2018-10-12 18:04:12 | 10/10/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SUBMIT MANUFACTURERS SPECIFICATIONS FOR THE PRESSURE |
| REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION, |
| 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| 2. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| 3. GAS APPLIANCES SHALL BE LISTED AND LABELED, THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ON-SITE AT THE TIME OF INSPECTION, 2017 FBC |
| FUEL GAS RES. SEC. G2413.2 AND G2404.3. |
| 4. THERE IS AN EXISTING POOL HEATER AND NO PERMIT HAS |
| BEEN SUBMITTED, THIS WILL BE TREATED AS A NEW PERMIT |
| FOR THIS EQUIPMENT SO PLEASE SUBMIT MANUFACTURERS |
| SPECIFICATIONS FOR POOL HEATER AND THE MANUFACTURER'S |
| SPECIFICATIONS FOR THE POOL HEATER SHALL BE ON SITE. |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| GAS RES SECS. G2413.4.1, G2413.4.2. |
| 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 7. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC. |
| 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| 8. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION BY A LICENSED CONTRACTOR AND SHALL HAVE ITS |
| OWN CIRCUIT, WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |