Plan Review Details - Permit 18100491
Plan Review Stops For Permit 18100491
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-08 Cont ID  
Sent By cthroop Date 2018-11-08 Time 08:55 Rev Time 0.00
Received By cthroop Date 2018-11-08 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By shill Date 2018-10-15 Time 08:26 Rev Time 0.00
Received By shill Date 2018-10-15 Time 08:26 Sent To  
Notes
2018-10-15 08:26:52****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, SCOPE NOT CLEAR. IS THE ROOF HATCH
 REPLACING AN EXISTING ROOF HATCH? ARE SKYLIGHTS
 REPLACING EXISTING OR NEW?
  
 2. FBC B 1609, REVISE PLAN TO SHOW LOCATION OF ROOF
 HATCH AND SKYLIGHTS. CLEARLY INDICATE IN WHICH ZONE
 THEY ARE PROPOSED.
  
 3. FBC B 1609, THE ASSEMBLY SELECTED HAS A DESIGN
 PRESSURE LIMITATION OF -60PSF. PROVIDE CALCULATIONS FOR
 ZONES 2 AND 3 FASTENING, PREPARED BY A DESIGN
 PROFESSIONAL AS REQUIRED BY THE PRODUCT APPROVAL.
  
 4. FBC 107, PROVIDE THE PAGES OF THE PRODUCT APPROVAL
 WHICH APPLY TO ALL ASSEMBLIES.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-08 Cont ID  
Sent By cthroop Date 2018-11-08 Time 08:55 Rev Time 0.00
Received By cthroop Date 2018-10-23 Time 11:24 Sent To  
Notes
2018-10-24 11:25:07RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-15 Cont ID  
Sent By shill Date 2018-10-15 Time 08:26 Rev Time 0.00
Received By shill Date 2018-10-10 Time 13:49 Sent To  
Notes
2018-10-11 13:49:19SHILL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved