Plan Review Details - Permit 18100210
Plan Review Stops For Permit 18100210
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-09 Cont ID  
Sent By scaldero Date 2018-10-09 Time 12:02 Rev Time 0.00
Received By scaldero Date 2018-10-09 Time 12:00 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-10-26 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-24 Time 15:33 Sent To  
Notes
2018-10-25 15:33:55RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-10-22 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-04 Time 13:26 Sent To  
Notes
2018-10-05 13:26:26ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By ccole Date 2018-10-26 Time 16:01 Rev Time 0.00
Received By ccole Date 2018-10-26 Time 15:53 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-22 Cont ID  
Sent By ccole Date 2018-10-22 Time 09:34 Rev Time 0.00
Received By ccole Date 2018-10-22 Time 09:34 Sent To I
Notes
2018-10-22 10:12:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18100210
 10/22/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PRIMARY PERMIT FOR THIS PROJECT LISTED ON THE
 APPLICATION WAS FOR A NEW MERCANTILE TENANT OCCUPANCY-
 GYPSY SURF- PERMIT #18020938. PLEASE PROVIDE A REVISED
 FLOOR PLAN TO SHOW THE LOCATION OF THE NEW PIZZA OVEN
 AND EXHAUST SYSTEM.
  
 2) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS OR A
 PRODUCT DATA SHEET FOR THE WOOD FIRED PIZZA OVEN TO
 VERIFY THE APPLIANCE IS LISTED AND LABELED IN
 ACCORDANCE WITH UL 2162- SEE SECTION 917.1 FBC M.
  
 3) INDICATE HOW MAKEUP AIR IS BEING PROVIDED PER
 SECTION 508.1 AND PROVIDE AN AIR BALANCE CALCULATION-
 SECTION 508.1.2 FBC M.
  
 4) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE EXHAUST FAN AND WALL BRACKET- SECTION 301.15 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  