Plan Review Details - Permit 18100669
Plan Review Stops For Permit 18100669
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-26 Cont ID  
Sent By rmcdouga Date 2018-11-26 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2018-11-13 Time 13:06 Sent To  
Notes
2018-11-14 13:06:34RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-17 Cont ID  
Sent By rmcdouga Date 2018-10-17 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2018-10-15 Time 13:42 Sent To I
Notes
2018-10-16 13:42:32REVISION ROUTED TO RMCDOUGAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-26 Cont ID  
Sent By rmcdouga Date 2018-11-26 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2018-11-26 Time 10:14 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-17 Cont ID  
Sent By rmcdouga Date 2018-10-17 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2018-10-17 Time 07:23 Sent To  
Notes
2018-10-17 08:04:02PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M 1602.3 PROVIDE BALANCED AIR RETURN AT THE
 MASTER BEDROOM SUITE. THE 10" DIAMETER TRANSFER DUCT
 FROM THE MASTER BEDROOM SUITE IS TOO SMALL. BASED ON
 FBCR-M1602.3 IT APPEARS THAT A 14" DIAMETER TRANSFER
 DUCT IS REQUIRED. SEE CODE REQUIREMENTS BELOW.
 M1602.3 BALANCED RETURN AIR. RESTRICTED RETURN AIR
 OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL
 ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE
 RETURN GRILL OR WHEN CEILING SPACES ARE USED AS RETURN
 PLENUMS AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE
 PORTION OF THE RETURN PLENUM TO ANOTHER. PROVISIONS
 SHALL BE MADE IN BOTH RESIDENTIAL AND COMMERCIAL
 BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND PRESSURE
 DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS WHERE RETURNS ARE
 CENTRALLY LOCATED SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) OR LESS. PRESSURE DIFFERENTIALS ACROSS FIRE
 WALLS IN CEILING SPACE PLENUMS SHALL BE LIMITED TO 0.01
 INCH WC (2.5 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR
 AIR TRANSFER PATHWAYS FROM THE HIGH PRESSURE ZONE TO
 THE LOW ZONE.
 EXCEPTIONS:
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE.
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (32 258
 MM2) (OF GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR
 SIZING THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH (25 MM) UNDERCUTTING OF DOORS TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
 2) THE SIGNED AND SEALED PLANS THAT WERE SUBMITTED HAVE
 BEEN CHANGED USING WHITEOUT. THIS IS NOT ACCEPTABLE PER
 CITY AMENDMENTS 107.2.1.3. HAVE THE ARCHITECT REDRAW
 THE PLANS WITH THE CORRECTIONS AND SIGN AND SEAL THEM
 AS REQUIRED BY FAC 61G1-16.003
  
  