Plan Review Details - Permit 18100279
Plan Review Stops For Permit 18100279
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2019-06-25 Cont ID  
Sent By jgomez Date 2019-06-25 Time 16:35 Rev Time 0.00
Received By jgomez Date 2019-06-25 Time 14:18 Sent To  
Notes
2019-06-25 16:37:26BUILDING REVIEW APPROVED WITH PROVISO:
 1-ENERGY CALCULATIONS SUBMITTED: REVISE THE WINDOW
 OVERHANG SEPARATION SHOWN ON PAGE 3 OF 4 TO MATCH
 PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2019-06-19 Cont ID  
Sent By jgomez Date 2019-06-19 Time 08:40 Rev Time 0.00
Received By jgomez Date 2019-06-19 Time 08:29 Sent To  
Notes
2019-06-19 08:40:08BUILDING REVIEW APPROVED WITH PROVISO:
 1-ENERGY CALCULATIONS SUBMITTED: REVISE THE WINDOW
 OVERHANG SEPARATION SHOWN ON PAGE 3 OF 4 TO MATCH
 PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2019-06-05 Cont ID  
Sent By jgomez Date 2019-06-05 Time 13:41 Rev Time 0.00
Received By jgomez Date 2019-06-05 Time 10:18 Sent To  
Notes
2019-06-05 10:20:32RESIDENTIAL (R3)ALTERATION/ADDITION FIFTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 1- IMPACT FEES: TO BE DONE LATER ONCE PLANS ARE
 APPROVED.
  
 2- ENERGY CALCULATIONS:
  
 A) OK.
  
 ORIGINAL COMMENT:
 B) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. THE NAME OF PERSON DOING
 THE CALCULATIONS WAS NOT PROVIDED AS REQUIRED BY SEC.
 R405.4.2.1. ONLY THE SIGNATURE WAS PROVIDED.
  
 NOTE:
 ARCHITECT'S RESPONSE LETTER STATES THAT "R 405.4.2.1 IS
 COMMERCIAL CODE REFERENCE, BUT FORM IS SIGNED BY MIKEL
 ABBOTT". THIS IS INCORRECT. SECTION CITED IS CORRECT.
 THE FBC CODE-ENERGY CONSERVATION IS DIVIDED INTO
 COMMERCIAL AND RESIDENTIAL. ALL CODE SECTIONS WITH THE
 LETTER "R" BEFORE THE CODE SECTION APPLIES FOR THE
 RESIDENTIAL CODE AND ALL CODE SECTIONS WITH THE LETTER
 "C" BEFORE THE CODE SECTION APPLIES TO THE COMMERCIAL
 PROJECTS. ALSO, THIS SECTION CLEARLY STATES TO PROVIDE
 THE NAME OF THE PERSON DOING THE CALCULATIONS NOT THE
 SIGNATURE.
 I HOPE THIS CLARIFIES THE COMMENT. IF THERE ARE ANY
 QUESTIONS, PLEASE FEEL FREE TO CONTACT ME. I WILL BE
 MORE THAN HAPPY TO ANSWER ANY QUESTION TO AVOID MORE
 DELAYS. AS YOU CAN SEE ON TOP OF THIS CHECKLIST, I WANT
 TO PASS THIS BUILDING REVIEW WITH A PROVISO BUT FEES
 WOULD APPLY IF THE CORRECTIONS ARE DONE AFTER THE
 PERMIT IS ISSUED. THANK YOU.
  
 ORIGINAL COMMENT:
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME AND JURISDICTION NUMBER (THIS
 JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 PARTIALLY ADDRESSED. PROVIDE COMPLETE NAME OF THE
 BUILDER. NAME PROVIDED DOESN'T MATCH NAME OF
 CONTRACTOR.
  
 D) OK.
  
 ORIGINAL COMMENT:
 E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 2 OF 4
 DOESN'T MATCH. SEE PLANS AND PRODUCT APPROVALS. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 PARTIALLY ADDRESSED. THE ROOF MATERIAL WAS REVISED BUT
 THE TYPE OF ROOF WAS NOT. SEE PLANS AND REVISE AS
 REQUIRED TO MATCH.
  
 F) OK.
  
 ORIGINAL COMMENT:
 G)WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. WINDOW AREA DOESN'T MATCH. NOTE: DOORS WITH
 GLAZING NEED TO BE ENTERED IN THE WINDOW AREA ALSO.
 OVERHANG DEPTH AND SEPARATION DOESN'T MATCH PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 CALCULATIONS ARE DONE FOR THE ADDITION ONLY. THERE ARE
 NOT WINDOWS ON THE NORTH SIDE OF THE ADDITION. GLASS
 AREA IN THE MASTER BEDROOM NEED TO BE COUNTED. THE
 WINDOWS OVERHANG SEPARATING DOESN'T MATCH PLANS. REVISE
 AS REQUIRED.
  
 3- OK.
  
 4- OK.
  
 5- OK.
  
 6- OK.
  
 7- OK.
  
 8- OK.
  
 9- OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13- OK.
  
 14- OK.
  
 15- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-05-22 Cont ID  
Sent By jgomez Date 2019-05-22 Time 09:37 Rev Time 0.00
Received By jgomez Date 2019-05-21 Time 17:57 Sent To  
Notes
2019-05-22 09:37:25RESIDENTIAL (R3)ALTERATION/ADDITION FOURTH BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 1- IMPACT FEES: TO BE DONE LATER ONCE PLANS ARE
 APPROVED.
  
 2- ENERGY CALCULATIONS:
  
 ORIGINAL COMMENT:
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER'S LEGALLY
 DESIGNATED AGENT PRIOR TO RECEIVE THE PERMIT AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME AND JURISDICTION NUMBER (THIS
 JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) ITEM #9 IS INCOMPLETE. NEED TO PROVIDE INFORMATION
 FOR ADJACENT WALL BETWEEN GARAGE AND THE MAIN HOUSE A/C
 AREA. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 2 OF 4
 DOESN'T MATCH. SEE PLANS AND PRODUCT APPROVALS. REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 F) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. THE
 RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL.
 OR, PROVIDE COMPLETE DOCUMENTATION SHOWING COMPLIANCE
 WITH THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON
 SEC. R806.2.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 G)WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. WINDOW AREA DOESN'T MATCH. NOTE: DOORS WITH
 GLAZING NEED TO BE ENTERED IN THE WINDOW AREA ALSO.
 OVERHANG DEPTH AND SEPARATION DOESN'T MATCH PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- OK.
  
 4- OK.
  
 5- OK.
  
 6- OK.
  
 7- OK.
  
 8- OK.
  
 9- OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13- OK.
  
 14- OK.
  
 15- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-03-01 Cont ID  
Sent By jgomez Date 2019-03-01 Time 16:34 Rev Time 0.00
Received By jgomez Date 2019-03-01 Time 10:55 Sent To  
Notes
2019-03-01 16:35:13RESIDENTIAL (R3)ALTERATION/ADDITION THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 NOTE 1: NEED ZONING APPROVAL
  
  
 NOTE 2:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE
 ENERGY CALCULATIONS ARE PROPERLY SIGNED BY OWNER OR
 AUTHORIZED AGENT AND THE NAME OF THE PERSON PREPARING
 THEM IS PROVIDED. PROVISO MEANS CONTRACTOR WILL SUBMIT
 REQUIRED INFORMATION AFTER THE PERMIT IS ISSUED BUT
 BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION
 FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
  
  
 1- IMPACT FEES: TO BE DONE LATER ONCE PLANS ARE
 APPROVED.
  
 ORIGINAL COMMENT:
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING.
 NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS TO
 AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 A) THE ENERGY FORM R405-2017 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER OR OWNER?S LEGALLY
 DESIGNATED AGENT PRIOR TO RECEIVE THE PERMIT AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017).
  
 B) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME AND JURISDICTION NUMBER (THIS
 JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D) ITEM #9 IS INCOMPLETE. NEED TO PROVIDE INFORMATION
 FOR ADJACENT WALL BETWEEN GARAGE AND THE MAIN HOUSE A/C
 AREA. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)ROOF TYPE AND MATERIAL SPECIFIED ON PAGE 2 OF 4
 DOESN'T MATCH. SEE PLANS AND PRODUCT APPROVALS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 F) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. THE
 RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL.
 OR, PROVIDE COMPLETE DOCUMENTATION SHOWING COMPLIANCE
 WITH THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON
 SEC. R806.2.
  
 G)WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH
 PLANS. WINDOW AREA DOESN'T MATCH. NOTE: DOORS WITH
 GLAZING NEED TO BE ENTERED IN THE WINDOW AREA ALSO.
 OVERHANG DEPTH AND SEPARATION DOESN'T MATCH PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 H)PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE SHGC FACTOR SPECIFIED ON THE
 ENERGY CALCULATIONS ON ITEM #7 AS REQUIRED BY SEC.
 R405.4.3 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 3- DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 RESPONSE:
 DRAINAGE PLAN PROVIDED NOW DOESN'T SHOW ANY DRAINAGE
 PLAN SHOWING HOW THE WATER IS DIVERTED TO ANY APPROVED
 POINT OF COLLECTION AS REQUIRED BY SEC. R401.3. THERE
 IS A NOTE STATING "SLOPE GRADE 1/4" PER FOOT". THIS
 INFORMATION IS INSUFFICIENT. SLOPE GRADE TOWARDS
 WHERE?. WATER CAN NOT BE DIVERTED TO THE NEIGHBORS AND
 IT HAS TO BE DIVERTED AWAY FROM THE FOUNDATION. REVISE
 AS REQUIRED.
  
 4- SHEET A-2.2:
 A) OK.
  
 B)OK.
  
 C) OK.
  
 D) OK
  
 E) OK
  
 F) OK.
  
 G) OK.
  
 H) OK
  
 5- OK.
  
 6- OK.
  
 7- SHEET A-2.0:
 A) OK.
  
 B) OK
  
 C)OK.
  
 8- OK.
  
 9- OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13- OK.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)OK
  
 B) OK
  
 C) OK
  
 D)OK.
  
 15- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-01-23 Cont ID  
Sent By jgomez Date 2019-01-23 Time 11:46 Rev Time 0.00
Received By jgomez Date 2019-01-22 Time 08:17 Sent To  
Notes
2019-01-23 11:46:55RESIDENTIAL (R3)ALTERATION/ADDITION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES: TO BE DONE LATER ONCE PLANS ARE
 APPROVED.
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING.
 NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS TO
 AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 3- DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 RESPONSE:
 DRAINAGE PLAN SUBMITTED DOESN'T SEEM TO COMPLY WITH
 SEC. R401.3 FBC-RESIDENTIAL. ALSO, IT LOOKS LIKE IS
 CREATING A HAZARD BY HAVING AN 8" DROP IN THE WALKING
 SURFACE. THE SWALES SHOWN ARE MORE LIKE RETENTION PONDS
 RATHER THAN SWALES THAT DIVERT THE WATER AWAY FROM THE
 BUILDING. THE RETENTION POND BETWEEN THE ADDITION AND
 ADJACENT NEIGHBOR LOOKS LIKE IT MAY BE CREATING A POND
 PROBLEM TO THE NEIGHBOR AND TO THE ADDITION ITSELF.
 ALSO, DRAINAGE CALCULATIONS SUBMITTED DON'T SEEM TO BE
 ADEQUATE. WHERE ARE THE COEFFICIENTS TAKEN FROM?. SEE
 FIGURE 1106.1 FBC-PLUMBING FOR RAINFALL RATES IN
 FLORIDA. ALSO, SIZES OF GUTTERS AND RAIN LEADERS SHOWN
 IN THE DRAINAGE PLAN ARE ARE NOT SPECIFIED. REVISE
 DRAINAGE PLAN AS REQUIRED.
  
 4- SHEET A-2.2:
 A) OK.
  
 B)OK.
  
 C) OK.
  
 D) PROVIDE COMPLETE SPECIFICATIONS FOR THE DOOR LEADING
 FROM THE GARAGE TO THE MAIN HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 IT LOOKS LIKE THERE ARE WINDOWS ADJACENT TO THE DOOR
 LEADING FROM THE PROPOSED GARAGE TO THE INTERIOR OF THE
 HOUSE. ALL OPENINGS LEADING TO THE HOUSE NEED TO COMPLY
 WITH SEC. R302.5.1 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 E) OK
  
 F) OK.
  
 G) OK.
  
 H) SPECIFY ATTIC ACCESS SIZE AND LOCATION IN THE
 ADDITION SEC. R307.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 LOCATION OF PROPOSED ATTIC ACCESS DOESN'T SEEM TO
 PROVIDE THE REQUIRED HEIGHT CLEARANCE ABOVE THE
 OPENING. REVISE AS REQUIRED.
  
 5- OK.
  
 6- OK.
  
 7- SHEET A-2.0:
 A) OK.
  
 B) FLOOD INFORMATION SHOWN UNDER EXISTING SITE DATA
 DOESN'T SEEM TO BE CORRECT. CLARIFY WHY SUBMITTING THIS
 INFORMATION IF THE PROPERTY IS NOT LOCATED IN A SPECIAL
 FLOOD ZONE AREA. ALSO, CLARIFY/REVISE NOTES AT THE
 BOTTOM OF AREA CALCULATIONS. FLOOD ELEVATION
 CERTIFICATE IS NOT REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 FLOOD INFORMATION SEEMS TO BE INCORRECT. PROPERTY IS NO
 LOCATED IN A SPECIAL FLOOD HAZARD AREA. CLARIFY WHERE
 IS THIS INFORMATION TAKEN FROM. OTHERWISE, REMOVE
 INFORMATION TO AVOID CONFUSION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C)OK.
  
 8- OK.
  
 9- OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13- OK.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 PROVIDE 2 COPIES OF NOA 16-0906.06. ONLY ONE WAS
 SUBMITTED.
  
 B) EXTERIOR SWING GARAGE DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 PROVIDE 2 COPIES OF NOA 15-0611.05. ONLY ONE WAS
 SUBMITTED.
  
 C) ROOF FINISH (SHINGLES?)
  
 RESPONSE:
 PROVIDE 2 COPIES OF NOA 14-1022.09. ONLY ONE WAS
 SUBMITTED.
  
 D)OK.
  
 15- OK.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-21 Cont ID  
Sent By jgomez Date 2018-11-21 Time 10:42 Rev Time 0.00
Received By jgomez Date 2018-11-20 Time 17:21 Sent To  
Notes
2018-11-21 10:42:38RESIDENTIAL (R3)ALTERATION/ADDITION BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  
 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING.
 NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS TO
 AVOID CONFLICTS/DELAYS.
  
 3- DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 SEC. R401.3 FBC_RESIDENTIAL:
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE
 APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR
 WHEN OTHERWISE WARRANTED.
  
 SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A
 LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
  
 4- SHEET A-2.2:
 A) PROPOSED FLOOR PLAN DOESN'T HAVE ANY ROOM
 DIMENSIONS. NEED TO PROVIDE DIMENSIONS OF ALL AREAS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)PROPOSED FLOOR PLAN SHOWS ONE WINDOW OF EXISTING
 BEDROOM TO BE BLOCKED TO ALLOW FOR THE ADDITION.
 SPECIFY SIZE AND TYPE OF EXISTING WINDOWS IN THIS
 BEDROOM TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 701.2 AND SEC. 702.5 FBC-EXISTING
 BUILDING OF WINDOW TO REMAIN.
  
 C) DOOR SCHEDULE NEEDS TO INCLUDE THE NEW GARAGE
 OVERHEAD DOOR AND EXTERIOR SWING DOOR. SEC. 107.2.1
 CITY AMENDMENTS.
  
 D) PROVIDE COMPLETE SPECIFICATIONS FOR THE DOOR LEADING
 FROM THE GARAGE TO THE MAIN HOUSE SHOWING COMPLIANCE
 WITH SEC. R302.5.1 FBC-RESIDENTIAL.
  
 E) PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS
 FOR NEW OVERHEAD GARAGE DOOR. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: PROVIDE STRUCTURAL BUCK DETAIL FOR ALL EXTERIOR
 SWING DOORS ALSO.
  
 F) FLOOR PLAN SHOWS AN EXISTING "FAMILY ROOM".
 ACCORDING TO CITY RECORDS AND PROPERTY APPRAISER THIS
 ROOM IS AN "ENCLOSED PORCH" NOT LIVABLE AREA. THERE ARE
 NO PERMITS SHOWING CONVERSION OF THIS ROOM. REVISE NAME
 OF ROOM TO ENCLOSED PORCH OR PROVIDE COMPLETE DRAWINGS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE ROOM
 CONVERSION TO LIVABLE SPACE. SEC. 105.1 CITY
 AMENDMENTS.
  
 G) CLARIFY DOORS "B" AND "C" SPECIFIED IN THE DOOR
 SCHEDULE. ARE THESE REALLY ALUM/GLASS FRENCH DOORS?.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 H) SPECIFY ATTIC ACCESS SIZE AND LOCATION IN THE
 ADDITION SEC. R307.1 FBC-RESIDENTIAL.
  
 5- SPECIFY CARBON MONOXIDE ALARM WITHING ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 6- LIST OF DRAWINGS SHOWN ON SHEET TS-1 DON'T MATCH
 DRAWINGS SUBMITTED. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- SHEET A-2.0:
 A) HATCHED AREA SQUARE FOOTAGE SPECIFIED ON THE SITE
 PLAN BY THE "NEW ADDITION" DOESN'T MATCH TOTAL
 ADDITIONAL A/C SPACE SHOWN IN THE AREA CALCULATIONS IN
 THE SAME SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) FLOOD INFORMATION SHOWN UNDER EXISTING SITE DATA
 DOESN'T SEEM TO BE CORRECT. CLARIFY WHY SUBMITTING THIS
 INFORMATION IF THE PROPERTY IS NOT LOCATED IN A SPECIAL
 FLOOD ZONE AREA. ALSO, CLARIFY/REVISE NOTES AT THE
 BOTTOM OF AREA CALCULATIONS. FLOOD ELEVATION
 CERTIFICATE IS NOT REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C)REVISE/CLARIFY THE "RESTORATION LEVEL" SPECIFIED
 UNDER "EXISTING BUILDING RENOVATION". THIS IS NOT
 RESTORATION LEVEL 3. THIS IS ALTERATION LEVEL 2 AND
 ADDITION. SEC. 504 AND 507 FBC-EXISTING BUILDING.
  
 8- SHEET A-5.0: SPECIFY COLUMNS AND BEAM/LINTEL AT THE
 ENDS OF OVERHEAD GARAGE DOOR AND EXTERIOR SWING DOORS
 IN NEW GARAGE
 SEC. R301.1 FBC-RESIDENTIAL.
  
 9- SPECIFY ROOF CROSS VENTILATION AS REQUIRED BY SEC.
 R806 FBC-RESIDENTIAL. SPECIFY SIZE AND LOCATION.
  
 10- PROVIDE ROOF SHEATHING NAIL TYPE, SIZE AND SPACING
 AS REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: NEED TO SPECIFY RING SHANK NAILS AND GABLE ROOFS
 ENDS ARE IN ZONE #3 (5'-0" MIN.).
  
