDING EXPOSURE WAS CHANGED FORM EXPOSURE C TO
 EXPOSURE B. THIS SEEMS TO BE INCORRECT. ACCORDING TO
 SEC. R301.2.1.4 AND SEC. R301.2.1.4.1 THIS BUILDING IS
 LOCATED IN EXPOSURE C NOT B. REVISE INFORMATION IN ALL
 PLANS AS REQUIRED OR PROVIDE COMPLETE ENGINEER ANALYSIS
 FOR EACH WIND DIRECTION. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 (B)CLARIFY IF DESIGN PRESSURES SHOWN ON THE EXTERIOR
 ELEVATIONS ARE GIVEN AS ULTIMATE WIND SPEED OR NOMINAL
 WIND SPEED. SEC. R301.2.1.3 FBC-RESIDENTIAL.
  
 (C)THE ADDRESS IS INCORRECT.
  
 (D)ENGINEER STATES THAT THERE ARE NO WINDOWS LOCATED IN
 ZONE 5. THIS IS INCORRECT. THERE ARE SOME WINDOWS THAT
 ARE LOCATED WITHIN 4 FEET OF THE CORNER. REVISE ALL
 RELEVANT INFORMATION AS REQUIRED.
  
 (E)NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY F. S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS. NOTE: THIS IS NOT A DIGITAL SUBMITTAL. HARD
 COPIES ARE REQUIRED.
  
 ORIGINAL COMMENT:
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE STONE VENEER SHOWN ON THE EXTERIOR
 ELEVATIONS TO SHOW COMPLIANCE WITH THE WIND RESISTANCE
 SEC. R703.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISE BATHROOM BUMP METAL FRAMING ENCLOSURE DETAIL ON
 SHEET A-010. THIS DETAIL SPECIFIES STUCCO. REVISE TO
 MATH PROPOSED STONE VENEER. SEC. R301.1
 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 BALCONY FLOOR CONSTRUCTION. ALSO SPECIFY WATERPROOFING
 AND FINISH FLOOR. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 BALCONY FLOOR CONSTRUCTION DETAIL ON SHEET A-010
 DOESN'T SPECIFY FINISH FLOOR. COORDINATE WITH SELECTED
 ASSEMBLY W-4 FROM FLORIDA PRODUCT APPROVAL FL16709-R4
 SUBMITTED.
  
 12-OK.
  
 13- OK.
  
 14- OK.
  
 15- OK.
  
  
 16- OK.
  
 17- OK.
  
 18- OK.
  
 19- SHEET 004:
 A) OK.
 B) OK.
 C) OK.
  
 20- OK.
  
 21- OK.
  
 22- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) OK.
 B) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE
 INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS.
 DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR FINISH
 FLOORING. NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO
 BE INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ZONES.
 NOTE: THIS NEEDS TO BE COORDINATED WITH ITEM #11 ABOVE.
  
 C) OK.
  
 NOTE: PRODUCT APPROVALS WILL BE REVIEWED ONCE BUILDING
 EXPOSURE AND DESIGN PRESSURES ARE REVISED. SEE ITEM #9
 ABOVE.
  
 D) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS/ELEVATIONS.
  
 E) CASEMENT WINDOWS SIZE AS SPECIFIED ON WINDOW
 SCHEDULE. SEE PLANS/ELEVATIONS.
  
 F) INSWING ENTRY DOORS WITH SIDELITES AND TRANSOM ABOVE
 AS SHOWN ON PLANS/ELEVATIONS.
 NOTE: NOA 18-0503.06 SUBMITTED IS FOR OUTSWING ENTRY
 DOORS ONLY.
  
 G)WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 H)WINDOW SYSTEM SHOWN BY THE STAIRWAY.
  
 23- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 24- ENERGY CALCULATIONS SUBMITTED (RESCHECK):
 A) LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED.
 B) BLOWER DOOR TEST WILL BE REQUIRED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-26 Cont ID  
Sent By jgomez Date 2018-11-26 Time 16:04 Rev Time 0.00
Received By jgomez Date 2018-11-21 Time 16:30 Sent To  
Notes
2018-11-21 17:33:36NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 SEC. R401.3 FBC_RESIDENTIAL:
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE
 APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR
 WHEN OTHERWISE WARRANTED.
  
 SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A
 LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
  
 2- LOT SPLIT. ADDRESSING NEED TO BE COORDINATED BEFORE
 ISSUANCE OF PERMIT.
  
 3- BUILDING AREAS ARE NOT CLEAR AND SEEM TO BE
 INCORRECT. SQUARE FOOTAGE SHOWN UNDER SCOPE OF WORK
 DOESN'T MATCH SQUARE FOOTAGES SHOWN UNDER SITE DATA ON
 SHEET C-001 AND AREA CALCULATIONS SHOWN ON SHEET A-001.
 ALSO, COORDINATE WITH SQUARE FOOTAGE AREA SHOWN ON SITE
 PLAN ON SHEET A-001.REVISE AS REQUIRED TO MATCH. THE
 NET LIVING AREA SHOWN UNDER SITE DATA ON SHEET C-001
 DOESN'T MATCH THE FIRS FLOOR AND SECOND FLOOR NET
 LIVING AREA SHOWN ON SAME DRAWING. REVISE AS REQUIRED
 TO MATCH. CLEARLY ADD ALL AREA SQUARE FOOTAGES
 INCLUDING GARAGE, PORCHES, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
 NOTE: BUILDING VALUATION WILL BE VERIFIED ONCE THE
 TOTAL SQUARE FOOTAGES ARE CORRECTED.
  
 4- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE DOOR #2
 LEADING TO THE MAIN HOUSE SHOWING COMPLIANCE WITH THE
 SEC. R302.5.1 FBC-RESIDENTIAL. NOTE: PROVIDE SPECS FOR
 THE CORE OF THE DOOR.
  
 5- SPECIFY CARBON MONOXIDE ALARMS BY ALL THE BEDROOMS
 IN THE LOCATION REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL.
  
 6- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R307.1
 FBC-RESIDENTIAL.
  
 7- WINDOWS SIZE AND TYPE SHOWN ON THE WINDOW SCHEDULE
 DON'T MATCH THE WINDOWS SHOWN ON FLOOR PLANS AND
 EXTERIOR ELEVATIONS. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS. ALSO, PROVIDE COMPLETE
 INFORMATION FOR STAIRWAY WINDOW SYSTEM.
 NOTE: SAME APPLIES TO ALL DOORS.
  
 8- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: COORDINATE WITH ITEM #7 ABOVE. AND CLEARLY
 INDICATE THE WINDOW SILL HEIGHT OF SECOND FLOOR
 WINDOWS.
  
 9- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON THE
 EXTERIOR ELEVATIONS SEEM TO BE LOW FOR A TWO STORY
 BUILDING LOCATED IN EXPOSURE "C" AND A WIND SPEED OF
 175MPH AS SPECIFIED ON PLANS. . ALSO, SOME WINDOWS ARE
 LOCATED IN END ZONE NOT INTERIOR (SEE NOTE "A" ON
 FIGURE R301.2(7) FOR MIN. END ZONE DIMENSION). REVISE
 AS REQUIRED, INCLUDING THE GARAGE DOORS. SEC. R301.2.1
 FBCD-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE STONE VENEER SHOWN ON THE EXTERIOR
 ELEVATIONS TO SHOW COMPLIANCE WITH THE WIND RESISTANCE
 SEC. R703.1.2 FBC-RESIDENTIAL.
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 BALCONY FLOOR CONSTRUCTION. ALSO SPECIFY WATERPROOFING
 AND FINISH FLOOR. SEC. R301.1 FBC-RESIDENTIAL.
  
 12- CLARIFY ROOF VENTILATION INFORMATION SHOWN ON SHEET
 A-007. SPECIFY LOCATION OF VENTS INCLUDING THE VENTS
 ABOVE THE EAVE OR CORNICE VENTS. CLARIFY IF DESIGNING
 FOR 1/150 VENTILATION RATIO OR IF DESIGNING 1/300
 VENTILATION RATIO PER EXCEPTION OF SEC. R806.2
 FBC-RESIDENTIAL.
  
 13- PROVIDE SPECIFICATIONS FOR CEILING DWELLING-GARAGE
 SEPARATION SHOWING COMPLIANCE WITH TABLE R302.6
 FBC-RESIDENTIAL.
  
 14- PROVIDE COMPLETE FRAMING DETAIL AND SPECIFICATIONS
 FOR EXTERIOR WALL IN MASTER BATHROOM SHOWER AND FOR
 EXTERIOR WALL BY STAIRWAY. INCLUDE ALL FRAMING AROUND
 WINDOW OPENINGS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. NOTE: DETAIL 3/A-008ON SHEET A-008 AND WALL
 FRAMING & OPENINGS DETAIL ON SHEET A-009 DON'T MATCH.
 COORDINATE ALSO. SEC. R301.1 FBC-RESIDENTIAL.
  
 15- PROVIDE COMPLETE SPECIFICATIONS FOR 2X STRUCTURAL
 BUCK FOR DOORS AND WINDOWS. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: STRUCTURAL BUCK IS THE RESPONSIBILITY OF THE
 DESIGNER OR RECORD. PRODUCT APPROVAL IS ONLY FOR THE
 ATTACHMENT OF DOOR/WINDOW. REVISE DETAILS ON SHEET
 A-009.
  
 16- IT LOOKS LIKE THE SOIL TEST REPORT SUBMITTED WAS
 PERFORMED ON THE WRONG LOT. THIS LOT WAS SPLIT INTO TWO
 LOTS. THE PROPOSED HOUSE IS GOING TO BE BUILT ON THE
 LOT WHERE AN IN GROUND POOL WAS LOCATED AND WAS
 REMOVED. THE NEW LOT IS EAST OF THE HOUSE WHERE THE
 BORINGS WERE PERFORMED. PROVIDE SOIL TEST REPORT FOR
 THE CORRECT LOT. SEC. 107.2.1 CITY AMENDMENTS.
  
 17- SHEET S-001. PROVIDE SPECIFICATIONS FOR SPECIAL
 FOUNDATION "D". CLARIFY WHY THERE ARE TWO FOUNDATION
 "A"??.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 18- DETAIL 2/A-009 ON SHEET A-009. REVISE CONNECTORS.
 SP4 AND SPH4 ARE FOR 2X4 WALLS. THIS BEARING WALL ARE
 2X8. SEC. 107.2.1 CITY AMENDMENTS.
  
 19- SHEET 004:
 A) FLOOR PLAN SPECIFIES "CONNECTION BY BUILDER" GIRDER
 TRUSSES F7 1/2, F15, F1 AND BEAM Q. CONNECTION IS THE
 RESPONSIBILITY OF THE DESIGNER OF RECORD. PROVIDE
 COMPLETE DETAILS/SPECIFICATIONS FOR END CONNECTORS AT
 ALL THESE GIRDER TRUSSES. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) FRAMING PLAN SPECIFIES "BEARING WALL" BETWEEN TRUSS
 GIRDER F1 AND BEAM Q. FOUNDATION PLAN DOESN'T SOW ANY
 BEARING WALL. REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 C) LEDGER A AND LEDGER B SPECIFICATIONS DON'T MATCH
 SPECIFICATIONS SHOWN WALL SECTION 1-A-008. COORDINATE
 AS REQUIRED AND PROVIDE LEDGER (NAILER) SPECIFICATIONS
 FOR SECOND FLOOR PLYWOOD FLOORING WHERE THERE IS NOT
 FLOOR TRUSS(SEE NORTH WALL AND SOUTH WALL) SEC. R301.1
 FBC-RESIDENTIAL.
  
 20- PROVIDE DETAIL CONNECTION AT THE ENDS OF LVL BEAM
 SHOWN ON FRAMING PLAN ON SHEET S-005 AT THE BALCONY
 AREA . SEC. R301.1 FBC-RESIDENTIAL
  
 21- SHEET S-006. CLARIFY ROOF SHEATHING NAIL TYPE AND
 SPACING. THERE ARE 3 DIFFERENT AREAS ON SAME SHEET WITH
 DIFFERENT INFORMATION. COORDINATE "PLYWOOD SHEATHING
 NAILING SCHEDULE WALL AND ROOF", "FASTENER SCHEDULE"
 AND "DIAPHRAGM SCHEDULE" TABLES ON SAME SHEET. SEE SEC.
 R803.2.3.1 FBC-RESIDENTIAL FOR REQUIRED FASTENING AND
 REVISE AS REQUIRED. ALSO, COORDINATE WITH DETAIL D ON
 SHEET S-008.
  
 22- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE
 INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS.
 DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR FINISH
 FLOORING. NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO
 BE INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ZONES.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 DESIGNER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NEXT TO THE SPECIFIED CONNECTOR.
  
