Plan Review Details - Permit 18100171
Plan Review Stops For Permit 18100171
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By dbattles Date 2018-10-29 Time 09:28 Rev Time 0.00
Received By dbattles Date 2018-10-29 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-19 Cont ID  
Sent By dbattles Date 2018-10-19 Time 15:47 Rev Time 0.00
Received By dbattles Date 2018-10-19 Time 14:18 Sent To  
Notes
2018-10-19 15:48:49****CORRECTIONS****
 W.P.B. PERMIT: 18100171
 REVIEWED: OCTOBER 19, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC R = FBC RESIDENTIAL
  
 1. THE DESIGN PRESSURE SHEET HAS THE WRONG WIND SPEED.
 IT SHOULD BE 170 MPH, BUT IT WAS ENTERED AT 70MPH. THAT
 CAUSED THE DESIGN PRESSURES TO BE WRONG FOR ALL
 OPENINGS.
 PLEASE UPDATE THE DESIGN PRESSURE SHEET.
  
 2. THE PRESSURES WILL THEN NEED TO BE ADJUSTED ON THE
 SHUTTER SCHEDULE. NEXT ON THE SCHEDULE SHEET THE
 MOUNTING CONNECTION TYPE IS C5 FOR ALL SHUTTERS. THAT
 C5 CONNECTION TYPE CORRESPONDS TO SHEET 10 OF 13 ON
 PRODUCT APPROVAL. YOU SHOULD ONLY HIGHLIGHT THE COLUMN
 FOR CONNECTION TYPE AND THE ROW FOR THE PRESSURE.
 YOU NEED TO USE THE MINIMUM EDGE DISTANCE AT THE TOP OF
 TABLE THAT SUITS YOUR NEEDS.
 IF YOU WIND UP WITH A FILLED BOX THAT MEANS IT WON?T
 WORK AND YOU NEED TO USE DIFFERENT EDGE SPACE.
  
 3. THE SPAN IS THE HEIGHT (SEE PAGE 2 OF 13) OF
 SHUTTER.
  
 4. ADJUST SPANS ON SHUTTER SCHEDULE AND USE THE SPAN IN
 PRODUCT APPROVAL FOR CONNECTION SPACING ON PAGE 10 OF
 13.
  
 5. THE SHUTTERS ARE INSTALLED VERTICAL LIKE THE SPAN.
  
 6. ADJUST EDGE DISTANCE AND SPACING IF APPLICABLE. YOU
 CAN LEAVE AT 9? IF THIS MEETS REQUIREMENT, BUT IT MAY
 BE MORE THAN REQUIRED AS WELL.
  
 PLEASE FEEL FREE TO CALL AND DISCUSS, OR COME IN TO GO
 OVER PRODUCT APPROVAL TABLES.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-29 Cont ID  
Sent By dbattles Date 2018-10-29 Time 09:28 Rev Time 0.00
Received By dbattles Date 2018-10-22 Time 12:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-19 Cont ID  
Sent By dbattles Date 2018-10-19 Time 15:47 Rev Time 0.00
Received By dbattles Date 2018-10-05 Time 11:08 Sent To  
Notes
***NONE***