 11- FLOOR INFORMATION SHOWN ON WALL SECTION "B" ON
 SHEET A-5.5 DOESN'T MATCH FOUNDATION PLANS ON SHEET
 A-5.0. SEC. 107.2.1 CITY AMENDMENTS.
  
 12- CLARIFY ROOFING INFORMATION SHOWN ON WALL SECTION
 "A" ON SHEET A-5.5. IS IT CONCRETE TILE OR ASPHALT
 SHINGLES?. MAIN HOUSE HAS SHINGLES. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 13- THERE ARE MANY SHEETS THAT REFERENCE THE 2014 CODE.
 UPDATE AS REQUIRED. THE CURRENT CODE IS THE FBC 6TH
 EDITION (2017) NOT THE FBC 5TH EDITION (2014). CHAPTER
 553 FLORIDA STATUTE. UPDATE ALL PLANS AS REQUIRED.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A)OVERHEAD GARAGE DOOR AS SHOWN ON PLANS.
  
 B) EXTERIOR SWING GARAGE DOOR AS SHOWN ON PLANS.
  
 C) ROOF FINISH (SHINGLES?)
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-22 Cont ID  
Sent By jpearson Date 2019-01-22 Time 07:22 Rev Time 0.00
Received By jpearson Date 2019-01-22 Time 07:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By fgiaquin Date 2018-10-30 Time 08:00 Rev Time 0.00
Received By fgiaquin Date 2018-10-30 Time 06:49 Sent To  
Notes
2018-10-30 08:00:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL NOTES SAY THE ADDIDTION WILL BE DONE TO
 THE 2011 NATIONAL ELECTRIC CODE. 2014 IS THE CURRENT
 NATIONAL ELECTRICAL CODE AND IS THE APPLICABLE CODE FOR
 THIS PROJECT. PROVIDE CORRECTION. FBC 107.2.1
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
  
 3. LOAD CALCULATION IS NOT ACCURATE. PROVIDE ACCURATE
 LOAD CALCULATION INCLUDING ALL LOADS. NEC 220; FBC RE
 E3602.2
  
 4. MISSING RECEPTACLE RIGHT OF EXTERIOR DOOR IN NEW
 MASTER BEDROOM. 210.52A1 NEC
  
 5. MISSING RECEPTACLE RIGHT OF CLOSET DOOR IN NEW
 MASTER BEDROOM. 210.52A1 NEC
  
 6. SMOKE/CARBON COMBO ALARM REQUIRED OUTSIDE BEDROOMS
 (NEW AND EXISITING) DUE TO NEW PROPOSED ATTACHED
 GARAGE. FBC R314 & 315
  
 7. RECEPTACLE REQUIRED IN GARAGE. 210.52G1
  
 8. ALL RECEPTACLES IN GARAGE MUST BE GFCI PROTECTED.
 210.8A2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2019-07-10 Cont ID  
Sent By jgomez Date 2019-07-10 Time 16:37 Rev Time 0.00
Received By jgomez Date 2019-07-08 Time 14:40 Sent To I
Notes
2019-07-09 14:40:32RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2019-06-25 Cont ID  
Sent By cpuell Date 2019-06-25 Time 16:56 Rev Time  
Received By jgomez Date 2019-06-19 Time 13:47 Sent To I
Notes
2019-06-20 13:47:23RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-06-19 Cont ID  
Sent By jgomez Date 2019-06-19 Time 10:18 Rev Time 0.00
Received By jgomez Date 2019-06-10 Time 14:11 Sent To I
Notes
2019-06-11 14:11:52RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-06-05 Cont ID  
Sent By jgomez Date 2019-06-05 Time 13:48 Rev Time 0.00
Received By jgomez Date 2019-05-31 Time 15:02 Sent To I
Notes
2019-06-03 15:02:52RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-22 Cont ID  
Sent By jgomez Date 2019-05-22 Time 09:41 Rev Time 0.00
Received By jgomez Date 2019-05-13 Time 15:01 Sent To I
Notes
2019-05-14 15:01:47RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-03-01 Cont ID  
Sent By jgomez Date 2019-03-01 Time 16:45 Rev Time 0.00
Received By jgomez Date 2019-02-25 Time 15:31 Sent To I
Notes
2019-02-26 15:31:33RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-01-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-02 Time 09:45 Sent To I
Notes
2019-01-04 09:45:49R33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-21 Cont ID  
Sent By jgomez Date 2018-11-21 Time 11:09 Rev Time 0.00
Received By jgomez Date 2018-10-05 Time 14:31 Sent To I
Notes
2018-10-09 14:32:11R33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 8 Status P Date 2019-07-10 Cont ID  
Sent By jgomez Date 2019-07-10 Time 16:34 Rev Time 0.00
Received By jgomez Date 2019-07-10 Time 15:43 Sent To  
Notes
2019-07-10 16:37:40$185.17 PAID. MU-2019-020385.
 $180.65 IMPACT FEES AND $4.52 FOR INTERNET SERVICE
 CHARGE BY PBC.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 7 Status F Date 2019-06-25 Cont ID  
Sent By jgomez Date 2019-06-25 Time 16:55 Rev Time 0.00
Received By jgomez Date 2019-06-25 Time 16:55 Sent To  
Notes
2019-06-25 16:56:061- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status F Date 2019-06-19 Cont ID  
Sent By jgomez Date 2019-06-19 Time 10:18 Rev Time 0.00
Received By jgomez Date 2019-06-19 Time 08:42 Sent To  
Notes
2019-06-19 10:18:341- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2019-06-05 Cont ID  
Sent By jgomez Date 2019-06-05 Time 13:48 Rev Time 0.00
Received By jgomez Date 2019-06-05 Time 13:48 Sent To  
Notes
2019-06-05 13:48:311- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2019-05-22 Cont ID  
Sent By jgomez Date 2019-05-22 Time 09:16 Rev Time 0.00
Received By jgomez Date 2019-05-22 Time 09:16 Sent To  
Notes
2019-05-22 09:17:141- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2019-03-01 Cont ID  
Sent By jgomez Date 2019-03-01 Time 12:52 Rev Time 0.00
Received By jgomez Date 2019-03-01 Time 12:52 Sent To  
Notes
2019-03-01 12:52:421- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-01-23 Cont ID  
Sent By jgomez Date 2019-01-23 Time 11:50 Rev Time 0.00
Received By jgomez Date 2019-01-23 Time 11:50 Sent To  
Notes
2019-01-23 11:50:311- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-21 Cont ID  
Sent By jgomez Date 2018-11-21 Time 11:07 Rev Time 0.00
Received By jgomez Date 2018-11-21 Time 07:46 Sent To  
Notes
2018-11-21 11:07:481- IMPACT FEES - PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-11-05 Cont ID  
Sent By cmontell Date 2018-11-05 Time 12:53 Rev Time 0.00
Received By cmontell Date 2018-11-05 Time 12:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-22 Cont ID  
Sent By jgomez Date 2019-05-22 Time 09:41 Rev Time 0.00
Received By jgomez Date 2019-05-22 Time 09:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-01 Cont ID  
Sent By jgomez Date 2019-03-01 Time 16:38 Rev Time 0.00
Received By jgomez Date 2019-03-01 Time 16:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-21 Cont ID  
Sent By jgomez Date 2018-11-21 Time 11:09 Rev Time 0.00
Received By jgomez Date 2018-11-21 Time 11:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-03-01 Cont ID  
Sent By jgomez Date 2019-03-01 Time 16:38 Rev Time 0.00
Received By jgomez Date 2019-03-01 Time 16:38 Sent To  
Notes
2019-03-01 16:39:28SHINGLES NOA 14-1022.09 SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-01-23 Cont ID  
Sent By jgomez Date 2019-01-23 Time 11:48 Rev Time 0.00
Received By jgomez Date 2019-01-23 Time 11:48 Sent To  
Notes
2019-01-23 11:49:501- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF FINISH (SHINGLES?)
  
