Plan Review Details - Permit 18100232
Plan Review Stops For Permit 18100232
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-11 Cont ID  
Sent By pvalenti Date 2018-12-11 Time 08:03 Rev Time 0.00
Received By pvalenti Date 2018-12-11 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-19 Cont ID  
Sent By pvalenti Date 2018-11-19 Time 10:51 Rev Time 0.00
Received By pvalenti Date 2018-11-19 Time 10:49 Sent To  
Notes
2018-11-19 10:55:27****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION (SHOW DISTANCE
 OF GENERATOR TO OPERABLE OPENING).

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-23 Cont ID  
Sent By jleahy Date 2018-10-23 Time 18:27 Rev Time 0.00
Received By jleahy Date 2018-10-23 Time 18:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By tklarge Date 2018-12-14 Time 10:35 Rev Time 0.00
Received By tklarge Date 2018-12-14 Time 10:18 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-12-07 Cont ID  
Sent By tklarge Date 2018-12-07 Time 16:48 Rev Time 0.00
Received By tklarge Date 2018-12-07 Time 16:44 Sent To  
Notes
2018-12-07 16:49:55SUBMIT TWO COPIES OF A GAS PLAN. THE ONLY PLAN IN THE
 PERMIT APPLICATION FOLDER WAS A VOIDED GAS PLAN. WPB
 AMEEND. TO FBC SEC. 107.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-10-23 Cont ID  
Sent By tklarge Date 2018-10-23 Time 10:42 Rev Time 0.00
Received By tklarge Date 2018-10-23 Time 10:28 Sent To  
Notes
2018-10-23 10:41:031) PLACE A NOTE ON THE PLANS THAT THE GENERATOR EXHAUST
 SHALL BE LOCATED A MINIMUM OF 10 FT. FROM BUILDING
 OPENINGS OR AS PER MANUF. INSTALLATION MANUAL.
 2) THE ORIGINAL GAS PLAN ON FILE IN THE CITY RECORDS
 SHOWS THE LONGEST RUN AT 100 FEET. THIS DISTANCE SHALL
 BE USED IN THE SIZING OF ALL THE GAS PIPING. 2017
 FBC-FUEL GAS SEC. 402.4.1, NOT 15 FEET.
 3) THE MINIMUM SIZE METALLIC PIPE AT THE OUTLET OF THE
 GAS METER SHALL BE 1 1/2 INCHES FOR A LESS THAN 2 PSI
 SYSTEM ACCORDING TO TABLE 402.4 (2) OF THE 2017
 FBC-FUEL GAS CODE.
 4) THE MINIMUM SIZE OF THE PE PIPE SHALL BE 1 1/4 INCH
 PER TABLE 402.4 (21) OF THE 2017 FBC-FUEL GAS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-14 Cont ID  
Sent By tklarge Date 2018-12-14 Time 10:36 Rev Time 0.00
Received By tklarge Date 2018-12-14 Time 10:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-11 Cont ID  
Sent By pvalenti Date 2018-12-11 Time 08:08 Rev Time 0.00
Received By pvalenti Date 2018-11-20 Time 14:19 Sent To  
Notes
2018-11-30 14:18:50RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-19 Cont ID  
Sent By pvalenti Date 2018-11-19 Time 10:55 Rev Time 0.00
Received By pvalenti Date 2018-10-04 Time 13:30 Sent To I
Notes
2018-10-05 13:30:41ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-17 Cont ID  
Sent By mcruz Date 2018-10-17 Time 08:58 Rev Time 0.00
Received By mcruz Date 2018-10-17 Time 08:57 Sent To  
Notes
***NONE***