2018-11-19 10:55:27 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION (SHOW DISTANCE | | OF GENERATOR TO OPERABLE OPENING). |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-10-23 |
Time |
18:27 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-10-23 |
Time |
18:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2018-12-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-12-14 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-12-14 |
Time |
10:18 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2018-12-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-12-07 |
Time |
16:48 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-12-07 |
Time |
16:44 |
Sent To |
|
|
Notes |
2018-12-07 16:49:55 | SUBMIT TWO COPIES OF A GAS PLAN. THE ONLY PLAN IN THE | | PERMIT APPLICATION FOLDER WAS A VOIDED GAS PLAN. WPB | | AMEEND. TO FBC SEC. 107.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-10-23 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-10-23 |
Time |
10:28 |
Sent To |
|
|
Notes |
2018-10-23 10:41:03 | 1) PLACE A NOTE ON THE PLANS THAT THE GENERATOR EXHAUST | | SHALL BE LOCATED A MINIMUM OF 10 FT. FROM BUILDING | | OPENINGS OR AS PER MANUF. INSTALLATION MANUAL. | | 2) THE ORIGINAL GAS PLAN ON FILE IN THE CITY RECORDS | | SHOWS THE LONGEST RUN AT 100 FEET. THIS DISTANCE SHALL | | BE USED IN THE SIZING OF ALL THE GAS PIPING. 2017 | | FBC-FUEL GAS SEC. 402.4.1, NOT 15 FEET. | | 3) THE MINIMUM SIZE METALLIC PIPE AT THE OUTLET OF THE | | GAS METER SHALL BE 1 1/2 INCHES FOR A LESS THAN 2 PSI | | SYSTEM ACCORDING TO TABLE 402.4 (2) OF THE 2017 | | FBC-FUEL GAS CODE. | | 4) THE MINIMUM SIZE OF THE PE PIPE SHALL BE 1 1/4 INCH | | PER TABLE 402.4 (21) OF THE 2017 FBC-FUEL GAS. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-12-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-12-14 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-12-14 |
Time |
10:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-12-11 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2018-12-11 |
Time |
08:08 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2018-11-20 |
Time |
14:19 |
Sent To |
|
|
Notes |
2018-11-30 14:18:50 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-11-19 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2018-11-19 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2018-10-04 |
Time |
13:30 |
Sent To |
I |
|
Notes |
2018-10-05 13:30:41 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-10-17 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-10-17 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-10-17 |
Time |
08:57 |
Sent To |
|
|
Notes |
|
|