 RESPONSE:
 PROVIDE 2 COPIES OF NOA 14-1022.09. ONLY ONE WAS
 SUBMITTED.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-11-21 Cont ID  
Sent By jgomez Date 2018-11-21 Time 11:08 Rev Time 0.00
Received By jgomez Date 2018-11-21 Time 07:46 Sent To  
Notes
2018-11-21 11:08:441- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ROOF FINISH (SHINGLES?)

Review Stop Z ZONING
Rev No 7 Status P Date   Cont ID  
Sent By   Date 2019-06-21 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-21 Time 14:39 Sent To B
Notes
2019-06-21 14:40:53PAUL GREILICH, SENIOR PLANNER
 [email protected]
 561-822-1443

Review Stop Z ZONING
Rev No 6 Status F Date   Cont ID  
Sent By   Date 2019-06-13 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-13 Time 15:53 Sent To B
Notes
2019-06-13 15:55:11FAILED - ****REPEAT COMMENTS****
  
 1.) MUST PROVIDE CUMULATIVE TOTAL SIDE SETBACK OF 15
 FEET, SLIGHTLY LESS SHOWN ON PLAN
 2.) LANDSCAPE PERMIT REQUIRED
  
  
 ****SPOKE WITH CONTRACTOR ON 5/21/19 TO NOTIFY HIM OF
 REPEAT SETBACK COMMENT*****
  
 ***CALLED MARLENE IPARRAGUIRRE (APPLICANT) AND LEFT
 MESSAGE ON 6/13/19 TO NOTIFY OF REPEAT SETBACK COMMENT.
 LEFT MESSAGE****
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 5 Status F Date   Cont ID  
Sent By   Date 2019-06-05 Time   Rev Time 0.00
Received By pgreilic Date 2019-06-05 Time 08:20 Sent To B
Notes
2019-06-05 08:21:27FAILED
  
 1.) MUST PROVIDE CUMULATIVE TOTAL SIDE SETBACK OF 15
 FEET, SLIGHTLY LESS SHOWN ON PLAN
 2.) LANDSCAPE PERMIT REQUIRED
  
  
 ****SPOKE WITH CONTRACTOR ON 5/21/19 TO NOTIFY HIM OF
 REPEAT SETBACK COMMENT*****
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2019-05-21 Cont ID  
Sent By pgreilic Date 2019-05-21 Time 10:14 Rev Time 0.00
Received By pgreilic Date 2019-05-21 Time 10:13 Sent To B
Notes
2019-05-21 10:14:26FAILED
  
 1.) MUST PROVIDE CUMULATIVE TOTAL SIDE SETBACK OF 15
 FEET, SLIGHTLY LESS SHOWN ON PLAN
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2019-02-27 Time   Rev Time 0.00
Received By pgreilic Date 2019-02-27 Time 09:21 Sent To B
Notes
2019-02-27 09:21:33FAILED
  
 1.) MUST PROVIDE CUMULATIVE TOTAL SIDE SETBACK OF 15
 FEET, SLIGHTLY LESS SHOWN ON PLAN
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2019-01-17 Time   Rev Time 0.00
Received By pgreilic Date 2019-01-15 Time 16:46 Sent To  
Notes
2019-01-17 13:27:23FAILED
  
 1.) MUST PROVIDE CUMULATIVE TOTAL SIDE SETBACK OF 15
 FEET, SLIGHTLY LESS SHOWN ON PLAN
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2018-10-29 Time   Rev Time 0.00
Received By pgreilic Date 2018-10-29 Time 14:41 Sent To  
Notes
2018-10-29 14:49:03FAILED
  
 1.) MUST PROVIDE CUMULATIVE TOTAL SIDE SETBACK OF 15
 FEET, SLIGHTLY LESS SHOWN ON PLAN
 2.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]