Plan Review Details - Permit 18100307
Plan Review Stops For Permit 18100307
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By jgomez Date 2018-10-30 Time 17:46 Rev Time 0.00
Received By jgomez Date 2018-10-30 Time 17:25 Sent To  
Notes
2018-10-30 17:47:55BUILDING REVIEW APPROVED WITH PROVISO:
 1- VERIFY EGRESS CLEAR OPENINGS (WIDTH) IN MASTER
 BEDROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By jgomez Date 2018-10-24 Time 15:19 Rev Time 0.00
Received By jgomez Date 2018-10-24 Time 14:51 Sent To  
Notes
2018-10-24 15:31:15RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- CALCULATED DESIGN PRESSURES SUBMITTED ARE INCORRECT.
 ACCORDING TO PLANS ON CITY RECORDS. OPENINGS #1 AND #7
 ARE LOCATED IN END ZONE NOT INTERIOR ZONE. REVISE AS
 REQUIRED. NOTE: ACCORDING TO NOTE "A" ON FIGURE
 R301.2(7) FBC-RESIDENTIAL END ZONE APPLIES TO OPENINGS
 WITHING 4'-0" IN ALL CASES. REVISE AS REQUIRED.
  
 2- CLEARLY SPECIFY SIZE OF OPERABLE WINDOWS ON MASTER
 BEDROOM WINDOW TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By jgomez Date 2018-10-30 Time 17:48 Rev Time 0.00
Received By jgomez Date 2018-10-25 Time 11:34 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By jgomez Date 2018-10-24 Time 15:31 Rev Time 0.00
Received By jgomez Date 2018-10-09 Time 11:06 Sent To I
Notes
***NONE***