2018-12-13 11:32:04 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18100354 |
| ADD: 3215 S DIXIE HWY |
| CONT: TBD/ TO BE DETERMINED |
| TEL: ???????????? |
| E-MAIL: CONTACT: |
| [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: TUES. DEC. 11/ 2018 |
| ACTION: DENIED |
| |
| |
| 1) BEFORE A PERMIT CAN BE ISSUED EITHER A CERTIFIED |
| BUILDING CONTRACTOR (CBC), A CERTIFIED GENERAL |
| CONTRACTOR (CGC) OR A PALM BEACH COUNTY LICENSED |
| CONTRACTOR WITH APPROPRIATE LICENSURE WILL NEED TO |
| APPLY FOR PERMIT WITH QUALIFIER?S SIGNATURE ON THE |
| PERMIT APPLICATION. 105.3.1 ACTION ON APPLICATION, 2017 |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 2) THE PERMIT FEE WAS SCRATCHED THROUGH AND A NEW |
| REDUCED VALUE WAS ASSIGNED TO THE PROJECT. THE |
| CALCULATED VALUE OF THE PROJECT IS $961,934.00 DOLLARS |
| IN VALUE. |
| 109.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE PROVIDE AN ITEMIZED LIST ON THE CONTRACTORS |
| LETTER HEAD AND SUBTRACT THESE LINE ITEMS AND THEIR |
| VALUE FROM THE OVERALL BUILDING VALUE STATED ON THE |
| PERMIT APPLICATION FOR THIS PROJECT. THE REMAINING |
| BALANCE WILL BE AFFECTIVELY THE VALUE OF THE BUILDING |
| YOU WILL BE PAYING FOR THIS PERMIT. THE BUILDING |
| DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR THE VALUE |
| OF THESE SUB-PERMITS NOT COVERED UNDER THE PRIME OR |
| MASTER PERMIT. |
| |
| 3) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| DEVELOPMENT. |
| (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected] |
| 4) SHEET 01-CS-1 COVER SHEET. THE COVER SHEET BUILDING |
| CODE INFO: |
| 4A) THE BUILDING CODE INFORMATION INDICATES THE |
| OCCUPANCY TYPE AS A GROUP S-2 OCCUPANCY, IS THIS USE |
| FOR STORAGE OF AUTOMOBILES OR IS THIS USEAGE FOR |
| AUTOMOBILE REPAIR SHOP. THE LIFE SAFETY PLAN SHOWS A |
| LOUNGE IN THIS BUILDING, IT WOULD APPEAR THIS MAYBE A |
| MOTOR VEHICLE SHOWROOM WHICH WOULD MAKE THE OCCUPANCY |
| TYPE BUSINESS, SEE 2017 FBC-B 304.1. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED TO DETERMINE |
| OCCUPANCY TYPE. |
| 4B) LIST OF STRUCTURAL MATERIALS OF BUILDING. BUILDING |
| CONSTRUCTION TYPE LISTED IS TYPE II-A. PLEASE REVIEW IN |
| THE 2017 FBC-B TABLE 601, PRIMARY STRUCTURAL FRAME, |
| THIS FRAMING MEMBER IS MISSING FROM THE STRUCTURAL |
| ELEMENTS THIS WOULD BE FOR BOTH WALL AND ROOF FRAMING |
| MEMBERS. FOR A TYPE II-A BUILDING 1 HOUR |
| FIRE-RESISTANCE RATING IS REQUIRED FOR THIS BUILDING |
| ELEMENT. THE STRUCTURAL MATERIALS LIST ALSO LIST ROOF |
| SUPPORTING STRUCTURE/ UNPROTECTED. PLEASE REFER BACK TO |
| TABLE 601 PRIMARY STRUCTURAL FRAME REQUIRES 1 HOUR FIRE |
| RESISTANCE RATING WHEREAS UNDER THE HEADING ROOF |
| CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS HOUR WITH |
| FOOTNOTES B & C. PLEASE PROVIDE THE MEAN ROOF HEIGHT. |
| PLEASE ALSO SEE FOOTNOTE (F) NOT LESS THAN THE |
| FIRE-RESISTANCE RATING AS REFERENCED IN SECTION 704.10 |
| 704.10 EXTERIOR STRUCTURAL MEMBERS. LOAD-BEARING |
| STRUCTURAL MEMBERS LOCATED WITHIN THE EXTERIOR WALLS OR |
| ON THE OUTSIDE OF A BUILDING OR STRUCTURE SHALL BE |
| PROVIDED WITH THE HIGHEST FIRE-RESISTANCE RATING AS |
| DETERMINED IN ACCORDANCE WITH THE FOLLOWING: |
| 1 .AS REQUIRED BY TABLE 601 FOR THE TYPE OF BUILDING |
| ELEMENT BASED ON THE TYPE OF CONSTRUCTION OF |
| THE BUILDING; |
| 2. AS REQUIRED BY TABLE 601 FOR EXTERIOR BEARING WALLS |
| BASED ON THE TYPE OF CONSTRUCTION; AND |
| 3. AS REQUIRED BY TABLE 602 FOR EXTERIOR WALLS BASED ON |
| THE FIRE SEPARATION DISTANCE. |
| |
| 4C) PLEASE PROVIDE A SURVEY WITH THE PROPOSED BUILDING |
| LAYOUT WITH DIMENSIONS TO THE PROPERTY LINES AND |
| DISTANCE BETWEEN THE EXISTING BUILDING AND THE PROPOSED |
| BUILDING. PLEASE ALSO PROVIDE AN ASSUMED PROPERTY LINE |
| BETWEEN THE 2 BUILDINGS WITH DISTANCE FROM BOTH |
| BUILDINGS TO THE ASSUMED PROPERTY LINE. |
| PROVIDE FOR THE WEST EXPOSURE OF THE EXISTING BUILDING |
| THE WALL AREA AND AREA OF UNPROTECTED OPENINGS AND THE |
| PERCENTAGE OF OPENINGS. PLEASE ALSO INDICATE IF THE |
| EXISTING BUILDING IS FIRE SPRINKLERED? FOR THE NEW |
| BUILDING PLEASE PROVIDE FOR THE EASTERN EXPOSURE OF THE |
| BUILDING THE WALL AREA AND AREA OF UNPROTECTED OPENINGS |
| AND THE PERCENTAGE OF OPENINGS. |
| 2017 FBC-B TABLE 602 & TABLE 705.8 ALLOWABLE OPENINGS |
| BASED ON FIRE SEPARATION DISTANCE. |
| |
| 4D) THE COVERSHEET INDICATES UNDER THE CONSTRUCTION |
| TYPE II-A (SI); 156,000 SF ALLOWABLE THIS IS WITH FIRE |
| SPRINKLER INCREASES AND ON THE LIFE SAFETY SHEET THE |
| SEPARATION OF EXITS TAKEN AT 1/3 THE DIAGONAL DISTANCE |
| IS ALSO TAKEN WHEN THERE ARE FIRE SPRINKLERS. THE LIFE |
| SAFETY PLAN ALSO STATES THAT FIRE SPRINKLERS ARE |
| REQUIRED BUT NO FIRE SPRINKLER PLANS WERE PROVIDED. |
| 2017 W. P. B. AMENDMENTS TO CHAPTER 1. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| SCHEMATIC FIRE SPRINKLERS |
| PRE-ENGINEERED SYSTEMS |
| FLORIDA ADMINISTRATIVE CODE 61G15-32.003 COMMON |
| REQUIREMENTS FOR FIRE PROTECTION ENGINEERING |
| |
| 5) LIFE SAFETY PLAN: |
| 5A) SAME COMMENT AS 4A. THE BUILDING CODE INFORMATION |
| INDICATES THE OCCUPANCY TYPE AS A GROUP S-2 OCCUPANCY, |
| IS THIS USE FOR STORAGE OF AUTOMOBILES OR IS THIS |
| USEAGE FOR AUTOMOBILE REPAIR SHOP. THE LIFE SAFETY PLAN |
| SHOWS A LOUNGE IN THIS BUILDING, IT WOULD APPEAR THIS |
| MAYBE A MOTOR VEHICLE SHOWROOM WHICH WOULD MAKE THE |
| OCCUPANCY TYPE BUSINESS, SEE 2017 FBC-B 304.1. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED TO |
| DETERMINE OCCUPANCY TYPE. THE LIFE SAFETY REQUIREMENTS |
| MAY CHANGE. |
| |
| 5B) PLEASE NOTE THE BUILDING CONSTRUCTION TYPE ON THIS |
| SHEET IS LISTED AS TYPE II-B NOT II-A AS ON THE |
| COVERSHEET. DISCREPANCY IN PLANS. 107.2.1.2. |
| |
| 5C) BUILDING HEIGHT NEEDS TO BE GIVEN AT THE MEAN ROOF |
| HEIGHT. 2017 FBC-B SECTION TABLE 1609.7(2) ADJUSTMENT |
| FACTORS FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF |
| HEIGHT FOR THE BUILDING. |
| |
| 5D) NOTE: OCCUPANCY LOADS MAY CHANGE ON OCCUPANCY TYPE |
| FBC-B TABLE 1004.1.2. |
| |
| 6) 11-A-1-1 TOILET ROOM: |
| |
| 6A) DETAIL # 1. THE ACCESSIBLE SHOWER IS SHOWN TO BE |
| 3-0 FEET X 3-0 FEET AND THE WALL DIRECTLY BEHIND THE |
| SEAT BEING 3 FOOT 2 INCHES IN LENGTH. PLEASE NOTE AS |
| DEPICTED THE SEAT DOES NOT EXTEND TO THE FRONT OF THE |
| SHOWER ENCLOSURE. SECTION 610.3 OF THE 2017 |
| FBC-ACCESSIBILITY CODE REQUIRES THE SEAT TO BE WITHIN 3 |
| INCHES OF THE COMPARTMENT ENTRY FOR TRANSFER TYPE |
| SHOWERS. |
| |
| 6B) DETAIL # 8. THE PLANS INDICATE THE GRAB BAR TO BE |
| 34 INCHES TO THE TOP OF THE GRAB BAR. THERE IS A |
| SECONDARY NOTE INDICATING 33 TO 36 INCHES TO CENTER |
| ALLOW. SINCE THE 2010 FBC-B ACCESSIBILITY CODE REQUIRES |
| THE POSITION OF THE GRAB BAR TO BE MEASURED FROM THE |
| TOP OF THE GRIPPING SURFACE, NOT CENTERLINE. ACCESS. |
| CODE 609.4. GRAB BARS SHALL BE INSTALLED IN A |
| HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36 |
| INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| TO THE TOP OF THE GRIPPING SURFACE? |
| |
| 6C) DETAIL # 8. PLEASE NOTE THE MIRROR AS DEPICTED IS |
| MEASURED FROM THE BOTTOM OF THE MIRROR FRAME NOT THE |
| BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 6D) DETAILS 4 & 7 SHOW A COUNTER TOP WITH OVERHANG THAT |
| CAN BE USED FOR CONSUMPTION OF EITHER FOOD OR DRINK. |
| 2017 FBC-ACCESS. CODE WHERE CONSUMPTION OF FOOD OR |
| DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND |
| STANDING SPACES AT THE DINING SURFACES SHALL COMPLY |
| WITH 902. |
| |
| 6D)(1)) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| COUNTERS, AND WHERE COVERED BY THE ABA SCOPING |
| PROVISIONS, EMPLOYEE WORK STATIONS. |
| |
| 6D)(2) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 6D)(3) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 7) SHEET 12-A-1-0 FLOOR PLAN. |
| |
| 7A) PLEASE NOTE THE ENVELOPE COMPLIANCE CERTIFICATE |
| VERSES SHEET 14-A-3.0 EXTERIOR ELEVATIONS DOOR AND |
| WINDOW SCHEDULE. PLEASE NOTE FOR THE EAST ELEVATION IN |
| THE ENVELOPE COMPLIANCE CERTIFICATE DOOR 1 & 2 ARE BOTH |
| LISTED AS 80 SQ. FT. WHEREAS THE EXTERIOR DOOR SCHEDULE |
| LIST THE ROLL-UP DOOR TO BE 10 FEET X 14 FEET OR 140 |
| SQ. FT. PLEASE CORRECT THE DISCREPANCY BETWEEN THE 2 |
| DOCUMENTS. 107.2.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 7B) SHEETS 12-A-1-0 ARCHITECTURAL FLOOR PLAN, SHEET 55 |
| THE LIFE SAFETY FLOOR PLAN BOTH SHOW TO ROLL-UP GARAGE |
| DOORS WHEREAS SHEET 28SS-E2 FLOOR PLAN ONLY INDICATE |
| THE 2 FRAMED OPENINGS 10? X 14? OPENINGS IN THE |
| ACCESSORY SCHEDULE. DISCREPANCY IN PLANS, ADDITIONAL |
| INFORMATION IS REQUIRED. 107.2.1.2. |
| |
| 7C) SHEET 22SS-E2 STRUCTURAL FLOOR PLAN UNDER THE |
| HEADING OF COVERINGS INDICATES THE ROOF AND COLOR TO BE |
| TBD (TO BE DETERMINED) SIGNATURE 300 COLOR, PLEASE |
| PROVIDE THE ROOF COLOR AND COMPLIANCE WITH AT HIGH |
| ALBEDO ROOF REQUIREMENT FOUND WITHIN THE ENVELOPE |
| COMPLIANCE CERTIFICATE PAGE 1 OF 2, ENVELOPE ASSEMBLIES |
| FOOTNOTE (D): |
| |
| 7C)(1) 3-YEAR AGED SOLAR REFLECTIVE VALUE > = 0.55 |
| THERMAL EMITTANCE |
| |
| 7C)(2) 3-YEAR AGED SOLAR REFLECTIVE VALUE > = 0.75. |
| |
| 7D) WITHIN THE ENVELOPE COMPLIANCE CERTIFICATE PAGE 1 |
| OF 21, ENVELOPE ASSEMBLIES FOOTNOTE ( C ) SHOW |
| COMPLIANCE WITH: |
| ENVELOPE COMPLIANCE CERTIFICATE, ENVELOPE CERTIFICATE |
| FOOTNOTE ( C ) THERMAL SPACER BLOCK WITH R-3.5 MUST BE |
| INSTALLED ABOVE THE PURLIN/ BATT, AND THE ROOF DECK |
| SECURED TO THE PURLINS. PLEASE SHOW HOW COMPLIANCE WILL |
| BE ACHIEVED. 107.2.1.2. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 7E) WITHIN THE ENVELOPE COMPLIANCE CERTIFICATE PAGE 1 |
| OF 21, ENVELOPE ASSEMBLIES THE EAST WALL DOOR 1 & 2 |
| BOTH INDICATE THEY ARE INSULATED, THE SUBMITTED NOA |
| 18-0801.01 REVIEWED BY THE ARCHITECT DOES NOT INDICATE |
| THE INSULATION NOR THE PROPOSED U-FACTOR. SHOW |
| COMPLIANCE WITH THE VALUES PROVIDED WITH IN THE ENERGY |
| REPORT. 107.2.1.2 ADDITIONAL INFORMATION REQUIRED FOR |
| CODE COMPLIANCE. THIS REPORT DOES NOT SHOW COMPLIANCE |
| WITH THE ENERGY DOCUMENTS SUBMITTED REQUIRING A U |
| FACTOR OF0.131. THIS MAY VARY WITH THE LARGER 140 SQ. |
| FEET DOOR. 2017 ENERGY CODE C104.2(3). |
| |
| 7F) WITHIN THE ENVELOPE COMPLIANCE CERTIFICATE PAGE 1 |
| OF 21, ENVELOPE ASSEMBLIES THE EAST WALL DOOR 3 & 4 |
| BOTH INDICATE THEY ARE INSULATED, THE SUBMITTED FLORIDA |
| APPROVAL FL4553-R11 REVIEWED BY THE ARCHITECT INDICATES |
| ON PAGE 2 OF 27 THESE DOORS ARE HOLLOW CORE METAL |
| DOORS, PLEASE PROVIDE THE PROPOSED U-FACTOR. SHOW |
| COMPLIANCE WITH THE VALUES PROVIDED WITH IN THE ENERGY |
| REPORT. 107.2.1.2 ADDITIONAL INFORMATION REQUIRED FOR |
| CODE COMPLIANCE. . 2017 ENERGY CODE C104.2(3). |
| |
| 8) PRODUCT APPROVALS: |
| |
| 8A) PRODUCT APPROVALS THE PRESSURES CANNOT BE |
| DETERMINED AT THIS TIME FOR VARIOUS REASONS. NEITHER |
| THE ARCHITECTURAL SHEETS NOR THE E SHEETS PROVIDE A |
| COMPONENTS AND CLADDING CHART FOR THE WALL OPENINGS |
| INTERIOR ZONE (4) AND WALL END ZONE (5) NOR THE ROOF |
| ZONES, (1), (2) AND (3). THIS CHART SHOULD BE |
| PREFERABLY IN VASD SINCE MOST PRODUCT APPROVALS ARE |
| SHOWN IN VASD. CHART SHOULD SHOW PRESSURES IN EFFECTIVE |
| WIND AREA OF 10 SQ. FT., 20 SQ. FT., 50 SQ. FT. & 100 |
| SQ. FT. 2017 FBC-B 1609.6 OR ASCE 7-10 CHAPTER 30 FOR |
| COMPONENTS AND CLADDING. |
| |
| 8B) PLEASE NOTE ON THE COVERSHEET UNDER THE HEADING |
| LIST OF DRAWINGS IT IS NOTED THAT THE DRAWINGS INCLUDED |
| BUT NOT UNDER THE ARCHITECTS DIRECTION. IF NOT UNDER |
| THE ARCHITECTS DIRECTION WHO IS IN CHARGE OF ALL OF THE |
| PLANS TO COORDINATE THE DESIGN AND PLANS ? |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC... |
| 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER |
| ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECTS? |
| OFFICE (OTHER ARCHITECTS). |
| FOR ANY STRUCTURAL PLANS DESIGNED BY AN ENGINEER THE |
| ARCHITECT OF RECORD SHOULD APPLY THEIR SHOP DRAWING |
| STAMP OF APPROVAL, REVIEWED, OR REVIEWED AS NOTED OR |
| DENIED. |
| |
| 8C)(1) THE SUBMITTED NOA 18-0801. 01 REVIEWED BY THE |
| ARCHITECT DOES NOT INDICATE WHICH SERIES OF DOORS |
| (610/611/620/621) ARE TO BE INSTALLED ON THIS PROJECT. |
| THE SECOND ISSUE IS THE ARCHITECT HAS NOT ELECTED TO |
| INDICATE THE SLAT GAUGE OPTION FOUND ON SHEET 1 OF 2. |
| ONLY ONE GAUGE OPTION HAS BEEN TESTED IN ACCORDANCE |
| WITH THE MIAMI-DADE PROTOCOLS TAS 201-94, TAS 202-94 |
| AND TAS 203-94. 2017 FBC-B 1609.6. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED FOR CODE COMPLIANCE. |
| |
| 8D)(1) THE FLORIDA APPROVAL REVIEWED BY THE DESIGNER OF |
| RECORD AND SUBMITTED FL#4553-R11 LIST ZHCW.R27575 SWING |
| DOORS, EXTERIOR INDICATES VARIOUS MODEL AND SIZES. |
| PLEASE CIRCLE THE MODEL AND DESIGN LOAD IN PSF. 2017 |
| FBC-B 1609.6 OR ASCE 7-10 CHAPTER 30 FOR COMPONENTS AND |
| CLADDING. |
| 8D)(2) PLEASE ALSO NOTE THE SUBMITTED FL#4553-R11 MAY |
| REQUIRE A FIRE RATING DEPENDING ON THE ASSUMED PROPERTY |
| LINE AND ALLOWABLE OPENINGS. IF A FIRE RATING WOULD BE |
