Plan Review Stops For Permit 18100200
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By cthroop Date 2018-10-24 Time 16:59 Rev Time 0.00
Received By cthroop Date 2018-10-24 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-09 Cont ID  
Sent By pvalenti Date 2018-10-06 Time 12:35 Rev Time 0.00
Received By shill Date 2018-10-09 Time 17:35 Sent To  
Notes
2018-10-09 17:38:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE FBC B 603.1, ALLOWABLE MATERIALS IN NON
 COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2,
 ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 A FLAME SPREAD TEST WAS PROVIDED BUT THE SPECIMEN WAS
 TESTED WITH THE NONCOMBUSTIBLE BOARD TOWARDS THE FLAME.
 IT IS NOT CLEAR WHY THE UNDERLAYMENT (OR LVT FLOORING)
 WAS NOT FACING THE FLAME. COMPLIANCE NOT CLEAR. EITHER
 PROVIDE RATIONALE FOR TESTING IN THIS MANNER OR PROVIDE
 A TEST WITH THE UNDERLAYMENT TOWARDS THE FLAME.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-06 Cont ID  
Sent By pvalenti Date 2018-10-06 Time 12:35 Rev Time 0.00
Received By pvalenti Date 2018-10-04 Time 13:59 Sent To I
Notes
2018-10-05 13:59:19BLDG <5JK