2018-10-24 10:21:49 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- SHUTTER MOUNTING CONDITION IS NOT CLEAR. SHUTTERS |
| DRAWING SUBMITTED ARE HIGHLIGHTED WITH TOO MANY |
| MOUNTING CONDITIONS (BUILD OUT, WALL MOUNTED, FLOOR |
| MOUNTED, TRUSS MOUNTED, ETC). CLEARLY SPECIFY THE |
| SHUTTERS MOUNTING CONDITION THAT APPLIES FOR EACH |
| OPENING FOR PROPER REVIEW OF THE SHUTTERS INSTALLATION |
| SCHEDULE. . SEC. 107.2.1 CITY AMENDMENTS. |
| NOTE: C5 AS SHOWN ON THE INSTALLATION SCHEDULE ON |
| COLUMN 4 IS NOT A SHUTTER MOUNTING CONDITION. REVISE AS |
| REQUIRED. |
| |
| 2- CLARIFY WHY THE SHUTTER SPAN SHOWN ON THE |
| INSTALLATION SCHEDULE FOR OPENING #3 IS MUCH SMALLER |
| THAN THE OPENING HEIGHT SHOWN. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 3- ACCORDION SHUTTERS ARE TYPICALLY VERTICALLY MOUNTED. |
| CLARIFY WHY SPECIFYING THAT THEY ARE INSTALLED |
| HORIZONTALLY OR REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 4- IF USING THE ENGINEER WIND LOAD CALCULATIONS FROM |
| ENGINEERING EXPRESS, THEN THEY NEED TO HAVE ENGINEER'S |
| ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| FLORIDA STATE WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORDS. |
| NOTE: CONTRACTOR MAY USE THE TABLES R301.2(2) AND |
| R301.2(3) FBC-RESIDENTIAL TO DETERMINE THE WIND LOADS. |
| |