Plan Review Details - Permit 18100432
Plan Review Stops For Permit 18100432
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-11-19 Cont ID  
Sent By lcrespo Date 2018-11-19 Time 15:28 Rev Time 0.00
Received By lcrespo Date 2018-11-19 Time 15:28 Sent To  
Notes
2018-11-19 15:29:5111/19/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-10-12 Cont ID  
Sent By lcrespo Date 2018-10-12 Time 18:03 Rev Time 0.00
Received By lcrespo Date 2018-10-12 Time 18:03 Sent To  
Notes
2018-10-12 18:04:1210/10/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT MANUFACTURERS SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION,
 2017 FBC FUEL GAS RES. SEC. G2421.1.
 2. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
 3. GAS APPLIANCES SHALL BE LISTED AND LABELED, THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ON-SITE AT THE TIME OF INSPECTION, 2017 FBC
 FUEL GAS RES. SEC. G2413.2 AND G2404.3.
 4. THERE IS AN EXISTING POOL HEATER AND NO PERMIT HAS
 BEEN SUBMITTED, THIS WILL BE TREATED AS A NEW PERMIT
 FOR THIS EQUIPMENT SO PLEASE SUBMIT MANUFACTURERS
 SPECIFICATIONS FOR POOL HEATER AND THE MANUFACTURER'S
 SPECIFICATIONS FOR THE POOL HEATER SHALL BE ON SITE.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS RES SECS. G2413.4.1, G2413.4.2.
 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 7. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
 8. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION BY A LICENSED CONTRACTOR AND SHALL HAVE ITS
 OWN CIRCUIT, WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-19 Cont ID  
Sent By lcrespo Date 2018-11-19 Time 15:28 Rev Time 0.00
Received By lcrespo Date 2018-11-09 Time 14:05 Sent To  
Notes
2018-11-13 14:05:53RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-12 Cont ID  
Sent By lcrespo Date 2018-10-12 Time 18:03 Rev Time 0.00
Received By lcrespo Date 2018-10-09 Time 14:21 Sent To  
Notes
2018-10-10 14:22:09PLUMB<5K