Plan Review Details - Permit 18100547
Plan Review Stops For Permit 18100547
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-20 Cont ID  
Sent By jwitmer Date 2018-11-20 Time 14:19 Rev Time 0.00
Received By jwitmer Date 2018-11-20 Time 13:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-28 Cont ID  
Sent By jpearson Date 2018-10-28 Time 13:20 Rev Time 0.00
Received By jpearson Date 2018-10-28 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-15 Cont ID  
Sent By pleduc Date 2018-10-15 Time   Rev Time 0.00
Received By pleduc Date 2018-10-15 Time 11:07 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-02-04 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-31 Time 12:51 Sent To  
Notes
2019-02-01 12:51:36RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-20 Cont ID  
Sent By cpuell Date 2018-11-20 Time 14:36 Rev Time 0.00
Received By cpuell Date 2018-10-11 Time 16:00 Sent To  
Notes
2018-10-12 16:00:41B32

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-02-04 Cont ID  
Sent By ccole Date 2019-02-04 Time 16:30 Rev Time 0.00
Received By ccole Date 2019-02-04 Time 16:30 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-08 Cont ID  
Sent By ccole Date 2018-11-08 Time 10:05 Rev Time 0.00
Received By ccole Date 2018-11-08 Time 09:22 Sent To  
Notes
2018-11-08 10:18:491ST REVIEW FBC-2017 MECHANICAL
 REVISION PERMIT #18100547
 11/8/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: THE O/A INTAKES ON THE WEST SIDE OF THE
 BUILDING ARE EXTENDING OUT FROM THE WALL AS SHOWN ON
 THE PLAN WHICH WILL REQUIRE ADDITIONAL DETAILS SHOWING
 HOW THEY WILL BE SUPPORTED AND ALSO HOW THE "WALL
 LOUVERS" THAT ARE CALLED OUT WILL BE INSTALLED- SECTION
 304.1 FBC M.
  
 2) M1.1: THE LOCATION OF THE O/A INTAKES APPEAR TO BE
 WITHIN 10' OF THE PARKING LOT WHICH IS PROHIBITED PER
 SECTION 401.4 FBC M.
  
 3) M1.1: CLARIFY HOW THE SUPPLY AIR FROM ROOMS 111,
 112, & 118 IS BEING RETURNED TO THE AIR HANDLERS.
 PLEASE NOTE THAT CORRIDORS SHALL BE USED AS A RETURN
 DUCT- SECTION 601.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-08 Cont ID  
Sent By gjohnson Date 2018-11-08 Time 08:56 Rev Time 0.00
Received By jesmith Date 2018-11-08 Time 08:52 Sent To  
Notes
2018-11-08 08:56:43REVISION REVIEW:
 APPROVED
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715