Plan Review Details - Permit 18100657
Plan Review Stops For Permit 18100657
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-05 Cont ID  
Sent By fgiaquin Date 2018-12-05 Time 05:39 Rev Time 0.00
Received By fgiaquin Date 2018-12-05 Time 05:10 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-19 Cont ID  
Sent By fgiaquin Date 2018-11-19 Time 05:34 Rev Time 0.00
Received By fgiaquin Date 2018-11-19 Time 05:20 Sent To I
Notes
2018-11-19 05:33:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INITAL PERMIT FEE SUBMITTED WAS $20000. CONTRACTOR
 WAS ASKED FOR SIGNED CONTRACT. SCOPE OF WORK PROVIDED
 IN CONTRACT DOES NOT MATCH SCOPE OF WORK ON PLANS.
 PROVIDE ACCURATE PLANS AND AN UP TO DATE CONTRACT.
 CONTRACT SAYS SA- X10, SB X2
  
 PLANS SAY SB X1, SA X5, CA X10. FBC 107.2.1
  
 2. NO LOAD CALCULATION PROVIDED, NO OCP PROVIDED FOR
 PANEL FEEDING SITE LIGHTS., ACCURATE LOAD CALCULATION
 INCLUDING ALL LOADS. NEC 220, FBC 107.2.1
  
 3. PROVIDE EXTERIOR AUTOMATIC LIGHTING CONTROL FOR SITE
 LIGHTING AS PER FBC CE 405.2.4 MUST BE ASTRONOMICAL
 TIME CLOCK WITH 10/HR BATTERY BACKUP. A NOTE ON DRAWING
 WILL SUFFICE.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By fgiaquin Date 2018-10-29 Time 06:27 Rev Time 0.00
Received By fgiaquin Date 2018-10-29 Time 05:49 Sent To I
Notes
2018-10-29 06:27:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. NOT ENOUGH INFORMATION ON ELECTRICAL DRAWING.
 PROVIDE WIRE SIZE, CONDUIT SIZE, AND OCP FOR SITE
 LIGHTING. IF ON MASTER SET OF DRAWING REFERENCE
 APPLICABLE PAGES IN RESPONSE TO PLAN REVIEW COMMENTS.
 FBC 107.2.1
  
 3. VALUE LOW, PROVIDE COPY OF CONTRACT. SIGNED BY BOTH
 OWNER AND ELECTRICAL CONTRACTOR QUALIFIER. VALUE TO
 INCLUDE ALL MATERIALS, LABOR, ENGINEERING COSTS ETC.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 4. SATISFY COMMENTS FROM ZONING DEPARTMENT.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-05 Cont ID  
Sent By fgiaquin Date 2018-12-05 Time 05:39 Rev Time 0.00
Received By fgiaquin Date 2018-11-26 Time 16:17 Sent To  
Notes
2018-11-27 16:18:09RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-19 Cont ID  
Sent By fgiaquin Date 2018-11-19 Time 05:34 Rev Time 0.00
Received By fgiaquin Date 2018-11-09 Time 14:03 Sent To  
Notes
2018-11-13 14:03:53RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-29 Cont ID  
Sent By fgiaquin Date 2018-10-29 Time 06:27 Rev Time 0.00
Received By fgiaquin Date 2018-10-15 Time 11:30 Sent To  
Notes
2018-10-16 11:30:19ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-12-04 Cont ID  
Sent By mcruz Date 2018-12-04 Time 13:53 Rev Time 0.00
Received By mcruz Date 2018-12-04 Time 13:51 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-15 Cont ID  
Sent By mcruz Date 2018-11-15 Time 11:12 Rev Time 0.00
Received By mcruz Date 2018-11-15 Time 11:09 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-26 Cont ID  
Sent By mcruz Date 2018-10-26 Time 11:35 Rev Time 0.00
Received By mcruz Date 2018-10-26 Time 11:23 Sent To E
Notes
2018-10-26 11:35:53ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) SHOW LIGHTING FROM PALM BEACH LAKES.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  