| REQUIRED BY FBC-B TABLE 602 AND TABLE 705.8 PLEASE |
| PROVIDE THE PROPER UL FIRE FILE SEE APPROVAL FOR THE |
| UL?S FOLLOW-UP SERVICE PROGRAM. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED FOR CODE COMPLIANCE. |
| |
| 8E) (1) THE SUBMITTED ROOFING NOA: 13-0425.14 HAS BEEN |
| SUPERSEDED TWICE, 15-0505.28 AND THE CURRENT NOA: |
| 18-0312.07 PLEASE UPDATE TO THE CURRENT NOA. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED FOR CODE COMPLIANCE. |
| 8E)(2) THE SUBMITTED ROOFING NOA: 13-0425.14 HAS BEEN |
| SUPERSEDED TWICE, 15-0505.28 AND THE CURRENT NOA: |
| 18-0312.07 WILL NEED TO SHOW (CIRCLE) IF THE EAVE IS TO |
| BE A FIXED EAVE OR FLOATING EAVE, FIXED END CAP OF |
| FLOATING END CAP AND PAGE 13 OF 13 LIST 3 SIZES OF THIS |
| PRODUCT 24 GAUGE DOUBLE LOCK STANDING SEAM IN 12 INCH, |
| 18 INCH AND 24 INCH WIDE PANELS. 2017 FBC-B 1609.6 OR |
| ASCE 7-10 CHAPTER 30 FOR COMPONENTS AND CLADDING. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED FOR CODE |
| COMPLIANCE. |
| |
| 8E)(3) TO DATE THE CITY HAS NOT SEEN ANY DOCUMENTATION |
| IF THE ENGINEER ASSOCIATED WITH MESCO BUILDING |
| SOLUTIONS INTENDS TO TAKE OR QUALIFIES TO TAKE FOR LOAD |
| COMBINATIONS THAT INCLUDE UPLIFT, THE NOMINAL WIND LOAD |
| THAT WOULD ALLOW TO BE MULTIPLIED BY 0.67 PROVIDED THE |
| TESTED SYSTEM AND WIND LOAD EVALUATION IS SATISFIED. |
| 2017 FBC-B 2211.5 ROOF SYSTEM DESIGN AISI S100. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED FOR CODE |
| COMPLIANCE. |
| |
| 8E)(4) THE SUBMITTED ROOFING NOA: 13-0425.14 HAS BEEN |
| SUPERSEDED TWICE, 15-0505.28 AND THE CURRENT NOA: |
| 18-0312.07 PAGE 10 0F 10 SHOWS DOUBLELOCK PANELS AND |
| NOTES FOR 12 INCH, 18 INCH AND 24 INCH WIDE PANELS WITH |
| BENDING MOMENT AT SUPPORTS AND BENDING MOMENT OF PANEL |
| BETWEEN SUPPORTS PANEL REACTION AT SUPPORTS AND THE |
| ALLOWABLE DEFLECTION OF PANEL ALL IN FT-LBS/ FT. |
| NOWHERE IN THIS REPORT IS THE PRESSURES GIVEN IN VASD. |
| IN TALKING WITH THE ENGINEER FOR THE ROOF PRODUCT |
| APPROVAL MIAMI-DADE REQUESTED THE RESULT OF TEST IN |
| FT-LBS./ FT. A ENGINEER OR QUALIFIED ARCHITECT CAN |
| CONVERT THE FT. LBS./ FT. INTO PSF. THERE IS A NOTE FOR |
| DOES INDICATE AS APPLICABLE DESIGN PRESSURES AS |
| DETERMINED FROM AND ASCE 7-10 MUST BE MULTIPLIED BY |
| 0.60. PLEASE PROVIDE THE VULT PRESSURES IN PSF. 2017 |
| FBC-B 1609.6 OR ASCE 7-10 CHAPTER 30 FOR COMPONENTS AND |
| CLADDING. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED |
| FOR CODE COMPLIANCE. |
| |
| 8E)(5) THE SUBMITTED ROOFING NOA: 13-0425.14 HAS BEEN |
| SUPERSEDED TWICE, 15-0505.28 AND THE CURRENT NOA: |