 D) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS/ELEVATIONS. NOTE: COORDINATE WITH ITEM #7 ABOVE.
  
 E) CASEMENT WINDOWS SIZE AS SPECIFIED ON WINDOW
 SCHEDULE. SEE PLANS/ELEVATIONS. NOTE: COORDINATE WITH
 ITEM #7 ABOVE.
  
 F) INSWING ENTRY DOORS WITH SIDELITES AND TRANSOM ABOVE
 AS SHOWN ON PLANS/ELEVATIONS. NOTE: COORDINATE WITH
 ITEM #7 ABOVE.
 NOTE: NOA 18-0503.06 SUBMITTED IS FOR OUTSWING ENTRY
 DOORS ONLY.
  
 G)WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 23- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 24- ENERGY CALCULATIONS SUBMITTED (RESCHECK):
 A) LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED.
 B) BLOWER DOOR TEST WILL BE REQUIRED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-24 Cont ID  
Sent By jpearson Date 2018-12-24 Time 09:29 Rev Time 0.00
Received By jpearson Date 2018-12-24 Time 09:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By jpearson Date 2018-10-30 Time 11:52 Rev Time 0.00
Received By jpearson Date 2018-10-30 Time 10:57 Sent To  
Notes
2018-10-30 11:52:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 54 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES AND CONFLICTS
 WITH NOTE IN ANOTHER AREA. PROVIDE CORRECTION. NEC
 406.12; FBC RE E4002.14
 2. AFCI PROTECTION SHOWN IN NOTE 58 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 3. RISER DIAGRAM SHOWS (3) 3/0 CONUCTORS TO FPL FROM
 METER. THIS WIRE SIZE IS NOT RATED AS REQUIRED THE
 SERVICE. PROVIDE CORRECTION. FBC RE E3603.1.1
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 5. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 6. IN MASTER BATH THE LIGHTING OVER THE TUB AND SHOWER
 APPEAR TO BE A MOUNTED LIGHT FIXTURE. NO PARTS OF
 CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR
 CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D); FBC
 RE E4003.11
 7. IN MASTER BATH, A GFCI PROTECTED RECEPTACLE OUTLET
 ON A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH
 BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D);
 FBC RE E3703.4, E3901.6
 8. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 9. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED
 GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL
 SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON
 THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE
 LEVEL ACCESS. THE SWITCH MUST BE LOCATED IN THE
 INTERIOR OF THE STRUCTURE TO CONTROL A LIGHTING OUTLET
 ON THE EXTERIOR. SWITCH IS CURRENTLY SHOWN ON THE
 EXTERIOR OF STRUCTURE. PROVIDE CORRECTION. NEC
 210.70(A)(2)(B), FBC RE E3903.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-03-05 Cont ID  
Sent By jgomez Date 2019-03-05 Time 11:32 Rev Time 0.00
Received By jgomez Date 2019-03-05 Time 08:08 Sent To I
Notes
2019-03-05 09:43:30DAVID BOWDEN REPLACED SHEET A-004 AND COORDINATED ALL
 PRODUCT APPROVALS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-23 Cont ID  
Sent By jgomez Date 2019-01-23 Time 15:46 Rev Time 0.00
Received By jgomez Date 2019-01-14 Time 15:32 Sent To I
Notes
2019-01-15 15:32:18RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-10 Cont ID  
Sent By jgomez Date 2019-01-10 Time 09:27 Rev Time 0.00
Received By jgomez Date 2019-01-10 Time 08:38 Sent To  
Notes
2019-01-10 08:38:55CONTRACTOR SUBMITTED PRODUCT APPROVAL FOR STAIRWAY
 WINDOW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-04 Cont ID  
Sent By jgomez Date 2019-01-04 Time 18:10 Rev Time 0.00
Received By jgomez Date 2018-12-13 Time 14:33 Sent To I
Notes
2018-12-14 14:33:46R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-29 Cont ID  
Sent By jesmith Date 2018-11-29 Time 09:04 Rev Time 0.00
Received By jesmith Date 2018-11-29 Time 09:04 Sent To  
Notes
2018-10-16 14:24:16R21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-11-26 Cont ID  
Sent By jgomez Date 2018-11-26 Time 09:02 Rev Time 0.00
Received By jgomez Date 2018-11-26 Time 09:02 Sent To  
Notes
2018-11-26 09:04:41$9,904.34 PAID. MU-2018-034795.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-11-05 Cont ID  
Sent By cmontell Date 2018-11-05 Time 13:42 Rev Time 0.00
Received By cmontell Date 2018-11-05 Time 13:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-29 Cont ID  
Sent By jesmith Date 2018-11-29 Time 08:26 Rev Time 0.00
Received By jesmith Date 2018-11-29 Time 08:19 Sent To  
Notes
2018-11-29 08:25:53APPROVED
 PROVISO
 1. ANY STUDOR (AIR ADMITTANCE VALVE) VENT SHALL BE
 ACCESSIBLE IN ACCORDANCE WITH THE MANUFACTURER'S
 RECOMMENDATIONS.
 2. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2019-03-05 Cont ID  
Sent By jgomez Date 2019-03-05 Time 11:16 Rev Time 0.00
Received By jgomez Date 2019-03-05 Time 11:16 Sent To  
Notes
2019-03-05 11:17:15BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) BALCONY
 UNDERLAYMENT THAT IS DESIGNED TO BE INSTALLED WITH
 FINISH FLOOR SPECIFIED ON PLANS. NOTE: FLINTASTIC
 MODIFIED BITUMEN ROOF SYSTEM PRODUCT APPROVAL
 FL16709-R4 SPECIFIED ON BALCONY FLOOR CONSTRUCTION
 DETAIL ON SHEET A-010 IS NOT GOOD FOR CERAMIC TILE.
  
  
 APPROVED:
 -NOA 17-0614.22 FOR POLYGLASS POLYSTICK UNDERLAYMENT.
 -NOA 15-0721.04 FOR ROOF TILE
 -NOA 17-0322.03 FOR ROOF TILE ADHESIVE AH-160

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-01-23 Cont ID  
Sent By jgomez Date 2019-01-23 Time 15:46 Rev Time 0.00
Received By jgomez Date 2019-01-23 Time 15:46 Sent To  
Notes
2019-01-23 15:46:521- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
  
 NOTE: BALCONY UNDERLAYMENT TO BE CLARIFIED ONCE THE
 FINISH FLOOR IS SPECIFIED. SEE BUILDING REVIEW
 COMMENTS.
  
  
  
 APPROVED:
 -NOA 17-0614.22 FOR POLYGLASS POLYSTICK UNDERLAYMENT.
 -NOA 15-0721.04 FOR ROOF TILE
 -NOA 17-0322.03 FOR ROOF TILE ADHESIVE AH-160

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-01-04 Cont ID  
Sent By jgomez Date 2019-01-04 Time 18:07 Rev Time 0.00
Received By jgomez Date 2019-01-04 Time 18:06 Sent To  
Notes
2019-01-04 18:06:501- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 NOTE: BALCONY UNDERLAYMENT TO BE CLARIFIED ONCE THE
 FINISH FLOOR IS SPECIFIED. SEE BUILDING REVIEW
 COMMENTS.
  
  
  
 APPROVED:
 -NOA 17-0614.22 FOR POLYGLASS POLYSTICK UNDERLAYMENT.
 -NOA 15-0721.04 FOR ROOF TILE
 -NOA 17-0322.03 FOR ROOF TILE ADHESIVE AH-160

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-11-26 Cont ID  
Sent By jgomez Date 2018-11-26 Time 15:36 Rev Time 0.00
Received By jgomez Date 2018-11-26 Time 15:36 Sent To  
Notes
2018-11-26 15:39:021- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE
 INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS.
 DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR FINISH
 FLOORING. NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO
 BE INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ZONES.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 APPROVED:
 -NOA 17-0614.22 FOR POLYGLASS POLYSTICK UNDERLAYMENT.
 -NOA 15-0721.04 FOR ROOF TILE
 -NOA 17-0322.03 FOR ROOF TILE ADHESIVE AH-160

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2019-01-17 Time   Rev Time 0.00
Received By pgreilic Date 2019-01-17 Time 13:23 Sent To B
Notes
2019-01-17 13:23:30LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-12-28 Time   Rev Time 0.00
Received By pgreilic Date 2018-12-28 Time 14:09 Sent To  
Notes
2018-12-28 14:09:121.) 25 FOOT FRONT SETBACK REQUIRED
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2018-10-30 Time   Rev Time 0.00
Received By pgreilic Date 2018-10-29 Time 15:51 Sent To  
Notes
2018-10-30 09:19:541.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]