Plan Review Stops For Permit 18100612 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-12-07 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-12-07 |
Time |
06:00 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-12-07 |
Time |
05:09 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-11-27 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-11-27 |
Time |
05:36 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-11-27 |
Time |
05:19 |
Sent To |
I |
|
Notes |
2018-11-27 05:24:18 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. AS PER LAST PLAN REVIEW COMMENTS: ELECTRICAL PLAN IS | | REQUIRED TO BE DESIGNED AND SIGNED/SEALED BY A DESIGN | | PROFESSIONAL OR SIGNED BY THE ELECTRICAL CONTRACTOR | | QUALIFIER. PROVIDE CORRECTION. FS 471.003(2)(H); | | 471.025; WPB FBC 107.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-10-19 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2018-10-19 |
Time |
07:15 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-10-19 |
Time |
07:15 |
Sent To |
M |
|
Notes |
2018-10-19 07:15:05 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. DICTATE ON PLAN WHAT HAS BEEN CHANGED/REVISED WITH | | "REVISION BUBBLES" WHICH IS NORMAL PRACTICE WITH | | REVISIONS. FBC 107.2.1 | | | | 2. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND | | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE | | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS | | 471.003(2)(H); 471.025; WPB FBC 107.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2018-12-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-12-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-12-06 |
Time |
15:18 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-11-14 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-11-14 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-11-14 |
Time |
16:46 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-10-16 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-10-16 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-10-16 |
Time |
13:17 |
Sent To |
E |
|
Notes |
2018-10-16 13:20:55 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS ON ANY PLAN SHEET OF WHAT | | IS REVISED. | | | | PER NFPA 1 | | | | 1.14 PLAN REVIEW. | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | PLEASE REVIEW AND PROVIDE THE LOCATION AND DEVICES THAT | | REPRESENT AS-BUILTS. | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3)ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-12-07 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-12-07 |
Time |
06:00 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-11-30 |
Time |
14:19 |
Sent To |
|
|
Notes |
2018-12-03 14:20:02 | RESUB OF REVISION ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-11-27 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-11-27 |
Time |
05:36 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-11-08 |
Time |
13:39 |
Sent To |
|
|
Notes |
2018-11-09 13:39:12 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-10-23 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-10-12 |
Time |
13:27 |
Sent To |
|
|
Notes |
2018-10-15 13:27:58 | REVISION ROUTED TO FIRE INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2018-10-23 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2018-10-23 |
Time |
08:55 |
Sent To |
I |
|
Notes |
|
|