| 18-0312.07 PAGE 10 0F 10 SHOWS DOUBLELOCK PANELS AND |
| THE STATEMENT THIS ROOF PANEL IS APPROVED FOR A MAXIMUM |
| SPAN OF 5 FEET. PLEASE NOTE THE PRODUCT APPROVAL DOES |
| NOT GIVE THE VALUE IF THE SPAN IS LESS LET?S SAY 2 |
| FEET, THEN YOU COULD INTERPOLATE BETWEEN THE 2 VALUES, |
| 2 FEET AND 5 FEET. WE SEE MANY TEST REPORTS OR THE |
| ACTUAL TEST FROM THE MANUFACTURER GIVES THESE VALUES. . |
| 2017 FBC-B 1609.6 OR ASCE 7-10 CHAPTER 30 FOR |
| COMPONENTS AND CLADDING. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED FOR CODE COMPLIANCE. |
| |
| 8F) PLEASE NOTE THE WALL PANEL SYSTEM UPLOADED INTO THE |
| SYSTEM IS NOT A PRODUCT APPROVAL, JUST ENGINEERING. THE |
| FLORIDA STATUTE 553.8.4.2 REQUIRES PRODUCT EVALUATION, |
| 3RD PARTY CERTIFICATION AND APPROVAL FOR PRODUCTS TO BE |
| APPROVED IN FLORIDA. THE MOST COMMON ARE MIAMI-DADE |
| NOA?S OR FLORIDA APPROVALS. FOR LOCAL PRODUCT APPROVALS |
| FLORIDA STATUTE 553.8425 GIVES THAT AUTHORITY TO THE |
| LOCAL JURISDICTION. THE CITY OF WEST PALM BEACH USES |
| THE SAME CRITERIA AS THE STATE AND MUST BE SUBMITTED |
| UNDER SEPARATE COVER TO BE REVIEWED BY THE BUILDING |
| OFFICIAL FOR APPROVAL. |
| |
| 8F)(1) THE SUBMITTED METAL ROOF AND WALL SYSTEMS BY |
| MBCI WALL PANEL AVP PANEL HAD NOT BEEN REVIEWED BY THE |
| DESIGNER OF RECORD. W. P. B. 107.3.4.1 PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 8F)(2) THE SUBMITTED METAL ROOF AND WALL SYSTEMS BY |
| MBCI WALL PANEL AVP PANEL WILL ALSO NEED TO SUPPLY A |
| RANGE OF PRESSURES, GIVEN NEGATIVE PRESSURES AT 2 FOOT |
| AND 8 FEET BETWEEN SPAN OF GIRTS. PLEASE PROVIDE |
| PRESSURES WHEN GIRTS ARE PLACED AT 3, 4, 5, 6, AND 7 |
| FEET CENTERS. PLEASE NOTE THERE IS ONLY ONE SET OF |
| VALUES GIVEN WITH FASTENING LAYOUT. IN THE WALL END |
| ZONES ADDITIONAL GIRTS MAYBE REQUIRED BETWEEN THE |
| CORNER COLUMN AND THE 1ST COLUMN IN FROM THE CORNERS |
| FOR THE HIGHER PRESSURES IN WALL ZONE 5. THIS IS STILL |
| A UNKNOWN. |
| |
| 9A) SHEET 14-A3.0 THE REAR, LEFT SIDE AND RIGHT SIDE OF |
| THE BUILDING SHOW WALL LOUVERS WITHIN THE METAL WALL |
| CLADDING. PLEASE SHOW COMPLIANCE WITH: |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31 (B) WALL LOUVERS |
| |
| 9B) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF |
| PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR |
| REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE |
| OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST |
| PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| (561)233-5025 FOR MORE INFORMATION. |
| |
| 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |