Plan Review Details - Permit 18100566
Plan Review Stops For Permit 18100566 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-11-15 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-11-15 |
Time |
13:42 |
Sent To |
|
|
Notes |
2018-11-15 13:46:11 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 2ND REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | COMMENTS FROM 1ST REVIEW HAVE NOT BEEN ADDRESSED. SEE | | BELOW. | | | | 1. ACCESSORY STRUCTURES ARE NOT PERMITTED ON VACANT | | LOTS PER THE CITY OF WEST PALM BEACH MUNICIPAL CODE. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. | | | | MUNI-CODE | | | | PERMITTED USES | | CHPT. 94 ZONING AND LAND DEVELOPMENT REGULATIONS | | | | ARTICLE 10 SUPPLEMENTAL DISTRICT REGULATIONS | | SECTION 94-304 ACCESSORY STRUCTURES. | | (A) GENERAL PROVISIONS. | | (1) ACCESSORY STRUCTURES MUST BE CONSTRUCTED | | SIMULTANEOUSLY WITH, OR FOLLOWING THE CONSTRUCTION OF | | THE MAIN BUILDING AND SHALL NOT BE OCCUPIED UNTIL AFTER | | THE PRINCIPAL STRUCTURE HAS RECEIVED A CERTIFICATE OF | | OCCUPANCY. NO ACCESSORY STRUCTURE SHALL BE CONSTRUCTED | | OR ESTABLISHED ON ANY LOT PRIOR TO THE TIME OF | | CONSTRUCTION OR RELOCATION OF THE PRINCIPAL STRUCTURE | | TO WHICH IT IS ACCESSORY. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-10-30 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-10-30 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-10-30 |
Time |
14:18 |
Sent To |
|
|
Notes |
2018-10-30 15:55:48 | BUILDING PLAN REVIEW | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | 1ST REVIEW | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ACCESSORY STRUCTURES ARE NOT PERMITTED ON VACANT | | LOTS PER THE CITY OF WEST PALM BEACH MUNICIPAL CODE. | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. | | | | MUNI-CODE | | | | PERMITTED USES | | CHPT. 94 ZONING AND LAND DEVELOPMENT REGULATIONS | | | | ARTICLE 10 SUPPLEMENTAL DISTRICT REGULATIONS | | SECTION 94-304 ACCESSORY STRUCTURES. | | (A) GENERAL PROVISIONS. | | (1) ACCESSORY STRUCTURES MUST BE CONSTRUCTED | | SIMULTANEOUSLY WITH, OR FOLLOWING THE CONSTRUCTION OF | | THE MAIN BUILDING AND SHALL NOT BE OCCUPIED UNTIL AFTER | | THE PRINCIPAL STRUCTURE HAS RECEIVED A CERTIFICATE OF | | OCCUPANCY. NO ACCESSORY STRUCTURE SHALL BE CONSTRUCTED | | OR ESTABLISHED ON ANY LOT PRIOR TO THE TIME OF | | CONSTRUCTION OR RELOCATION OF THE PRINCIPAL STRUCTURE | | TO WHICH IT IS ACCESSORY. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-11-15 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-11-07 |
Time |
13:13 |
Sent To |
|
|
Notes |
2018-11-08 13:13:25 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-10-30 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2018-10-30 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2018-10-22 |
Time |
15:24 |
Sent To |
|
|
Notes |
2018-10-23 15:24:48 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2018-11-14 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-11-14 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-11-14 |
Time |
16:00 |
Sent To |
B |
|
Notes |
2018-11-14 16:01:32 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | 1) PURSUANT TO SEC. 94-304(A)(1) ACCESSORY STRUCTURES | | MUST BE CONSTRUCTED SIMULTANEOUSLY WITH, OR FOLLOWING | | THE CONSTRUCTION OF THE MAIN BUILDING AND SHALL NOT BE | | OCCUPIED UNTIL AFTER THE PRINCIPAL STRUCTURE HAS | | RECEIVED A CERTIFICATE OF OCCUPANCY. NO ACCESSORY | | STRUCTURE SHALL BE CONSTRUCTED OR ESTABLISHED ON ANY | | LOT PRIOR TO THE TIME OF CONSTRUCTION OR RELOCATION OF | | THE PRINCIPAL STRUCTURE TO WHICH IT IS ACCESSORY. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ | | ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1442 | | E-MAIL: [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-10-25 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-10-25 |
Time |
16:56 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-10-25 |
Time |
16:27 |
Sent To |
B |
|
Notes |
2018-10-25 16:56:47 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | 1) INDICATE ON THE SURVEY THE LOCATION OF THE PROPOSED | | CONTAINERS. | | 2) INDICATE THE SETBACK DIMENSION FROM THE CONTAINERS | | TO ALL PROPERTY LINES. | | 3) IS THE PROPERTY VACANT? | | 4) WHAT IS THE PURPOSE OF THE CONTAINERS? | | 5) RESPOND TO COMMENTS IN WRITING. | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | GENERATE ADDITIONAL COMMENTS. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ | | ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1442 | | E-MAIL: [email protected] |
|
|
|